GA/T 999-2012English879 Add to Cart 5 days [Need to translate] Test method for verifying field performance of smoke management system-Hot smoke test Obsolete GA/T 999-2012
GA/T 999-2012English879 Add to Cart 5 days [Need to translate] Test method for verifying field performance of smoke management system-Hot smoke test Obsolete GA/T 999-2012

PDF similar to GA/T 999-2012


Standard similar to GA/T 999-2012

GB 4351   GA 602   GB 4066.2   

Basic data

Standard ID GA/T 999-2012 (GA/T999-2012)
Description (Translated English) Test method for verifying field performance of smoke management system-Hot smoke test
Sector / Industry Public Security (Police) Industry Standard (Recommended)
Classification of Chinese Standard C84
Classification of International Standard 13.220.01
Word Count Estimation 21,230
Date of Issue 2012-06-19
Date of Implementation 2012-08-01
Quoted Standard GB 2626-2006; GB/T 2903-1998; GB/T 5907; GB/T 14107; GB 50019-2003
Adopted Standard AS 4391-1999, NEQ
Regulation (derived from) Notice on the issuance of public safety industry standards; Industry standard filing announcement No. 3 (No. 159)
Issuing agency(ies) Ministry of Public Security

GA/T 999-2012: Test method for verifying field performance of smoke management system-Hot smoke test


---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Test method for verifying field performance of smoke management system-Hot smoke test ICS 13.220.01 C84 People's Republic of China Public Security Industry Standards Smoke evacuation system performance field-proven method Hot smoke test method Hotsmoketest Issued on. 2012-06-19 2012-08-01 implementation People's Republic of China Ministry of Public Security

Table of Contents

Introduction Ⅲ Introduction Ⅳ 1 Scope 1 2 Normative references 1 3 Terms and definitions 4 test apparatus 2 5 5 test procedure 6 Test personnel and facilities security 8 7 data records 9 8 Test preparation and test reports 10 Appendix A (normative) flue gas temperature and the smoke plume bottom layer at the interface and volume flow 12

Foreword

This standard was drafted in accordance with GB/T 1.1-2009 given rules. The standard reference to Australian Standards AS4391-1999 "smoke control systems Hot smoke test" (in English). This standard was proposed by the Ministry of Public Security Fire Department. This standard by the National Standardization Technical Committee on Fire Building Fire Safety Engineering at the Technical Committee (SAC/TC113/SC13) Centralized. This standard is drafted by. Ministry of Public Security of Sichuan Fire Research Institute. Participated in the drafting of this standard. Sichuan Province Public Security Fire Department, Ministry of Public Security Fire Department. The main drafters of this standard. a Xie Yuan, Zhang Xiaoming, Yang, Lu Guojian, Hu Zhong, Li Yue, Hu Rui.

Introduction

Based on the outcome of the reference standard in fire inspection of construction projects studied achieved in the field of foreign advanced standards, to prevent discharge Smoke system design, construction and management personnel to provide on-site evaluation of a smoke control system performance of hot smoke test methods can not test site Damage under the premise of the performance of smoke control system on-site testing. Objective hot smoke tests in the construction of smoke control system debugging process, flue gas generated by quantitative tests to examine the source of fire fire conditions Smoke control capability under smoke control system. Test combustion by ethanol pool fire heat plume colorless, non-toxic, with a visible tracer smoke Gas injection thermal plume, the flow characteristics of hot plume demo and start smoke control system, performance evaluation whether the smoke control system can meet the requirements. Smoke evacuation system performance field-proven method Hot smoke test method

1 Scope

This standard specifies the conditions under no structural damage and internal facilities, equipment, test method using hot smoke test smoke control system architecture The required test equipment, test procedures and security requirements, and produce smoke and quantitatively determine the size of the fire hot smoke test methods. This standard applies to hot smoke test in a special spatial structure, smoke control system design implementation of complex buildings, such as. the atrium, factories, cargo Other staff positions, department stores, shopping centers, office buildings and sports complex and entertainment centers and other crowded public buildings, tunnels, subways, car Station, airport and other transportation hubs buildings and large underground construction. Hot smoke test data can also be used to verify the smoke flow simulation software.

2 Normative references

The following documents for the application of this document is essential. For dated references, only the dated version suitable for use herein Member. For undated references, the latest edition (including any amendments) applies to this document. GB 2626-2006 respirator self-absorption filter anti-particulate respirators GB/T 2903-1998 Copper - copper-nickel (constantan) thermocouple wire GB/T 5907 fire first part basic terms GB/T 14107 Fire basic terms of the second part GB 50019-2003 heating, ventilation and air conditioning design

3 Terms and Definitions

GB/T 5907 and GB/T 14107 and defined by the following terms and definitions apply to this document. 3.1 Fuming means smokegenerator A way to generate quantitative volumetric flow of flue gas, comprising fuming cake into smoke and smoke leading source means two parts, fuming source, hair Chimney and smoke pot and other types. 3.2 Test fire source testfire Test test for the source of fire smoke control system, the heat release power is controlled in size without destroying the buildings and facilities and equipment Within the range. 3.3 Tracer smoke tracersmoke Fuming smoke particles generated by smoldering source, into ethanol burning hot smoke plume, the plume show flow characteristics.