Test method for verifying field performance of smoke management system-Hot smoke test
| Obsolete |
GA/T 999-2012
|
GA/T 999-2012 | English | 879 |
Add to Cart
|
5 days [Need to translate]
|
Test method for verifying field performance of smoke management system-Hot smoke test
| Obsolete |
GA/T 999-2012
|
PDF similar to GA/T 999-2012
Standard similar to GA/T 999-2012 GB 4351 GA 602 GB 4066.2
Basic data Standard ID | GA/T 999-2012 (GA/T999-2012) | Description (Translated English) | Test method for verifying field performance of smoke management system-Hot smoke test | Sector / Industry | Public Security (Police) Industry Standard (Recommended) | Classification of Chinese Standard | C84 | Classification of International Standard | 13.220.01 | Word Count Estimation | 21,230 | Date of Issue | 2012-06-19 | Date of Implementation | 2012-08-01 | Quoted Standard | GB 2626-2006; GB/T 2903-1998; GB/T 5907; GB/T 14107; GB 50019-2003 | Adopted Standard | AS 4391-1999, NEQ | Regulation (derived from) | Notice on the issuance of public safety industry standards; Industry standard filing announcement No. 3 (No. 159) | Issuing agency(ies) | Ministry of Public Security |
GA/T 999-2012: Test method for verifying field performance of smoke management system-Hot smoke test ---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Test method for verifying field performance of smoke management system-Hot smoke test
ICS 13.220.01
C84
People's Republic of China Public Security Industry Standards
Smoke evacuation system performance field-proven method
Hot smoke test method
Hotsmoketest
Issued on. 2012-06-19
2012-08-01 implementation
People's Republic of China Ministry of Public Security
Table of Contents
Introduction Ⅲ
Introduction Ⅳ
1 Scope 1
2 Normative references 1
3 Terms and definitions
4 test apparatus 2
5 5 test procedure
6 Test personnel and facilities security 8
7 data records 9
8 Test preparation and test reports 10
Appendix A (normative) flue gas temperature and the smoke plume bottom layer at the interface and volume flow 12
Foreword
This standard was drafted in accordance with GB/T 1.1-2009 given rules.
The standard reference to Australian Standards AS4391-1999 "smoke control systems Hot smoke test" (in English).
This standard was proposed by the Ministry of Public Security Fire Department.
This standard by the National Standardization Technical Committee on Fire Building Fire Safety Engineering at the Technical Committee (SAC/TC113/SC13)
Centralized.
This standard is drafted by. Ministry of Public Security of Sichuan Fire Research Institute.
Participated in the drafting of this standard. Sichuan Province Public Security Fire Department, Ministry of Public Security Fire Department.
The main drafters of this standard. a Xie Yuan, Zhang Xiaoming, Yang, Lu Guojian, Hu Zhong, Li Yue, Hu Rui.
Introduction
Based on the outcome of the reference standard in fire inspection of construction projects studied achieved in the field of foreign advanced standards, to prevent discharge
Smoke system design, construction and management personnel to provide on-site evaluation of a smoke control system performance of hot smoke test methods can not test site
Damage under the premise of the performance of smoke control system on-site testing.
Objective hot smoke tests in the construction of smoke control system debugging process, flue gas generated by quantitative tests to examine the source of fire fire conditions
Smoke control capability under smoke control system. Test combustion by ethanol pool fire heat plume colorless, non-toxic, with a visible tracer smoke
Gas injection thermal plume, the flow characteristics of hot plume demo and start smoke control system, performance evaluation whether the smoke control system can meet the requirements.
Smoke evacuation system performance field-proven method
Hot smoke test method
1 Scope
This standard specifies the conditions under no structural damage and internal facilities, equipment, test method using hot smoke test smoke control system architecture
The required test equipment, test procedures and security requirements, and produce smoke and quantitatively determine the size of the fire hot smoke test methods.
This standard applies to hot smoke test in a special spatial structure, smoke control system design implementation of complex buildings, such as. the atrium, factories, cargo
Other staff positions, department stores, shopping centers, office buildings and sports complex and entertainment centers and other crowded public buildings, tunnels, subways, car
Station, airport and other transportation hubs buildings and large underground construction.
Hot smoke test data can also be used to verify the smoke flow simulation software.
2 Normative references
The following documents for the application of this document is essential. For dated references, only the dated version suitable for use herein
Member. For undated references, the latest edition (including any amendments) applies to this document.
GB 2626-2006 respirator self-absorption filter anti-particulate respirators
GB/T 2903-1998 Copper - copper-nickel (constantan) thermocouple wire
GB/T 5907 fire first part basic terms
GB/T 14107 Fire basic terms of the second part
GB 50019-2003 heating, ventilation and air conditioning design
3 Terms and Definitions
GB/T 5907 and GB/T 14107 and defined by the following terms and definitions apply to this document.
3.1
Fuming means smokegenerator
A way to generate quantitative volumetric flow of flue gas, comprising fuming cake into smoke and smoke leading source means two parts, fuming source, hair
Chimney and smoke pot and other types.
3.2
Test fire source testfire
Test test for the source of fire smoke control system, the heat release power is controlled in size without destroying the buildings and facilities and equipment
Within the range.
3.3
Tracer smoke tracersmoke
Fuming smoke particles generated by smoldering source, into ethanol burning hot smoke plume, the plume show flow characteristics.
|