US$369.00 ยท In stock Delivery: <= 3 days. True-PDF full-copy in English will be manually translated and delivered via email. JG/T 382-2012: Pass box Status: Valid
Standard ID | Contents [version] | USD | STEP2 | [PDF] delivered in | Standard Title (Description) | Status | PDF |
JG/T 382-2012 | English | 369 |
Add to Cart
|
3 days [Need to translate]
|
Pass box
| Valid |
JG/T 382-2012
|
PDF similar to JG/T 382-2012
Basic data Standard ID | JG/T 382-2012 (JG/T382-2012) | Description (Translated English) | Pass box | Sector / Industry | Building & Construction Industry Standard (Recommended) | Classification of Chinese Standard | Q70 | Classification of International Standard | 91.060.50 | Word Count Estimation | 14,150 | Quoted Standard | GB/T 191; GB/T 1184-1996; GB 4793.1; GB/T 13306; GB/T 13554-2008; GB 15763.1; GB 50073-2001; HG/T 3088 | Regulation (derived from) | Bulletin of the Ministry of Housing and Urban No. 1383; industry standard filing Notice 2013 No. 1 (No. 157 overall); | Issuing agency(ies) | Ministry of Housing and Urban-Rural Development of the People's Republic of China | Summary | This standard specifies the transfer window of terms and definitions, classification and marking, the basic provisions, requirements, test methods, inspection rules, marking, packaging, transportation and storage. This standard applies to industrial and c |
JG/T 382-2012: Pass box---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Pass box
ICS 91.060.50
Q70
People's Republic of China building industry standards
Pass the window
Posted on May 16,.2012
2012-11-01 implementation
Ministry of Housing and Urban-Rural Development, People's Republic of China released
Foreword
This standard was drafted in accordance with the rules given in GB/T 1.1-2009.
This standard proposed by the Ministry of Housing and Urban Standard and Design Institute.
This standard by the Ministry of Housing and Urban Construction Environment and Energy Standardization Technical Committee.
This standard is drafted by. China Academy of Building Research.
Participated in the drafting of this standard. Institute of Military Medical Sciences, Chinese People's Liberation Army Institute of Health, Tianjin University, Shanghai Feili and machine
Electric Technology Co., Ltd., Beijing Jiu Jie Purification Engineering Co., Ltd., Suzhou net Group Suzhou Antai Air Technology Co., Ltd., Shanghai Song Hua air
Purification Equipment Co., Ltd.
The main drafters of this standard. Zhang Yi Zhao, Niu Victoria music, Qi Jiancheng, Liu Junjie, Zhu Ying City, Lang Hongmei, Jin Zhen, Hong Yu Zhong.
Pass the window
1 Scope
This standard specifies the transmission window terms and definitions, classification and marking, the basic provisions, requirements, test methods, inspection rules, signs, packaging,
Transportation and storage.
This standard applies to industrial and civil buildings in the room with air separation requirements of the transfer window products used in the production and testing.
2 Normative references
The following documents for the application of this document is essential. For dated references, only the dated version applies to this article
Pieces. For undated references, the latest edition (including all amendments) applies to this document.
GB/T 191 Packaging - Pictorial signs
GB/T 1184-1996 Tolerances on shape and position tolerances
GB 4793.1 Safety requirements for electrical equipment for measurement, control and laboratory use - Part 1. General requirements
GB/T 13306 signs
GB/T 13554-2008 high efficiency air filter
GB 15763.1 Building safety glass fire glass
Design specifications for clean rooms
HG/T 3088 vehicle doors and windows rubber seal
3 Terms and definitions
The following terms and definitions apply to this document.
3.1
Installed on the wall of the room for the transfer of materials and having the basic function of isolating the room air on both sides of the wall.
4 classification and marking
4.1 Classification
4.1.1 transfer window According to the use of function is divided into basic type, purification type, disinfection type, negative pressure type, airtight type five, as shown in Table 1.
Table 1 transfer window classification
Type tag code function
Basic A Transfer window with basic functions
Purification type B1
Has the basic functions, and has a self-recirculating air purification system composed of a fan and an efficient air filter
System, can transfer the air inside the window to purify
|