0-9 seconds. Auto-delivery.
|
Code for design of noise control of industrial enterprises [including section: Explanation of Provisions]
| Valid |
Standards related to (historical): GB/T 50087-2013
PDF Preview
GB/T 50087-2013: PDF in English (GBT 50087-2013) GB/T 50087-2013
GB
NATIONAL STANDARD
OF THE PEOPLE’S REPUBLIC OF CHINA
UDC
Code for design of noise control of industrial enterprises
ISSUED ON. NOVEMBER 29, 2013
IMPLEMENTED ON. JUNE 1, 2014
Issued by. Ministry of Housing and Urban-Rural Development;
General Administration of Quality Supervision, Inspection
and Quarantine of the People’s Republic of China.
3. No action is required - Full-copy of this standard will be automatically &
immediately delivered to your EMAIL address in 0~60 minutes.
NATIONAL STANDARD
OF THE PEOPLE’S REPUBLIC OF CHINA
Code for design of noise control of industrial enterprises
Main drafting organization.
Ministry of Housing and Urban-Rural Development of the People’s
Republic of China
Approved by.
Ministry of Housing and Urban-Rural Development of the People’s
Republic of China
Date of implementation.
June 1, 2014
China Architecture & Building Press
Beijing 2013
Foreword
This Code was revised by Beijing Municipal Institute of Labor Protection
jointly with organizations concerned on basis of the previous national
standard "Specifications for the design of noise control system in industrial
enterprises" (GBJ 87-85) according to the requirements of Building Code
[2009] No. 88 issued by the Ministry of Housing and Urban-Rural
Development - “Notice on printing the development and revision plan of
national engineering construction standards from in 2009”.
During the process of revising this Code, the drafting group carried out
extensive investigations, carefully summarized the practical experience,
made reference to relevant international standards and advanced standards
of other countries, widely solicited for opinions, made improvement, reviewed
and finalized this Code.
This Code comprises eight clauses. Its main technical contents are. General
provisions, Terms, Design limits of noise control of industrial enterprises,
Industrial enterprises in the overall design of noise control, Sound insulation
design, Muffler design, Sound absorption design, and Vibration isolation
design.
The main technical contents revised in this Code are. 1. added the content on
limit for impulsive noise; 2. made an appropriate modification on the noise
limits for various workplaces; 3. modified the relevant clauses on the noise
and vibration control measures.
This Code shall be under management of the Ministry of Housing and
Urban-Rural Development. The routine management and the interpretation of
specific technical contents shall be performed by Beijing Municipal Institute of
Labor Protection. During the process of implementing this Code, the relevant
opinions and advices, whenever necessary, can be sent to Beijing Municipal
Institute of Labor Protection (Address. No. 55, Taoranting Road, Xicheng
District, Beijing, 100054, China).
Main drafting organization of this Code. Beijing Municipal Institute of Labor
Protection
The drafting organizations of this Code. Institute of Acoustics, Chinese
Academy of Sciences, China Academy of Building Research, China
Architecture Design and Research Group, Chinese Research Academy of
Environmental Science, National Industrial Standard Rating Station of
Building Materials, Beijing Center for Disease Prevention and Control, Beijing
Urban Construction Science Technology Promoting Association, North China
Institute of Science and Technology, Beijing Greentec Acoustic Engineering
Table of Contents
Foreword ... 4
1 General provisions ... 7
2 Terms ... 7
3 Design limits of noise control of industrial enterprises... 9
4 Industrial enterprises in the overall design of noise control ... 10
5 Sound insulation design ... 13
6 Muffler Design ... 20
7 Sound Absorption Design ... 26
8 Vibration Isolation Design ... 29
Explanation of wording in this Code ... 30
Normative References ... 31
EXPLANATION OF PROVISIONS ... 32
Code for design of noise control of industrial enterprises
1 General provisions
1.0.1 This Code is formulated with view to preventing the noise hazard of
industrial enterprises, guaranteeing the employees' health, ensuring the
safety production and normal work, and protecting environment.
1.0.2 This Code is applicable to the noise control design of the construction,
renovation, extension and technical transformation engineering of industrial
enterprises.
1.0.3 The noise control design of the construction, renovation and extension
engineering of industrial enterprises shall be carried out in parallel with the
engineering design.
1.0.4 The design of noise control of industrial enterprise shall cover
comprehensive analysis on the production process, operating maintenance,
noise reduction effect, and technical and economic efficiency.
1.0.5 As for the noise generated during production process and by
equipment, control shall be carried out at the sound source at first by
replacing the high noise process and equipment with the low noise process
and equipment; if it still fails to meet the requirement, the noise control
measures such as sound insulation, noise elimination, sound absorption,
vibration isolation and integrated control shall be taken.
1.0.6 As for such workshops and workplaces that still fail to meet the design
limit of noise control after being taken with corresponding noise control
measures, proper personal protective measures shall be taken.
1.0.7 In addition to the requirements stipulated in this Code, the design of
noise control of industrial enterprises also shall comply with those in the
current relevant standards of the nation.
2 Terms
2.0.1 Workplace
All working places controlled directly or indirectly by the employing unit and
serving for occupational activities of laborers.
2.0.2 Impulsive noise
The sound field where the energy density is uniform and is randomly
distributed in all transmission directions.
2.0.13 Sound bridge
The rigid connection between two layers in the double-layer or multi-layer
sound insulation structure, by which the sound energy is transmitted in these
two layers in the manner of vibration.
2.0.14 Sound lock
A structure with a large number of chambers or corridors being capable of
absorbing sound energy, which is used to connect both sides indoors but also
achieve very low sound coupling, so as to improve the sound insulation
capacity of two compartments.
2.0.15 Muffler
The airflow line with acoustic lining or in special shape, which can effectively
reduce the noise in air flow.
2.0.16 Sound absorption
The process that the sound energy is reduced or converted to other types of
energy when the sound wave passes through a certain medium or shots onto
a certain dielectric surface.
2.0.17 Vibration isolation
The measure using elastic support to reduce the capability of the system to
respond to extrinsic motivation. At stable state, vibration isolation is
represented by the reciprocal of transmissibility.
2.0.18 Insertion loss
The sound pressure level difference at a certain measurement point before
and after inserting the noise control equipment.
3 Design limits of noise control of industrial
enterprises
3.0.1 The noise limits of various workplaces of industrial enterprises shall be
in accordance with those specified in Table 3.0.1.
Table 3.0.1 -- Noise Limits of Various Workplaces
Workplaces Noise limits
planning and industrial layout of the located area, and the site should not be
selected at the centralized area of noise-sensitive buildings.
4.2.2 The site of industrial enterprise generating high noise shall be located
at the windward side of the wind direction with local perennial minimum
frequency in summer of the urban residents centralized area; the site of
noise-sensitive industrial enterprise shall be located at the downwind side of
the wind direction with local perennial minimum frequency in summer of the
surrounding major noise source.
4.2.3 For the noise-sensitive enterprise, its site should not be selected at
the high noise environment area and shall be far away from traffic artery,
airport and main air route.
4.2.4 For the site selection of industrial enterprises, the natural buffer region
shall be utilized.
4.3 General layout design
4.3.1 Under the premise of meeting the process flow requirements, the
general layout of industrial enterprises shall meet the following requirements.
1 In combination with the function partition and process partition, the living
quarters and administrative office area shall be separated from the production
area, and the high noise plant and low noise plant shall be arranged
separately. The major noise sources in industrial enterprises should be
concentrated relatively and should be far away from the on-site or off-site
areas required to be quiet.
2 Tall buildings and structures insensitive to noise and in a direction
conducive to sound insulation should be arrange...