GB 26875.5-2011: [GB/T 26875.5-2011] Remote-monitoring system of urban fire protection -- Part 5: Functional requirements for receiving software
Status: Valid
| Standard ID | Contents [version] | USD | STEP2 | [PDF] delivered in | Standard Title (Description) | Status | PDF |
| GB 26875.5-2011 | English | 189 |
Add to Cart
|
3 days [Need to translate]
|
[GB/T 26875.5-2011] Remote-monitoring system of urban fire protection -- Part 5: Functional requirements for receiving software
| Valid |
GB 26875.5-2011
|
PDF similar to GB 26875.5-2011
Basic data
| Standard ID | GB 26875.5-2011 (GB26875.5-2011) |
| Description (Translated English) | [GB/T 26875.5-2011] Remote-monitoring system of urban fire protection -- Part 5: Functional requirements for receiving software |
| Sector / Industry | National Standard |
| Classification of Chinese Standard | C81 |
| Classification of International Standard | 13.220.20 |
| Word Count Estimation | 7,722 |
| Date of Issue | 2011-07-29 |
| Date of Implementation | 2012-05-01 |
| Quoted Standard | GB/T 17544-1998; GB 50440 |
| Regulation (derived from) | Announcement of Newly Approved National Standards No. 12 of 2011 |
| Issuing agency(ies) | General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China, Standardization Administration of the People's Republic of China |
| Summary | This Chinese standard relates to city fire remote monitoring system, fire alarm system and the information terminal admissibility admissibility of software terminology and definitions, basic requirements, functional requirements and test methods. This standard applies to the city fire remote monitoring system and fire alarm receiving system information terminal admissibility of software installation. |
GB 26875.5-2011: [GB/T 26875.5-2011] Remote-monitoring system of urban fire protection -- Part 5: Functional requirements for receiving software
---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Remote-monitoring system of urban fire protection.Part 5. Functional requirements for receiving software
ICS 13.220.20
C81
National Standards of People's Republic of China
City fire remote monitoring system
Part 5. software functionality requires acceptance
Part 5. Functionalrequirementsforreceivingsoftware
Issued on. 2011-07-29
2012-05-01 implementation
Administration of Quality Supervision, Inspection and Quarantine of People's Republic of China
Standardization Administration of China released
Foreword
Part 4, Chapter 5 are mandatory, the rest are recommended.
GB 26875 "city fire remote monitoring system" is divided into six parts.
--- Part 1. User information transfer means;
--- Part 2. Communications server software functionality requires;
--- Part 3. alarm transmission network communication protocol;
--- Part 4. Basic data items;
--- Part 5. admissibility software functional requirements;
--- Part 6. information management software functional requirements.
This section GB of Section 526 875.
This section drafted in accordance with GB/T 1.1-2009 given rules.
This part of the National Fire Fire Communications Standardization Technical Committee Technical Committee (SAC/TC113/SC14) centralized.
This section is responsible for drafting unit. Shenyang Fire Research Institute Ministry of Public Security.
Participated in the drafting of this section. Wansheng (China) Technology Co., Ltd., Gulf Fire Network Limited, Shenyang Mabel Control Co.,
Tongfang Co., Ltd., Guangdong 100 Xun Information Technology Co., Ltd., Shanghai VTech Communications, Jiangxi Shengan development of urban security information
Ltd., Beijing Science and Technology Development Co., Ltd. Qingdao WebEx.
The main drafters of this section. Suihu Lin, Qu Li, Liu Haixia, Ernst & Young Gu, Bo, Yuan Guobin, Hu Rui fees plunger. STUDIES OF Yim,
Zou Zhigang, Liang Weifeng, Chen Xingyu, Deng Tao commentary, Jun.
City fire remote monitoring system
Part 5. software functionality requires acceptance
1 Scope
This section GB 26875 specifies the city fire remote monitoring system and fire alarm system receiving information terminal receiving software
Terms and definitions, basic requirements, functional requirements and test methods.
This section applies to the city fire remote monitoring system and fire alarm system receiving information terminal installation of software acceptance.
2 Normative references
The following documents for the application of this document is essential. For dated references, only the dated version suitable for use herein
Member. For undated references, the latest edition (including any amendments) applies to this document.
GB/T 17544-1998 Information technology - Software packages - Quality requirements and testing
GB 50440 city fire remote monitoring system technical specifications
3 Terms and Definitions
GB 50440 and defined by the following terms and definitions apply to this document.
3.1
Fire information terminal firealarminformationterminal
Provided fire communication and command centers or other Alarming center for receiving city fire remote monitoring center received alarm system to send
Fire alarm network terminal user information.
4 Basic requirements
Receiving software should meet the following basic requirements.
a) accept the use of Chinese software interface should display;
b) operation acceptance process should be a clear indication;
c) Software exceptions should not occur during operation;
d) receiving the software user documentation should meet GB/T 17544-1998 of 3.2 requirements.
5 Functional requirements
5.1 General functional requirements accepted software
5.1.1 or later running through login, it should accept automatically monitor the working status.
5.1.2 should have the character information display interface and the geographic information display screen, respectively, display text information and geographic information.
5.1.3 screen should display the following information.
a) not receiving information;
b) the date and clock information;
c) the software version information;
d) receiving agent, the receiving operator information;
e) acceptance or who withdrew seat status information.
The above information, a) items should not be overwritten.
5.1.4 should be able to record, start and stop time and personnel to inquire about their login, logout time, notes and other duty.
5.1.5 should be accepted, query and exit operating authority.
5.1.6 should be standard city fire remote monitoring system clock synchronization.
5.1.7 should have irregularities prompts.
5.2 alarm receiving system software functionality requires acceptance
5.2.1 should be able to receive, display, fire alarm and inquiry information recording user information transmission means, operating state building fire
information.
5.2.2 should be able to receive, display, record and alarm information inquiry system communication sent by the server.
5.2.3 receive all kinds of information, it should be able to drive sound and display interface device emits sound signals and the display prompts. Fire alarm beeping letter
Number and prompts should be clearly distinguished from other information, and display and process priority. Acoustic signal should be able to eliminate the manual, when you receive a new message,
Acoustic signal should start again. After receiving the information, the corresponding acoustic signal, display the prompt should automatically eliminated.
5.2.4 receiving user information transmission means fire alarm, fault status information, should be able to show the following.
a) the information received, the user name, address, contact name, telephone, unit, type, related systems or components, status, etc.
information.
b) the user's geographic information, location information of the location information building fire in the building as well as parts; the part position in the department
EC plan should be clearly displayed.
c) the same type of history information recording the user information transmission means for sending at least 25 of these.
5.2.5 The fire alarm should be able to confirm the information and documented.
5.2.6 should be able to transfer information to a fire terminal confirmed fire alarm information, the information should include. alarm network user name, address,
Contact name, phone number, name of the building, the building where the alarm detailed positions, the monitoring center receiving member number or name, etc.; and to receive,
Confirm the time display and record fire information returned from the terminal, the command center receiving member number or name and other information; when a communication failure alarms.
5.2.7 should be able to fault status information of the user information transmission means to verify the record, query and statistics related to Internet users
The relevant departments to send personnel or verified failure information; the results of the fault should be able to search.
5.2.8 Test should be able to send commands to the user manual information transmission means the communication link, the user information transmission means test, the test failure
Alarms should be defeated; and to record, display and query results.
5.3 fire information terminal receiving software functional requirements
5.3.1 should be able to receive, display, record and query the alarm monitoring center receiving the fire alarm system to send the information.
5.3.2 received the internal fire alarm systems and alarm information, should be able to drive sound and display interface device emits sound signals and the display mention
Shown. Fire alarms sound cue and prompts alarm information should be clearly distinguished from, and display and process priority. Acoustic signal should
Can eliminate the manual, when you receive a new message, the acoustic signal should start again. After receiving the information, the corresponding acoustic signal, display the prompt should automatically eliminated.
5.3.3 When receiving the fire alarm information, alarm network should be able to display the user's name, address, contact name, phone number, building name, newspaper
Police point where the location of the building, networking, users of geographic information, the monitoring center receiving member number or name, the reception time information; after manual confirmation
After confirmation time feedback to the monitoring center, command center staff received number or name and other information; when a communication failure alarms.
5.3.4 should be able to detect the communication status between the monitoring center, there should be a fault alarm and can record and check the type of fault, failure
And the elimination of time.
6 Test methods
6.1 General
6.1.1 measured by parties accepting packages and user documentation.
6.1.2 before the test, in accordance with the relevant requirements of the user documentation for hardware configuration and software installation, connection-related system equipment, complete software, each
Entry is set so that the relevant system equipment in proper working condition.
6.1.3 alarm receiving system acceptance testing process by the method of software functions 6.2, 6.3, fire information receiving terminal software functionality testing process
According to the method of 6.2, 6.4, respectively, with reference to the corresponding user documentation process operation carried out one by one.
6.2 General function test methods
6.2.1 software running accept, observe and record the admissibility of the software into operation situation.
6.2.2 See accepted software interface and text information display geographic information display interface situation.
6.2.3 Check and record the received software information display, observe the information is not received additional information not covered by the case, observe and record the current
Members receiving status information display case.
6.2.4 accept different member logout, login duty notes, withdraw and accept software running operation, recording the operating time and related
Content, view the operation time and the content is consistent with the case by accepting the software recorded query window.
6.2.5 View Software Operation accepting the role permission settings and circumstances.
When modify the software to run acceptance; 6.2.6 to modify the standard clock system, observe and record the accepted standard software and system clock synchronization conditions
Bell, clock synchronization application to perform the operation, observe and record the accepted standard software and system clock synchronization situation.
6.2.7 man-made illegal operations, such as the unauthorized operation, observe and record the software prompts accept the situation.
6.3 alarm receiving software function test methods accepted
6.3.1 user information transmission device of the machine as well as fire protection facilities and user information transmission device connected, sending fire alarm
Building fire facilities and operating status information at least three, in accepting the system software is displayed on the screen to accept the received information is accepted.
Observe and record the receiving software to receive, display information and time conditions; viewing software recorded cases accepted by software query window.
6.3.2 artificially created internal fault alarm system, observe and record the receiving software to receive, display case; by accepting the query window to view software
System Alarm recording situation.
6.3.3 user information transmission device of the machine as well as fire protection facilities and user information transmission device connected, sending fire alarm
Building fire facilities and operating status information at least three, and the fire alarm is not the first article sent; receiving software receives the first message
After manually eliminate acoustic signal; together artificially created internal system failure, such as closing fire information terminal; receiving receiving information; execution View
Observe and record the following elements.
a) receiving acoustic signals sound emanating from the device driver software and accept the software interface display case;
b) message queue display without accepting;
c) the elimination of manual re-start situation acoustic signal acoustic signal;
Sound cue d) fire alarm information with other information beeping difference signal;
e) fire alarm information display priority display case cue;
Sound f) within the system and fault information cue prompts the case;
g) Information received after the acoustic signal, the display prompts automatic elimination situation.
6.3.4 By building fire facilities and user information transmission device connected, sending fire alarm and fault status information, receiving software
After receiving the accept operation performed, observed and recorded the display.
6.3.5 user information transmission apparatus of the present building or fire fighting facilities and user information transmission device is connected, the transmission of fire alarms,
After accepting the software to receive, conduct police intelligence to confirm the operation, observe and record the fire alarm software received confirmation information, the recording archiving operations
Tips and Treatment.
6.3.6 confirm a fire alarm, fire information terminal after receiving fire information, confirm the information, observe and record the information content and fire
Police received information terminal, the terminal profile case of fire information return; disconnect the communication link with the fire information terminal, reconfirm
A fire alarm, observe and record the alarm prompts the communication failure; the view of the fire from the alarm receiving software via a query window
Information accepted the situation.
6.3.7 user information transmission apparatus of the present building or fire fighting facilities and user information transmission device is connected, the transmission fault status information,
After accepting the software to receive, verify, inform, receiving operation, observe and record the receiving state to verify the software fault information, inform, and acceptance
Time situation; view fault status information received by the results recorded case of software query window.
6.3.8 Test Artificial send commands to a user information transmission means, observe and record the test cases and test results; disconnect the user
Communication link information transmission means, once again initiate the test command, observe and record the test cases and test results; acceptance by software query window
Check test records mouth situation.
6.4 fire information terminal software function test methods accepted
6.4.1 confirmed by the alarm system receiving a fire alarm, a fire was observed and recorded information receiving terminal software to receive, display information and
Time situation.
6.4.2 confirmed by the alarm system receiving a fire alarm, fire alarm receiving software receives the information terminal to the first information, eliminate manual
In addition to the acoustic signal; together artificially created internal system failure, such as disconnection of the communication link between the terminal and the monitoring center; receiving fire alarm
And fault information within the system; the implementation process to observe and record the following elements.
a) receiving acoustic signals sound emanating from the device driver software and accept the software interface display case;
b) did not accept the information display area information queue display case;
c) the elimination of manual re-start situation acoustic signal acoustic signal;
Sound d) fire alarm cue with the internal system fault information beeping difference signal;
Sound internal e) information system failures and prompts cue the case;
f) Information received after the acoustic signal, display the prompt elimination of the situation.
6.4.3 confirmed by the alarm system receiving a fire alarm, fire alarm receiving software receives the information terminal after receiving an operator to observe and
Record display; after manual confirmation, observe and record the alarm receiving system receiving software receives feedback situation; accepted by the alarm system again
Reconfirmed a fire alarm, fire alarm receiving software receives the information terminal after manual confirmation before the communication link disconnect between the monitoring center
Road, and then manually confirm the operation, observe and record prompts the communication failure; the view of the fires reported to the software by accepting the query window
Police received information recording situation.
6.4.4 disconnect the communication link between the monitoring center, failure to observe and record prompt time, the alarm message situation; recovery
Communication links between the monitoring center, failure to observe and record the time and signal cancellation conditions; view fault record by receiving software query window
Recording situation.
1102-
5.57862
Rights Proprietary Rights Reserved
ISBN. 155 066 · 1-43699
Tips & Frequently Asked Questions:
Question 1: How long will the true-PDF of GB 26875.5-2011_English be delivered?
Answer: Upon your order, we will start to translate GB 26875.5-2011_English as soon as possible, and keep you informed of the progress. The lead time is typically 1 ~ 3 working days. The lengthier the document the longer the lead time.
Question 2: Can I share the purchased PDF of GB 26875.5-2011_English with my colleagues?
Answer: Yes. The purchased PDF of GB 26875.5-2011_English will be deemed to be sold to your employer/organization who actually pays for it, including your colleagues and your employer's intranet.
Question 3: Does the price include tax/VAT?
Answer: Yes. Our tax invoice, downloaded/delivered in 9 seconds, includes all tax/VAT and complies with 100+ countries' tax regulations (tax exempted in 100+ countries) -- See Avoidance of Double Taxation Agreements (DTAs):
List of DTAs signed between Singapore and 100+ countriesQuestion 4: Do you accept my currency other than USD?
Answer: Yes. If you need your currency to be printed on the invoice, please write an email to
[email protected]. In 2 working-hours, we will create a special link for you to pay in any currencies. Otherwise, follow the normal steps: Add to Cart -- Checkout -- Select your currency to pay.