HOME   Cart(0)   Quotation   About-Us Tax PDFs Standard-List Powered by Google www.ChineseStandard.net Database: 189760 (15 Mar 2025)

GB/T 7725-2022 PDF English


Search result: GB/T 7725-2022 English: PDF (GB/T7725-2022)
Standard IDContents [version]USDSTEP2[PDF] delivered inName of Chinese StandardStatus
GB/T 7725-2022English1280 Add to Cart 0-9 seconds. Auto-delivery. Room air conditioner Valid
GB/T 7725-2004EnglishRFQ ASK 9 days Room air conditioners Obsolete
GB/T 7725-1996EnglishRFQ ASK 9 days Room air conditioners Obsolete
GB/T 7725-1987EnglishRFQ ASK 3 days Room air conditioners Obsolete


PDF Preview: GB/T 7725-2022


GB/T 7725-2022: PDF in English (GBT 7725-2022)

GB/T 7725-2022 GB NATIONAL STANDARD OF THE PEOPLE’S REPUBLIC OF CHINA ICS 91.140.30 CCS Y 61 Replacing GB/T 7725-2004 Room air conditioner 房间空气调节器 (ISO 5151:2017, Non-ducted air conditioners and heat pumps - Testing and rating for performance, NEQ) ISSUED ON: OCTOBER 12, 2022 IMPLEMENTED ON: MAY 01, 2023 Issued by: State Administration for Market Regulation; Standardization Administration of the People's Republic of China. Table of Contents Foreword ... 3 1 Scope ... 6 2 Normative references ... 6 3 Terms and definitions, symbols ... 7 4 Product classification ... 24 5 Technical requirements ... 27 6 Tests ... 33 7 Inspection rules ... 51 8 Marks, packaging, transportation and storage ... 56 Annex A (normative) Multi-split room air conditioners ... 60 Annex B (normative) Calculation of seasonal energy consumption efficiency of room air conditioners ... 66 Annex C (informative) Occurrence time of each temperature calculated based on the meteorological data of a typical city (taking Nanjing as an example) ... 95 Annex D (normative) Tests and calculation methods for cooling capacity and heating capacity ... 97 Annex E (informative) Measuring instruments ... 120 Annex F (informative) Air volume measurement ... 123 Annex G (informative) Cooling condensed water measurement ... 130 Annex H (informative) Diagram of heating capacity test procedure in D.4 ... 131 Annex I (normative) Measurement of noise ... 136 Annex J (normative) Standby power test ... 143 Annex K (informative) Grading of some performances ... 144 Annex L (informative) Test method for temperature control fluctuation ... 147 Annex M (informative) Refrigerant enthalpy method ... 149 Annex N (informative) Enthalpy method of outdoor side air ... 152 Annex O (informative) Verification test method for indoor side calorimeters ... 156 Annex P (informative) Verification test method for outdoor side calorimeters ... 158 Annex Q (informative) Verification test method for balance calorimeter ... 160 Bibliography ... 161 Room air conditioner 1 Scope This document specifies the terms and definitions, product classification, technical requirements, tests, inspection rules, marks, packaging, transportation and storage for room air conditioners. This document applies to household and similar free-supply room air conditioners (hereinafter referred to as air conditioners) that use air-cooled or water-cooled condensers, fully enclosed motor-compressors, and whose rated cooling capacity is below 14000W for the purpose of creating a comfortable indoor environment), as well as ducted air conditioners whose rated cooling capacity is less than 8kW and external static pressure is less than 25Pa. This document does not apply to the following products and systems: - portable air conditioners; - individual components that cannot form a complete cooling system; - air conditioners using absorption cooling cycle; - other ducted air conditioners. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. GB/T 191, Packaging and storage marks GB/T 1766, Paints and varnishes - Rating schemes of degradation of coats (ISO 4628:2003, NEQ) GB/T 2423.3, Environmental testing - Part 2: Testing method - Test Cab: Damp heat, steady state (GB/T 2423.3-2016, IEC 60068-2-78:2012, IDT) GB/T 2423.17, Environmental testing for electric and electronic products - Part 2: Test method - Test Ka: Salt mist (GB/T 2423.17-2008, IEC 60068-2-11:1981, IDT) GB/T 2828.1, Sampling procedures for inspection by attributes - Part 1: Sampling 3.1.2 heat pump A cooling system that heats up the indoor air by converting the flow direction of the refrigerant in the cooling system, absorbing heat from the low temperature outdoor air and releasing heat to the room. NOTE: Air conditioners with heat pump heating capabilities are called heat pump air conditioners. 3.1.3 supplementary electrical heating devices An electric heating device used with a heat pump for heating. 3.1.4 cooling capacity The sum of the heat removed from the room per unit time when the air conditioner is in cooling operation under any given working conditions and conditions. NOTE: The unit is watts (W). The rated value of cooling capacity includes rated cooling capacity, rated intermediate cooling capacity, rated maximum cooling capacity and rated minimum cooling capacity. Among them, the rated intermediate cooling capacity is within the range of 50% of the rated cooling capacity ± 100W. 3.1.5 cooling power input The power consumed by the air conditioner during the cooling capacity test. NOTE: The unit is watts (W). The rated value of cooling power input includes rated cooling power input and rated intermediate cooling power input. 3.1.6 heating capacity When the air conditioner is in heating operation under any given working conditions and conditions, the sum of the heat sent into the room per unit time. NOTE 1: The unit is watts (W). The rated value of heating capacity includes rated heating capacity, rated intermediate heating capacity, rated maximum heating capacity, rated minimum heating capacity and rated low temperature heating capacity. Among them, the rated intermediate heating capacity is within the range of 50% of the rated heating capacity ±100W. NOTE 2: The heating capacity is only the heating capacity of the heat pump, not including the heating capacity of the supplementary electric heating device. 3.1.7 heating power input The power consumed by the air conditioner during the heating capacity test. NOTE: The unit is watts (W). The rated value of heating power input includes rated heating power input, rated intermediate heating power input and rated low temperature heating power input. 3.1.8 effective power input The average electric power input into the air conditioner within the specified time, including: a) the power input at which the compressor operates; b) the power input of the electric heating device used only for defrosting; c) the power input to all control and safety devices; d) the power input to heat exchange conveyors (fans, pumps, etc.). NOTE: The unit is watts (W). The power input of the supplementary heating device is not included. 3.1.9 energy efficiency ratio; EER Under any given working condition and specified conditions, when the air conditioner is in cooling operation, the ratio of cooling capacity to effective power input. NOTE: The unit is watts per watt (W/W). 3.1.10 coefficient of performance; COP Under any given working condition and specified conditions, when the air conditioner is in heating operation, the ratio of the heating capacity to the effective power input. NOTE: The unit is watts per watt (W/W). 3.1.11 standard air Dry air at 20°C and at a standard barometric pressure of 101.325 kPa, having a mass density of 1.204 kg/m3. 3.1.12 indoor discharge air-flow The air volume sent by the indoor unit of the air conditioner to the room or air supply area per unit time when the ventilation and exhaust doors of the air conditioner for the exchange of indoor and outdoor air are completely closed (if any) and operated under specified conditions. NOTE: The unit is cubic meter per second (m3/s) or cubic meter per hour (m3/h). 3.1.13 room-type calorimeter A test device consisting of two adjacent rooms with a partition wall in between. One room is used as interior. The other room is used exterior. Each room is air-conditioned. Its cooling, heating and water volume can be measured and controlled. They are used to balance the cooling capacity and dehumidification capacity of the air conditioner NOTE: When running at full load, all indoor units and compressors work, unless the indoor units and compressors are controlled by the automatic controller of the air conditioner. 3.1.22 multi-split room air conditioner A device that supplies conditioned air to multiple rooms. NOTE: It is mainly composed of one outdoor unit connected to more than one indoor unit, which can realize the combined system of multiple indoor units working at the same time, some indoor units working at the same time or a single indoor unit working. Hereinafter it is referred to as "multi- split air conditioner". 3.1.23 standby mode When the air conditioner is connected to the mains power supply, one or more of the following user-oriented functions or protection functions are provided, and any product mode is continuous: - other modes can be triggered by triggering remote switches (including remote control), internal sensors, timers; - information or status display including a clock; - sensor-based functionality. NOTE: In this mode, protective devices such as crankcase heaters do not work. 3.1.24 cooling load factor; CLF During the cooling operation of the air conditioner, when the air conditioner is intermittently operated by turning on (ON) and off (OFF) the indoor temperature regulator, within one cycle of intermittent operation consisting of ON time and OFF time, the ratio of the heat removed from the room to the heat removed from the room during continuous cooling operation during this cycle time. 3.1.25 heating load factor; HLF During the heating operation of the air conditioner, when the air conditioner is intermittently operated by turning on (ON) and off (OFF) the indoor temperature regulator, within one cycle of intermittent operation consisting of ON time and OFF time, the ratio of the heat delivered to the room to the heat delivered to the room in continuous heating operation during this cycle time. 3.1.26 part load factor; PLF Under the same temperature and humidity conditions, the ratio of the energy consumption efficiency of the air conditioner during intermittent operation to the energy consumption efficiency of continuous operation. 3.1.27 degradation coefficient; CD The coefficient by which the efficiency of the air conditioner decreases due to intermittent operation. 3.1.28 seasonal energy efficiency ratio; SEER During the cooling season, the ratio of the sum of the heat removed from the room to the sum of the electricity consumed by the air conditioner during cooling operation. 3.1.29 heating seasonal performance factor; HSPF During the heating season, when the air conditioner is in heating operation, the ratio of the sum of the heat sent into the room to the sum of the electricity consumed. 3.1.30 annual performance factor; APF During the cooling season and heating season of the air conditioner, the ratio of the sum of the cold removed from the indoor air and the heat sent into the room to the sum of the electricity consumed during the same period. 3.1.31 cooling seasonal total energy; CSTE During the cooling season, the total amount of electricity consumed by the air conditioner during cooling operation. NOTE: The unit is watt-hour (W·h). 3.1.32 heating seasonal total energy; HSTE During the heating season, the total amount of electricity consumed by the air conditioner during heating operation. NOTE: The unit is watt-hour (W·h). 3.1.33 annual power consumption; APC The sum of the cooling seasonal total energy in the cooling season and the heating seasonal total energy in the heating season. NOTE: The unit is watt-hour (W·h). 3.1.34 cooling load The cooling capacity when the outdoor temperature is 35°C is taken as the cooling building load. The straight line connecting this point with 23°C (0 load point) is the cooling load line. The intersection of the vertical line at the overtemperature point and the cooling load line is called as cooling load. 5.2.2.1 Rated cooling capacity Test according to 6.3.2. The measured cooling capacity of fixed speed room air conditioner and variable speed room air conditioner shall not be less than 95% of the rated cooling capacity. 5.2.2.2 Rated intermediate cooling capacity Test according to 6.3.2. The measured intermediate cooling capacity of variable speed air conditioners shall not be less than 95% of the rated intermediate cooling capacity. 5.2.2.3 Rated minimum cooling capacity Test according to 6.3.2. When the indicated value of the minimum cooling capacity is less than 1 kW, the measured minimum cooling capacity of the variable speed air conditioner shall not be greater than 120% of the indicated value. When the indicated value of the minimum cooling capacity is not less than 1 kW, the measured minimum cooling capacity of the variable speed air conditioner shall not be greater than 105% of the indicated value (or not greater than the indicated value + 200W, whichever is larger). 5.2.2.4 Rated maximum cooling capacity Test according to 6.3.2. The measured maximum cooling capacity of variable speed air conditioners shall not be less than 95% of the rated maximum cooling capacity. 5.2.3 Cooling power input 5.2.3.1 Rated cooling power input Test according to 6.3.3. The measured cooling power input of fixed speed and variable speed air conditioners shall not exceed 110% of the rated cooling power input. For every 300 W cooling capacity of the water-cooled air conditioner, add 10 W as the rated power input of the cooling system water pump and cooling water tower fan. 5.2.3.2 Rated intermediate cooling power input Test according to 6.3.3. The measured intermediate cooling power input of variable speed air conditioners shall not be greater than 110% of the rated intermediate cooling power input. 5.2.3.3 Rated minimum cooling power input Test according to 6.3.3. When the indicated value of the minimum cooling power input is less than 500 W, the measured minimum cooling power input of the variable speed air conditioner shall not be greater than 120% of the indicated value. When the indicated value of the minimum cooling power input is not less than 500 W, the actual measured minimum cooling power input of the variable speed air conditioner shall not be greater than 110% of the indicated value (or not greater than the indicated value + 100 W, whichever is larger). 5.2.3.4 Rated maximum cooling power input Test according to 6.3.3. The measured maximum cooling power input of variable speed air conditioners shall not be greater than 110% of the rated maximum cooling power input. 5.2.4 Heating capacity 5.2.4.1 Rated heating capacity Test according to 6.3.4. The measured heating capacity of fixed speed and variable speed air conditioners shall not be less than 95% of the rated heating capacity. 5.2.4.2 Rated intermediate heating capacity Test according to 6.3.4. The measured intermediate heating capacity of variable speed air conditioners shall not be less than 95% of the rated intermediate heating capacity. 5.2.4.3 Rated low temperature heating capacity When testing according to the method in 6.3.4 and under low temperature heating conditions, the measured low temperature heating capacity of fixed speed and variable speed air conditioners shall not be less than 95% of the rated low temperature heating capacity. 5.2.4.4 Rated minimum heating capacity Test according to 6.3.4. When the indicated value of the minimum heating capacity is less than 1 kW, the actual measured minimum heating capacity of the variable speed air conditioner shall not be greater than 120% of the indicated value. When the indicated value of the minimum heating capacity is not less than 1 kW, the actual measured minimum heating capacity of the variable speed air conditioner shall not be greater than 105% of the indicated value (or not greater than the indicated value + 200W, whichever is larger). 5.2.4.5 Rated maximum heating capacity Test according to 6.3.4. The rated maximum heating capacity of variable speed air conditioners shall not be less than 95% of the indicated value. 5.2.5 Heating power input 5.2.5.1 Rated heating power input Test according to 6.3.5. The measured heating power input of the fixed speed and variable speed air conditioners shall not be greater than 110% of the rated heating power input. min of starting and running. It is not allowed to operate thereafter. When the motor overload protector does not reset within the first 5 min of operation, if it is reset within 30 min after shutdown, it shall run continuously for 1 h. 5.2.8 Minimum operating cooling and freezing The requirements for testing according to the test method in 6.3.8 are as follows: a) The parts of the air conditioner shall not be deformed or damaged to affect the normal operation of the air conditioner. b) The area of frost condensed on the windward surface of the indoor evaporator shall not be greater than 50% of the windward area of the evaporator or the air volume drop shall not exceed 25% of the initial air volume. If the frosting area on the windward surface of the evaporator is not easy to be seen by visual inspection or the air volume cannot be measured, the requirements of c) shall be met. c) When the compressor cannot be automatically started and stopped during the test, if the coil temperature is measured, compared with the initial temperature, the temperature measured at the midpoint of each coil within a period of at least 20 min of operation shall not be lower than 2 K. If the suction pressure is measured, the corresponding saturated suction temperature shall be converted. During at least 20 min of operation, the saturated suction temperature shall not be lower than 2 K, compared with the initial saturated suction temperature. When the compressor can start and stop automatically during the test, if the coil temperature is measured, during the test, compared with the initial temperature, the temperature measured at the midpoint of the coil 10 min after the compressor starts shall not be lower than 2 K. If the suction pressure is measured, the corresponding saturated suction temperature shall be converted. During the test period, the saturated suction temperature 10 min after the start of the compressor shall not be lower than 2 K, compared with the initial saturated suction temperature. 5.2.9 Freeze dripping Test according to 6.3.9. There shall be no visible ice falling, water dripping or blowing out at the indoor side of the air conditioner. 5.2.10 Maximum operating heating The requirements for testing according to the test method of 6.3.10 are as follows: a) All parts of the air conditioner shall not be deformed or damaged to affect the normal operation of the air conditioner. b) During the first hour of continuous operation of the air conditioner, its motor overload protector shall not trip. c) When the air conditioner is stopped for 3 min, it will start to run continuously for 1 h. However, the motor overload protector is allowed to trip within the first 5 min of starting and running. It is not allowed to operate thereafter. When the motor overload protector does not reset within the first 5 min of operation, if it is reset within 30 min after shutdown, it shall run continuously for 1 h. 5.2.11 Minimum operating heating When the test is carried out according to 6.3.11, the safety device shall not trip off during the 1h test run of the air conditioner. 5.2.12 Condensation and condensed water removal capacity The requirements for testing according to 6.3.12 are as follows: a) The condensation on the outer surface of the air conditioner shell shall not drip. The indoor air supply shall not contain water droplets. b) When the air conditioner adopts the method of condensed water splashing the condenser, the condensed water shall not drip or blow out from the air conditioner. 5.2.13 Automatic defrosting The requirements for testing according to 6.3.13 are as follows: a) In the defrosting cycle, the duration that the air supply temperature on the indoor side is lower than 18°C is not more than 1 min. b) After the air conditioner is defrosted, the frost layer of the outdoor heat exchanger shall be completely melted. 5.2.14 Noise The requirements for testing according to 6.3.14 are as follows: a) When the air conditioner is tested for noise in a semi-anechoic room, the noise test value shall not be greater than the upper limit of the indicated value (indicated value + upper deviation). The upper deviation of the manufacturer's indicated value for air conditioner noise is +3dB(A). b) There shall be no abnormal noise and vibration when the air conditioner is in use. 5.2.15 Seasonal energy consumption efficiency Air-cooled air conditioners are tested according to methods in 6.3.2~6.3.5. Calculation of seasonal energy consumption efficiency is according to Annex B. The calculated value shall not be less than 95% of the declared value of seasonal energy consumption efficiency of the air conditioner. conditions, then use the temperature controller to set the outlet air temperature to the lowest or highest temperature allowed by the air conditioner. Test under this state. 6.2.4 During the cooling capacity and heating capacity tests, the ventilation door and exhaust door (if any), fan speed, and guide grille for exchanging indoor and outdoor air of the air conditioner shall be set within the normal use adjustment control range according to the manufacturer's regulations. If not specified by the manufacturer, the ventilation door and exhaust door (if any) for exchanging indoor and outdoor air of the air conditioner are completely closed. Fan speed, guide grills are adjusted to the position of maximum cooling capacity or maximum heating capacity without violating the manufacturer's regulations. 6.2.5 No changes shall be made to the air conditioner except for the connection of devices and instruments required for the test in the prescribed manner. 6.2.6 The air conditioner fan speed and air resistance shall not be changed during the test. The test results shall adopt the values corrected according to the standard atmospheric pressure. 6.2.7 When using the indoor air-enthalpy test method to carry out the cooling capacity and heating capacity tests, see the measurement method for air volume in Annex F. The test shall be carried out under the condition that the external static pressure is 0Pa. NOTE: Additional guidelines for air flow measurement can be found in ISO 3966 and GB/T 2624.1. 6.2.8 The installation of air conditioners shall meet the following requirements. a) Follow the installation procedure and accessories specified by the manufacturer for installation. If the unit has multiple installation methods, all tests shall be carried out under the most unfavorable installation method. Requirements such as the installation distance from the air conditioner to the wall and the size of the protrusion through the wall shall follow the relevant recommendations of the manufacturer. b) For ducted air conditioners with a rated cooling capacity of less than 8kW and an outlet static pressure of less than 25Pa, it shall be tested under the condition of free air supply. c) If necessary, after evacuating the refrigerant circuit of the air conditioner, charge the refrigerant according to the refrigerant type and charge amount specified by the manufacturer. d) The length of the connecting pipe between the indoor unit and the outdoor unit of the split-type air conditioner during the test shall not be less than 5 m. Or according to the manufacturer's regulations, take the larger value. The length of the connecting pipe is the actual length, not the equivalent length. Elbows, pipeline branches, connection boxes or other filters used in connection operations ......
 
Source: Above contents are excerpted from the PDF -- translated/reviewed by: www.chinesestandard.net / Wayne Zheng et al.