US$230.00 · In stock · Download in 9 secondsGB/T 25861-2023: Water-source high temperature heat pumps using the vapor compression cycle Delivery: 9 seconds. True-PDF full-copy in English & invoice will be downloaded + auto-delivered via email. See step-by-step procedureStatus: Valid GB/T 25861: Evolution and historical versions
| Standard ID | Contents [version] | USD | STEP2 | [PDF] delivery | Name of Chinese Standard | Status |
| GB/T 25861-2023 | English | 230 |
Add to Cart
|
0-9 seconds. Auto-delivery
|
Water-source high temperature heat pumps using the vapor compression cycle
| Valid |
| GB/T 25861-2010 | English | 519 |
Add to Cart
|
3 days
|
Water-source high temperature heat pumps using the vapor compression cycle
| Obsolete |
Excerpted PDFs (Download full copy in 9 seconds upon purchase)PDF Preview: GB/T 25861-2023
GB/T 25861-2023: Water-source high temperature heat pumps using the vapor compression cycle---This is an excerpt. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.), auto-downloaded/delivered in 9 seconds, can be purchased online: https://www.ChineseStandard.net/PDF.aspx/GBT25861-2023
GB
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
ICS 27.200
CCS J 73
Replacing GB/T 25861-2010
Water-source High Temperature Heat Pumps Using the
Vapor Compression Cycle
Issued on: MARCH 17, 2023
Implemented on: OCTOBER 1, 2023
Issued by. State Administration for Market Regulation;
Standardization Administration of the People’s Republic of China.
Table of Contents
Foreword... 3
1 Scope... 5
2 Normative References... 5
3 Terms and Definitions... 6
4 Types and Basic Parameters... 6
5 Technical Requirements... 8
6 Test Methods... 11
7 Inspection Rules... 15
8 Marking, Packaging, Transportation and Storage... 16
Water-source High Temperature Heat Pumps Using the
Vapor Compression Cycle
1 Scope
This document specifies the type and basic parameters, technical requirements, test methods,
inspection rules, marking, packaging, transportation and storage of water-source high
temperature heat pumps using the vapor compression cycle (hereinafter referred to as the
“units”).
This document is applicable to water-source heat pump units for industrial and commercial
purposes, using vapor compression systems driven by electric motors, and with an outlet water
temperature on the use-side of not less than 55 C.
2 Normative References
The contents of the following documents constitute indispensable clauses of this document
through the normative references in the text. In terms of references with a specified date, only
versions with a specified date are applicable to this document. In terms of references without a
specified date, the latest version (including all the modifications) is applicable to this document.
GB/T 191 Packaging-Pictorial Markings for Handling of Goods
GB 2894-2008 Safety Signs and Guideline for the Use
GB 4706.32-2012 Household and Similar Electrical Appliances - Safety - Particular
Requirements for Electrical Heat Pumps, Air-conditioners and Dehumidifiers
GB/T 6388 Transport Package Shipping Mark
GB/T 9237 Refrigerating Systems and Heat Pumps - Safety and Environmental Requirements
GB/T 10870-2014 The Methods of Performance Test for Water Chilling (heat pump) Packages
Using the Vapor Compression Cycle
GB/T 13306 Plates
GB/T 18430.1-2007 Water Chilling (heat pump) Packages Using the Vapor Compression Cycle
- Part 1.Water Chilling (heat pump) Packages for Industrial & Commercial and Similar
Application
GB 25131 Safety Requirements for Water Chillers (heat pump) Using the Vapor Compression
Cycle
GB/T 26572 Requirements of Concentration Limits for Certain Restricted Substances in
Electrical and Electronic Products
JB/T 4330-1999 Determination of Noise Emitted by Refrigerating and Air Conditioning
Equipment
JB/T 7249 Refrigeration and Air Conditioning Apparatus - Terminology
3 Terms and Definitions
The terms and definitions defined in JB/T 7249 and GB/T 10870-2014, and the following are
applicable to this document.
3.1 water-source high temperature heat pumps using the vapor compression cycle
Water-source heat pump units that use the vapor compression refrigeration cycle driven by
electric motors to produce hot water of not less than 55 C.
4 Types and Basic Parameters
4.1 Types
In accordance with the nominal operating conditions of the units, the hot water outlet
temperature is classified into.
a) H1N type. nominal outlet temperature is 55 C;
b) H2N type. nominal outlet temperature is 60 C;
c) H3N type. nominal outlet temperature is 70 C;
d) H4N type. nominal outlet temperature is 80 C;
e) H5N type. nominal outlet temperature is 90 C.
NOTE. where N is a, b, c, d or e, indicating the sub-division in accordance with the water source
temperature (on the heat source side), please refer to Table 2 for details.
4.2 Basic Parameters
4.2.1 The temperature range of the unit water source is shown in Table 1.
5.1.8 The insulation layer of the units shall have good insulation performance, and be non-toxic,
odorless and flame-retardant.
5.1.9 The units shall have protection functions, such as motor overload protection, phase loss
protection (three-phase power supply), water system water failure protection, antifreeze
protection, and high- and low-pressure protection of the refrigeration system, etc. Various
control functions are normal, and various protection devices shall meet the design requirements
and be sensitive and reliable.
5.1.10 The heat exchange equipment shall have the corresponding anti-corrosion performance,
and the units shall not contaminate the water source during use.
5.1.11 The outer surface of the units shall be clean and the painted surface shall be smooth.
Pipeline accessories shall generally be installed horizontally and vertically. Before filling the
refrigerant, the surface in the units that comes into contact with the refrigerant and lubrication
shall be kept clean and dry.
5.1.12 The materials of the refrigeration system components of the units shall not deteriorate
under the action of refrigerant, lubricating oil and their mixtures, and shall ensure the normal
operation of the whole units.
5.1.13 The regulating device of the units with energy regulation shall be sensitive and reliable.
5.2 Performance Requirements
5.2.1 Air tightness, vacuum and pressure test
5.2.1.1 The air tightness requirements for the units shall comply with the provisions of 5.2.1 in
GB/T 18430.1-2007.
5.2.1.2 The vacuum requirements for the units shall comply with the provisions of 5.2.2 in
GB/T 18430.1-2007.
5.2.1.3 The pressure test requirements for the units shall comply with the provisions of 5.2.3 in
GB/T 18430.1-2007.
5.2.2 Operation
When the units are normally operating, the inspection items shall meet the design requirements.
5.2.3 Nominal heating capacity
The measured nominal heating capacity of the units shall not be less than 95% of the indicated
value.
5.2.4 Nominal heating power consumption
The measured nominal heating power consumption of the units shall not be greater than 110%
6.3.1 Air tightness, vacuum and pressure tests
6.3.1.1 The air tightness test of the units shall be carried out in accordance with the provisions
of “air tightness test” in 6.3.1 of GB/T 18430.1-2007.
6.3.1.2 Vacuum test. after passing the air tightness test, vacuumize the units to 80 Pa and
maintain the pressure for at least 30 minutes.
6.3.1.3 The pressure test shall be carried out in accordance with the provisions of “pressure test”
in 6.3.1 of GB/T 18430.1-2007.
6.3.2 Operation test
The units shall be operated under conditions approximate to the nominal heating conditions,
and the operating conditions of the units, the sensitivity and reliability of the safety protection
devices shall be checked, and the actions of the temperature, electrical appliances and other
control elements shall be checked to see whether they are normal.
6.3.3 Nominal heating capacity test
The nominal heating capacity of the units shall be tested under the nominal heating conditions
specified in Table 4 in accordance with the refrigerant method in GB/T 10870-2014.
6.3.4 Nominal heating power consumption test
When the units are tested under the nominal heating capacity, the input power and current of
the units shall be measured.
6.3.5 Test of coefficient of performance for heating
The coefficient of performance for heating of the units is calculated based on the data measured
in tests of 6.3.3 and 6.3.4 in accordance with the provisions of GB/T 10870-2014.
6.3.6 Maximum heating operation test
The maximum heating operation test of the units shall be carried out in accordance with the
following provisions.
a) The test voltage is the rated voltage (not exceeding the rated voltage 10%). After the
operation under the maximum heating operation conditions specified in Table 4
becomes stable, during the entire test process, the units shall normally operate without
any faults;
b) The units shall be able to continuously operate, and the motor overload protection
device or other protection devices shall not operate;
c) When the units are shut down for 10 minutes, re-start and continuously operate them
for 1 hour, but the motor overload protector is allowed to trip off within the first 5
minutes of the startup operation, and it is not allowed to action thereafter; if the motor
overload protector that trips off within the first 5 minutes of the re-started continuous
operation is not reset, and reset within more than 30 minutes of shutdown, the units
shall continuously operate for 1 hour.
6.3.7 Minimum heating operation test
The units shall continuously operate for at least 30 minutes at the rated voltage in accordance
with the minimum operation heating conditions specified in Table 4.
6.3.8 Noise test
The units are tested at the rated voltage and rated power and approximate to the nominal heating
conditions in accordance with the rectangular hexahedron measurement method in JB/T 4330-
1999.The sound pressure level is calculated in accordance with the surface average sound
pressure level method in JB/T 4330-1999.
6.3.9 Water system pressure loss test
The pressure loss test of the water system shall be carried out in accordance with the
requirements of Appendix B in GB/T 18430.1-2007.
6.3.10 Variable operation test
Change a certain condition in the variable operation specified in Table 4, and the other
conditions shall subject to the flow and temperature conditions under the nominal operating
conditions. The test shall include the corresponding nominal operating conditions, maximum
operating conditions, and minimum operating temperature condition points specified in Table
2.The test results are plotted into curves or tables, and each curve or table shall contain the data
of not less than 4 measurement points.
7 Inspection Rules
7.1 Exit-factory Inspection
Each unit shall receive the exit-factory inspection, and the inspection items, technical
requirements and test methods shall be in accordance with the provisions of Table 7.
7.2 Sampling Inspection
7.2.1 The units shall be sampled from the products that have passed the exit-factory inspection,
and the inspection items and test methods shall be in accordance with the provisions of Table
7.
Table 7 -- Inspection Items
No. Item Exit-factory Inspection
Sampling
Inspection
Type
Inspection
Technical
Requirements
Test
Methods
b) Product name and model;
c) Unit type;
d) Main technical performance parameters (nominal heating capacity, refrigerant type
and volume of filling, rated voltage, frequency and number of phases, total input
power, overall dimensions of the unit, and mass, etc.);
e) Product exit-factory No.;
f) Manufacturing date.
8.1.2 The units shall have a marking indicating the operating status, direction, water flow
direction, liquid level and oil level mark, etc.
8.1.3 The units shall be accompanied by technical documents, such as product certificate,
instruction manual and packing list, etc.
The contents of the product certificate shall include.
a) Product model and name;
b) Product exit-factory No.;
c) Inspection conclusion;
d) Signature or seal of the inspector;
e) Inspection date.
The contents of the product instruction manual shall include.
a) Product model and name, scope of application, serial No. of this document, noise and
water system pressure loss;
b) Product structural diagram, electrical schematic diagram and wiring diagram;
c) Installation instructions and requirements (the installation of units using flammable
refrigerants shall comply with the requirements of GB/T 9237);
d) Instructions for use, maintenance and care precautions (for units using flammable
refrigerants, the maintenance and care shall comply with the requirements of
Appendix DD in GB 4706.32-2012 in addition to meeting the requirements of GB/T
9237).
8.1.4 If the units use flammable refrigerants, then, it shall be permanently marked in a
prominent position of the units in accordance with the color and style of the 2-2 warning symbol
“Beware of Fire” in GB 2894-2008, and the vertical height of the marking symbol shall be not
less than 30 mm.
...... Source: Above contents are excerpted from the full-copy PDF -- translated/reviewed by: www.ChineseStandard.net / Wayne Zheng et al.
Tips & Frequently Asked QuestionsQuestion 1: How long will the true-PDF of English version of GB/T 25861-2023 be delivered?Answer: The full copy PDF of English version of GB/T 25861-2023 can be downloaded in 9 seconds, and it will also be emailed to you in 9 seconds (double mechanisms to ensure the delivery reliably), with PDF-invoice. Question 2: Can I share the purchased PDF of GB/T 25861-2023_English with my colleagues?Answer: Yes. The purchased PDF of GB/T 25861-2023_English will be deemed to be sold to your employer/organization who actually paid for it, including your colleagues and your employer's intranet. Question 3: Does the price include tax/VAT?Answer: Yes. Our tax invoice, downloaded/delivered in 9 seconds, includes all tax/VAT and complies with 100+ countries' tax regulations (tax exempted in 100+ countries) -- See Avoidance of Double Taxation Agreements (DTAs): List of DTAs signed between Singapore and 100+ countriesQuestion 4: Do you accept my currency other than USD?Answer: Yes. www.ChineseStandard.us -- GB/T 25861-2023 -- Click this link and select your country/currency to pay, the exact amount in your currency will be printed on the invoice. Full PDF will also be downloaded/emailed in 9 seconds. Question 5: Should I purchase the latest version GB/T 25861-2023?Answer: Yes. Unless special scenarios such as technical constraints or academic study, you should always prioritize to purchase the latest version GB/T 25861-2023 even if the enforcement date is in future. Complying with the latest version means that, by default, it also complies with all the earlier versions, technically.
How to buy and download a true PDF of English version of GB/T 25861-2023?A step-by-step guide to download PDF of GB/T 25861-2023_EnglishStep 1: Visit website https://www.ChineseStandard.net (Pay in USD), or https://www.ChineseStandard.us (Pay in any currencies such as Euro, KRW, JPY, AUD). Step 2: Search keyword "GB/T 25861-2023". Step 3: Click "Add to Cart". If multiple PDFs are required, repeat steps 2 and 3 to add up to 12 PDFs to cart. Step 4: Select payment option (Via payment agents Stripe or PayPal). Step 5: Customize Tax Invoice -- Fill up your email etc. Step 6: Click "Checkout". Step 7: Make payment by credit card, PayPal, Google Pay etc. After the payment is completed and in 9 seconds, you will receive 2 emails attached with the purchased PDFs and PDF-invoice, respectively. Step 8: Optional -- Go to download PDF. Step 9: Optional -- Click Open/Download PDF to download PDFs and invoice. See screenshots for above steps: Steps 1~3 Steps 4~6 Step 7 Step 8 Step 9
|