US$319.00 · In stock Delivery: <= 3 days. True-PDF full-copy in English will be manually translated and delivered via email. GB 19212.20-2008: [GB/T 19212.20-2008] Safety of power transformers, power supply units and similar -- Part 20: Particular requirements for perturbation attenuation transformers Status: Valid
| Standard ID | Contents [version] | USD | STEP2 | [PDF] delivered in | Standard Title (Description) | Status | PDF |
| GB 19212.20-2008 | English | 319 |
Add to Cart
|
3 days [Need to translate]
|
[GB/T 19212.20-2008] Safety of power transformers, power supply units and similar -- Part 20: Particular requirements for perturbation attenuation transformers
| Valid |
GB 19212.20-2008
|
PDF similar to GB 19212.20-2008
Basic data | Standard ID | GB 19212.20-2008 (GB19212.20-2008) | | Description (Translated English) | [GB/T 19212.20-2008] Safety of power transformers, power supply units and similar -- Part 20: Particular requirements for perturbation attenuation transformers | | Sector / Industry | National Standard | | Classification of Chinese Standard | K41 | | Classification of International Standard | 29.180 | | Word Count Estimation | 12,182 | | Date of Issue | 2008-03-24 | | Date of Implementation | 2009-01-01 | | Quoted Standard | GB 19212.1-2003 | | Adopted Standard | IEC 61558-2-19-2000, MOD | | Regulation (derived from) | Announcement of Newly Approved National Standards No. 5, 2008 (No. 118 overall) | | Issuing agency(ies) | General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China, Standardization Administration of the People's Republic of China | | Summary | This Chinese standard specifies the safety requirements for all aspects of the transformer. This standard applies to stationary or mobile, single -phase or polyphase, air-cooled, independence or supporting the use of isolation or safety isolation transformers, power supply voltage does not exceed the rated AC 1000V, rated frequency not exceeding 500Hz, rated output not exceeding 10kVA. Interference attenuation transformers intended to be used as office equipment or similar equipment supply, with a midpoint in the output circuit output to attenuate conducted interference power grid. In addition, the installation procedures and equipment specifications circuit between the double insulation or reinforced insulation should be achieved through the use of this transformer. This standard applies to dry-type transformers. Its winding can be sealed or non- sealed. If the isolation transformer to two or more devices to provide power, then some of the equipment so exposed conductive parts of the connection need to meet IEC 60364-4-41 requirements of 413. 5. This standard does not include"decay"function of the performance. This feature can be of different characteristics, such as to obtain a laminated block or special. This is also applicable to an electronic circuit with a transformer. This standard is not intended to be used with the transformer input and output terminals or output jack to connect an external circuit and its components. |
GB 19212.20-2008: [GB/T 19212.20-2008] Safety of power transformers, power supply units and similar -- Part 20: Particular requirements for perturbation attenuation transformers ---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Safety of power transformers, power supply units and similar.Part 20. Particular requirements for perturbation attenuation transformers
ICS 29.180
K41
National Standards of People's Republic of China
Power transformers, power supply units and similar products
Safety - Part 20. disturbance attenuation
Particular requirements for transformers
(IEC 61558-2-19.2000, MOD)
Posted 2008-03-24
2009-01-01 implementation
Administration of Quality Supervision, Inspection and Quarantine of People's Republic of China
Standardization Administration of China released
Foreword
All technical content in this Part of GB 19212 is mandatory.
GB 19212 "of power transformers, power supply units and similar products" currently proposed is divided into 24 parts.
Part 1. General requirements and tests
Part 2. Particular requirements for separating transformers for general use
Part 3. Particular requirements for control transformers
Part 4. Gas and oil burner ignition transformers for special requirements
Particular requirements for isolating transformers for general purposes. Part 5
Part 6. Particular requirements for shaver transformers and shaver supply units
Part 7. Particular requirements for safety isolating transformers for general purposes
Part 8. Particular requirements for transformers for toys
Particular requirements for bell and bell transformers. Part 9
Part 10. Particular requirements for class Ⅲ portable transformers for filament lamps
Part 11. Particular requirements for the operating voltage 1000V above high insulation level transformers
Particular requirements for the leakage magnetic transformers. Part 12
Particular requirements for constant voltage transformers. Part 13
Part 14. General Purpose Particular requirements for auto-transformers
Part 15. Particular requirements for regulator
Part 16. Particular requirements for supply of medical locations isolation transformer
Part 17. Particular requirements for power supply units and similar products
Part 18. Particular requirements for transformers for switch mode power supplies
Part 19. Particular requirements for medical devices for transformers
Part 20. Particular requirements for transformers interference attenuation
Particular requirements for small reactors. Part 21
Particular requirements for having a special media (liquid medium SF6) transformer. Part 22
Part 23. Electrical transformers have the highest rated temperature of the specific requirements
Particular requirements for transformers for construction sites. Part 24
This is Part 20 GB 19212's.
The partial modification using IEC 61558-2-19.2000 (first edition), "Safety of power transformers, power supply units and similar products
Part 2-19. Particular requirements for transformers disturbance attenuation "(in English).
This section according to IEC 61558-2-19.2000 redrafted. This part of IEC 61558-2-19.2000 In addition to this technical difference
The modified content section, but entirely due to GB 19212.1-2003 "power transformers, power supply units referenced in this section and similar production
Product Safety - Part 1. General requirements and tests "(IEC 61558-1.1998, MOD) and IEC 61558-1.1998 Existing technical
Differences arising, see GB 19212.1-2003 the foreword. Taking into account China's national conditions, in using IEC 61558-2-19.2000, the present
Part made some changes. About the technical differences have been incorporated into the text, and they are involved in terms of the margin of a single vertical line
Identity.
For ease of use, this part of IEC 61558-2-19.2000 also made the following editorial changes.
a) "this International Standard" be replaced by "this section";
b) use a decimal point instead of a decimal comma ",". ",";
c) Remove IEC 61558-2-19.2000 Foreword.
Taking into account the actual situation in China, this part of IEC 61558-2-19.2000 in the power supply voltage and rated voltage tolerance aspects
It has been modified. IEC standards +6% - 10%, and this part of the country according to national standards, to + 7% - 10%. this
Part of IEC 61558-2-19.2000 preferred value in the interference attenuation transformer AC rated output voltage complements increased domestic
Common 220V, 380V AC and 36V rated output voltage.
This section is based on GB 19212.1-2003 on the development, it needs to be used in conjunction with GB 19212.1-2003.
This part is the GB 19212.1-2003 corresponding chapter, article supplement and modified so GB of content 19212.1-2003
Conversion-oriented part of the contents. The newly added section for GB 19212.1-2003 Terms numbered starting from 101.
This part is proposed by the China Electrical Equipment Industrial Association.
This part of the National Standardization Technical Committee transformers (SAC/TC44) centralized.
This part by the China Electronics Standardization Institute, Shenyang Transformer Research Institute drafted.
The main drafters of this section. Yangyu Tao, Sun Jun.
Power transformers, power supply units and similar products
Safety - Part 20. disturbance attenuation
Particular requirements for transformers
1 Scope
The chapter GB 19212.1-2003 by the following instead.
This section provides various aspects of the transformer (eg, electrical, thermal and mechanical aspects) safety requirements.
This section applies to Stationary or mobile, single-phase or multi-phase, air-cooled (natural cooling or forced cooling), alone or supporting the use of isolation
Or safety isolating transformer, its rated supply voltage not exceeding AC 1000V, rated frequency not exceeding 500Hz, rated output not exceeding
10kVA. Disturbance attenuation transformer intended to be used as office equipment or similar equipment power supply, the output circuit having a midpoint output to
It attenuate conducted interference MAINS.
In addition, the installation procedures and equipment specifications double insulation or reinforced insulation between circuits should be implemented through the use of such a transformer.
Note 1. The use of such a transformer connected to the device specified in this does not mean that you can reduce the requirements for the device.
Disturbance attenuation isolating transformer.
--- No-load output voltage and rated output voltage exceeding 50V AC or ripple-free DC 120V, but not more than AC 500V or
Ripple-free DC 708V; To comply with national wiring regulations or requirements for a particular purpose, no-load output voltage or the rated output voltage
These limits may be exceeded, but not exceed 1000V AC or ripple-free DC 1415V.
Disturbance attenuation safety isolating transformer.
--- No-load output voltage or the rated output voltage does not exceed 50V AC or ripple-free DC 120V.
This section applies to dry-type transformers. Windings can be sealed or non-sealed.
If the isolation transformer to two or more devices to provide power, so some of the devices connected to the exposed conductive parts
Need to comply with the provisions of 413.5 of IEC 60364-4-41.
Note 2. The media is filled with a liquid or powder material (such as sand) of the transformer, the additional requirements are under consideration.
Note 3. to note the following.
--- For transformer intended to use in a tropical climate countries, special requirements may be necessary;
--- Located in areas of special environmental conditions may require specific requirements.
Note 4. This section does not prevent the use of the output circuit midpoint no other types of transformers as attenuation transformers.
This section does not include the performance of "decay" feature. This function can be different characteristics, e.g., to block or special laminate
obtain.
This section also applies to transformers incorporating electronic circuits. This part is not intended to be used with the transformer input and output terminals or output
A receptacle connector and an external circuit components.
2 Normative references
GB 19212.1-2003 this chapter apply.
3 Terms and Definitions
In addition to the following entries, GB 19212.1-2003 this chapter apply.
The chapter increased the following entries.
3.101
The secondary winding has a center point for conducted interference attenuation power transformer, scheduled for limiting devices of the transformer is electrically connected
Transient appears on the source of.
4 General requirements
GB 19212.1-2003 this chapter apply.
General Description 5 tests
GB 19212.1-2003 this chapter apply.
6 RATINGS
In addition to the following terms outside, GB 19212.1-2003 this chapter apply.
The chapter increased the following provisions.
6.101 rated output voltage shall not exceed.
--- Interference attenuation isolating transformer, AC or 500V ripple-free DC 708V;
--- Interference attenuation safety isolating transformer, AC 50V and (or) ripple-free DC 120V.
AC rated output voltage is preferably.
--- Interference attenuation isolating transformer, 72V, 120V, 220V, 230V, 380V, 400V and 440V;
--- Interference attenuation safety isolating transformer, 6V, 12V, 24V, 36V, 42V and 48V.
6.102 rated output not exceeding 10kVA.
Preferably of rated output.
--- 10VA, 16VA, 25VA, 40VA, 63VA, 100VA, 160VA, 250VA, 400VA, 630VA,
1000VA, 1600VA, 2500VA, 4000VA, 6300VA and 10000VA.
6.103 rated frequency shall not exceed 500Hz.
6.104 rated supply voltage not exceeding AC 1000V.
Flag by visual inspection to verify compliance with the requirements of 6.101 to 6.104.
Category 7
In addition to the following terms outside, GB 19212.1-2003 this chapter apply.
Article 7.2 the following modifications.
Press the short circuit protection or protection of normal use classification.
--- Inherent short-circuit proof transformers;
--- Non-inherent short-circuit proof transformers;
--- Safe transformers.
8 Marking and other information
In addition to the following terms outside, GB 19212.1-2003 this chapter apply.
Article 8.1 the following modifications.
h) interference attenuation transformer should be marked with one of the graphic symbols shown in 8.11.
8.3 GB 19212.1-2003 that section does not apply.
8.4 GB 19212.1-2003 that section does not apply.
8.11 Addition of the following.
Symbol Description Symbol IEC 60417a number
No harm isolation transformer interference attenuation
Short-circuit proof isolating transformer interference attenuation (intrinsic resistance
Inherent short-circuit or short-circuit proof)
Non-hazardous safety isolation transformer interference attenuation
Short-circuit proof safety isolating transformer interference attenuation (solid
There are short-circuit proof non-inherently short-circuit proof)
aIEC 60417 (all parts).1998.
The chapter increased the following provisions.
8.101 All transformers shall be accompanied by the specification, illustrate the use of a transformer, and warned people not to use the following connections.
--- Connection midpoint and fixtures protective grounding;
--- Transformer secondary connection to the fixed wiring.
8.102 input and output voltage ratio
If the independent isolation transformer input and output voltage ratio is less than 1.1, then the transformer should be accompanied by instructions, instructions should be noted
use correctly.
9 contact with hazardous live parts Protection
GB 19212.1-2003 this chapter apply.
10 change the input voltage setpoint
In addition to the following terms outside, GB 19212.1-2003 this chapter apply.
Transformer has not allowed more than one rated supply voltage.
Do not allow the transformer is equipped for regulating the input connector (for example, taps) to accommodate various supply voltage regulating device.
11 load output voltage and output current
In addition to the following terms outside, GB 19212.1-2003 this chapter apply.
11.1 before that section is replaced by the following two paragraphs.
When connected to the transformer rated frequency rated supply voltage, secondary connected cosφ = 1, enables the secondary rated output load, input
Rated voltage and the difference shall not exceed 3%.
12 no-load output voltage
In addition to the following terms outside, GB 19212.1-2003 this chapter apply.
The chapter increased the following provisions.
12.101 In any case, no-load output voltage shall not exceed the following values, even in a predetermined without the separate windings are connected in series
When connected in series should be so.
--- Interference attenuation isolating transformer, AC or 500V ripple-free DC 708V;
--- Interference attenuation safety isolating transformer, 50V AC or ripple-free DC 120V.
12.102 no-load output voltage and load output voltage difference can not be too large.
When the transformer is connected to the rated frequency at ambient temperature rated supply voltage, by measuring the load output voltage to verify compliance
12.101 and 12.102 requirements.
Under this measured load output voltage during the test in Chapter 11 of the measured load output voltage difference, the latter percentage voltage
Represented, should not exceed 6%.
NOTE. This ratio is defined as follows.
U -U load load
U × 100% load
13 short-circuit voltage
GB 19212.1-2003 this chapter apply.
Fever 14
GB 19212.1-2003 this chapter apply.
15 short-circuit and overload protection
GB 19212.1-2003 this chapter apply.
16 Mechanical strength
GB 19212.1-2003 this chapter apply.
17 dust, solid objects and moisture into the harmful Protection
GB 19212.1-2003 this chapter apply.
18 Insulation resistance and dielectric strength
GB 19212.1-2003 this chapter apply.
19 Structure
In addition to the following terms outside, GB 19212.1-2003 this chapter apply.
Which is replaced by the following.
19.1 input and output circuits shall be electrically isolated from each other, but also in the structure should ensure that there can be any one of these circuits
It connected directly or indirectly through other metal parts.
By visual inspection and measurement, and to consider the provisions of chapter 18 and 26 to verify eligibility.
19.1.1 input and output winding insulation between the windings by double or reinforced insulation components.
Also comply with the following requirements.
--- Class Ⅰ transformer, insulation between the input winding and the case should be determined by the composition of the basic insulation, insulation between the output windings and the housing
It should consist of double or reinforced insulation;
--- Of class Ⅱ transformer insulation insulation between the input winding and the housing and between the output windings and the body should be determined by double or plus
Strong insulation components.
19.1.2 intermediate metal parts (such as the core) is not connected with the housing and is located in the input and output transformer windings, where goldsmith
Between the case of components and input winding, insulation or metal parts and intermediate output windings shall be composed of at least basic insulation.
Note. Do not input or output windings, or the housing by at least basic insulation to isolate the intermediate metal parts is considered to be connected with the related parts.
Also comply with the following requirements.
--- Class Ⅰ transformer between the input and output windings via the intermediate metal parts should be insulated by a double or reinforced insulation composition;
--- Of class Ⅱ transformer between the input and output windings by double or reinforced insulation composed by insulating intermediate metal parts; input
Between the windings and the housing, and the housing and between the output windings by double or reinforced insulation by insulating intermediate metal parts.
Edge components.
19.1.3 Ⅰ class transformer between the input and output windings shall not have a protective shield.
19.1.4 transformer can not be equipped with electrical input and output capacitor connected to the circuit.
The chapter increased the following provisions.
There can not be a connection between the output circuit and 19.101 protectorate.
There can not be connected to the output circuit between 19.102 and housing.
By visual inspection to verify their eligibility.
Position input and output terminals connected to external conductors 19.103 shall guarantee the access of these measurements between the wire terminal access point
When the distance between the input and output terminals is not less than 25mm. If the distance is to rely on to achieve the separator, the separator must be used
Edge material, and it should be permanently attached to the transformer.
By visual inspection and, in the case of ignoring the intermediate metal parts is checked by measuring eligibility.
19.104 to 19.110 blank.
19.111 pairs isolation transformer, the output socket, if any, should be part of the transformer. For matching transformers, connections with the device
To ensure having double insulated cable or cord.
19.112 output winding should have the outlet (if any) the midpoint of the ground terminal connection terminals. For having more than one output
Windings, each output winding should use double or reinforced insulation to isolate. In addition, the midpoint tap of the windings can be connected together
Received with all output jack on a common terminal (if any) connected to the ground terminal. Ground terminal output circuit outlet must not be with Paul
Protective earth terminal is connected.
By visual inspection, by the tests and 18.1 according to the provisions of Chapter 26 Compliance is checked by measurement.
Note. disturbance attenuation transformers can have both a metal material and a shell of insulating material.
19.113 transformer should be fitted with circuit protection device shown in FIG. 101, in order to be connected to the device, connected to the phase line and the midpoint
Between conductors or between two phase conductors can disconnect the output circuit shorted. In this case, circuit protection devices should be in the table
101 within specified time action.
Note. This table is taken from IEC 60364-4-41 Table 41A.
By visual inspection and the following tests to verify eligibility.
The input of the transformer is connected to equal 0.94 times to 1.07 times the rated voltage (whichever is more severe voltage), each input
Once the terminal is connected to a midpoint, then the output terminals are connected to the test circuit protection devices. Circuit protection device should be in the table
101 within the predetermined operation time.
19.114 functional reasons, when using a shield between the input and output winding is connected to ground, the shield layer and between the output windings
INSULATION shall consist of double or reinforced insulation.
101 output short circuit protection when
Table 101 maximum break time
U0a /
Longest interruption time /
> 400
0.8
0.4
0.4
0.2
0.1
aU0 exchange for a nominal rms voltage.
20 Component
In addition to the following terms outside, GB 19212.1-2003 this chapter apply.
The chapter following modifications.
20.3 pairs of input and output voltage ratio of 1, and a predetermined voltage to be used in zone Ⅱ transformer, whose output circuit
Plug socket should be able to accept it intended to be directly related to the national power grid connected to.
The chapter increased the following provisions.
Circuit protection devices 20.101 in intended to be permanently connected to fixed wiring interference attenuation on the transformer, the operator shall comply 19.113
Co GB 13539.5 fuse or circuit breaker small components. In mobile disturbance attenuation transformers, circuit protection device may be made
GB 9364 in line with the rated current is less than or equal to 6.3A fuse components.
By visual inspection to verify compliance.
21 Internal wiring
GB 19212.1-2003 this chapter apply.
22 Supply connection and other external flexible cable or cord
Except for the following, GB 19212.1-2003 this chapter apply.
Only output less than or equal 250VA only allows the use of Z-connected.
23 Terminals for external conductors
GB 19212.1-2003 this chapter apply.
24 protection grounding device
GB 19212.1-2003 this chapter apply.
25 Screws and connections
GB 19212.1-2003 this chapter apply.
26 creepage distances, clearances and distances through insulation
GB 19212.1-2003 this chapter apply.
27 resistance to heat, abnormal heat, to fire and to tracking
GB 19212.1-2003 this chapter apply.
28 rust
GB 19212.1-2003 this chapter apply.
Book GB 19212.20-2008
appendix
Appendix GB 19212.1-2003 apply.
8002-
02.
Tips & Frequently Asked Questions:Question 1: How long will the true-PDF of GB 19212.20-2008_English be delivered?Answer: Upon your order, we will start to translate GB 19212.20-2008_English as soon as possible, and keep you informed of the progress. The lead time is typically 1 ~ 3 working days. The lengthier the document the longer the lead time. Question 2: Can I share the purchased PDF of GB 19212.20-2008_English with my colleagues?Answer: Yes. The purchased PDF of GB 19212.20-2008_English will be deemed to be sold to your employer/organization who actually pays for it, including your colleagues and your employer's intranet. Question 3: Does the price include tax/VAT?Answer: Yes. Our tax invoice, downloaded/delivered in 9 seconds, includes all tax/VAT and complies with 100+ countries' tax regulations (tax exempted in 100+ countries) -- See Avoidance of Double Taxation Agreements (DTAs): List of DTAs signed between Singapore and 100+ countriesQuestion 4: Do you accept my currency other than USD?Answer: Yes. If you need your currency to be printed on the invoice, please write an email to [email protected]. In 2 working-hours, we will create a special link for you to pay in any currencies. Otherwise, follow the normal steps: Add to Cart -- Checkout -- Select your currency to pay.
|