| Standard ID | Contents [version] | USD | STEP2 | [PDF] delivered in | Standard Title (Description) | Status | PDF |
| GA 1151-2014 | English | 439 |
Add to Cart
|
3 days [Need to translate]
|
General requirements for wireless communication function of fire alarm system
| Obsolete |
GA 1151-2014
|
PDF similar to GA 1151-2014
Standard similar to GA 1151-2014 GB 14287.3 GB 14287.1 GB 12791
Basic data | Standard ID | GA 1151-2014 (GA1151-2014) | | Description (Translated English) | General requirements for wireless communication function of fire alarm system | | Sector / Industry | Public Security (Police) Industry Standard | | Classification of Chinese Standard | C81 | | Classification of International Standard | 13.220.20 | | Word Count Estimation | 10,190 | | Date of Issue | 2014-04-16 | | Date of Implementation | 2014-04-16 | | Quoted Standard | GB 4717; GB/T 9969; GB 12978; GB 14287.1; GB 16808; GB 16838; GB/T 17626.2; GB/T 17626.3; GB 23757 | | Regulation (derived from) | Fire alarm system wireless communication function General requirements "industry standard release implementation; on the publication of public safety industry standard announcement (2014); industry standard filing bulletin 2015 fourth (total 184th) | | Issuing agency(ies) | Ministry of Public Security | | Summary | This standard specifies the requirements, test, inspection rules and product marks of the wireless communication function in the fire alarm system. This standard applies to the general industrial and civil buildings installed with a wireless communication |
GA 1151-2014: General requirements for wireless communication function of fire alarm system---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
General requirements for wireless communication function of fire alarm system
ICS 13.220.20
C81
People's Republic of China Public Security Industry Standards
Fire Alarm System wireless communication function General requirements
Issued on. 2014-04-16
2014-04-16 implementation
People's Republic of China Ministry of Public Security
Foreword
The standard Chapter 3, Chapter 5, Chapter 6 content mandatory, the rest are recommended.
This standard was drafted in accordance with GB/T 1.1-2009 given rules.
This standard was proposed by the Ministry of Public Security Fire Department.
This standard by the National Standardization Technical Committee on Fire fire detection and alarm Technical Committee (SAC/TC113/SC6) centralized.
This standard is drafted by. Ministry of Public Security Shenyang Fire Research Institute.
It participated in the drafting of this standard. Versalinks Information Technology (Shanghai) Co., Ltd.
The main drafters of this standard. Liu Cheng, Liu Changan, Li Xiaobai, Liuzuo Li, Song Liwei, Zhao Yu, Zhang Binbin, Guo Jinlong, Wei Bin, Qian Shi E,
Ding Hongjun.
This standard is the first release.
Fire Alarm System wireless communication function General requirements
1 Scope
This standard specifies the requirements for a fire alarm system in wireless communication function, testing, inspection rules and product logos.
This standard applies to general industrial and civil buildings to install fire alarm system with a wireless communication function, electrical fire monitoring system
System and combustible gas alarm system.
2 Normative references
The following documents for the application of this document is essential. For dated references, only the dated version suitable for use herein
Member. For undated references, the latest edition (including any amendments) applies to this document.
GB 4717 fire alarm controller
GB/T 9969 General Instructions industrial products
GB 12978 fire electronic products inspection rules
GB 14287.1 electrical fire control system - Part 1. Electrical fire monitoring equipment
GB 16808 combustible gas alarm controller
GB 16838 fire electronic products environment test methods and severities
GB/T 17626.2 Electromagnetic compatibility Testing and measurement techniques - Electrostatic discharge immunity test
GB/T 17626.3 electromagnetic compatibility test and measurement technology RFEMS test
GB 23757 fire protection requirements for electronic products
3 Requirements
3.1 General
Fire alarm system with a wireless communication function, electrical fire monitoring system and combustible gas alarm system (hereinafter referred to as the "System"), should be
First, meet the requirements of Chapter 3, and then press the provisions of Chapter 4 of the test, and meet the test requirements.
3.2 appearance requirements
System surface without corrosion, coating loss and blistering, no scratches, cracks, burrs and other mechanical damage, no loose fastening parts.
3.3 Basic functional requirements
Various components of the wireless communication system can be complex 3.3.1 within the system to achieve, it can also be used independent of the wireless communication module.
3.3.2 various components within the system having a wireless communication function (including a wireless communication module) should be between the maximum communication distance under the condition, by
Wireless communication functions to achieve the following requirements.
Fire Alarm a) fire alarm controller, fault alarm function should meet the requirements of GB 4717;
b) monitoring alarm electrical fire monitoring equipment, fault alarm function should meet the requirements of GB 14287.1;
c) combustible gas alarm controller combustible gas concentration display, combustible gas alarm, fault alarm function should meet
GB 16808 requirements.
Wireless communication systems 3.3.3 In addition to complying with this standard, it should also comply with the relevant national regulations on radio equipment management.
|