US$169.00 · In stock Delivery: <= 3 days. True-PDF full-copy in English will be manually translated and delivered via email. GB/T 18294.5-2010: Technical identification methods for fire -- Part 5: Gas chromatography-mass spectrometry analysis Status: Valid
| Standard ID | Contents [version] | USD | STEP2 | [PDF] delivered in | Standard Title (Description) | Status | PDF |
| GB/T 18294.5-2010 | English | 169 |
Add to Cart
|
3 days [Need to translate]
|
Technical identification methods for fire -- Part 5: Gas chromatography-mass spectrometry analysis
| Valid |
GB/T 18294.5-2010
|
PDF similar to GB/T 18294.5-2010
Basic data | Standard ID | GB/T 18294.5-2010 (GB/T18294.5-2010) | | Description (Translated English) | Technical identification methods for fire -- Part 5: Gas chromatography-mass spectrometry analysis | | Sector / Industry | National Standard (Recommended) | | Classification of Chinese Standard | C82 | | Classification of International Standard | 13.220.01 | | Word Count Estimation | 7,782 | | Date of Issue | 2011-01-14 | | Date of Implementation | 2011-06-01 | | Quoted Standard | GB/T 19267.7; GB/T 20162 | | Regulation (derived from) | Announcement of Newly Approved National Standards No. 2 of 2011 | | Issuing agency(ies) | General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China, Standardization Administration of the People's Republic of China |
GB/T 18294.5-2010: Technical identification methods for fire -- Part 5: Gas chromatography-mass spectrometry analysis ---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Technical identdication methods for fire.Part 5. Gas chromatography-mass spectrometry analysis
ICS 13.220.01
C82
National Standards of People's Republic of China
Fire technology identification method
Part 5. Gas chromatography - mass spectrometry
Part 5. Gaschromatography-massspectrometryanalysis
2011-01-14 release
2011-06-01 Implementation
General Administration of Quality Supervision, Inspection and Quarantine of the People 's Republic of China
China National Standardization Management Committee released
Foreword
GB/T 18294 "fire technology identification method" is divided into six parts.
- Part 1. Ultraviolet spectroscopy;
- Part 2. Thin layer chromatography;
- Part 3. Gas Chromatography;
- Part 4. High performance liquid chromatography;
- Part 5. Gas chromatography - mass spectrometry;
Part 6. Infrared spectroscopy.
This part is part 5 of GB/T 18294.
This part is drafted in accordance with the rules given in GB/T 1.1-2009.
This part is made by the Ministry of Public Security of the People's Republic of China.
This section is headed by the National Fire Safety Standardization Technical Committee Fire Investigation Subcommittee (SAC/TC113/SC11).
This part of the drafting unit. Ministry of Public Security Tianjin Fire Research Institute.
The main drafters of this section. Tian Guihua, Lu Zhibao, Deng Zhenyu, Liang Guofu, Geng Huimin.
Fire technology identification method
Part 5. Gas chromatography - mass spectrometry
1 Scope
This part of GB/T 18294 specifies the terms and definitions of gas chromatography-mass spectrometry (GC-MS) in fire technology identification.
Test equipment, test conditions and test methods.
This part applies to gasoline, kerosene, diesel, paint thinner and other fire scene common flammable liquid and its combustion residue identification.
2 normative reference documents
The following documents are indispensable for the application of this document. For dated references, only the dated edition applies to this article
Pieces. For undated references, the latest edition (including all modifications) applies to this document.
GB/T 19267.7 Physical and chemical testing of microchemical evidence for criminal technology - Part 7. Gas chromatography - mass spectrometry
GB/T .20162 Fire technology identification material extraction method
3 terms and definitions
GB/T 19267.7 and GB/T .20162 and the following terms and definitions apply to this document.
3.1
Total ion chromatogram total ionchromatogram
In the chromatographic conditions under which the flammable liquid is passed through a capillary column, the total ion current of each component obtained by mass spectrometry
The intensity varies with the scan time.
3.2
Extraction of ion - flow chromatograms extractedionchromatogram
A map of the characteristic ion peaks of the flammable liquid selected from the total ion chromatogram.
4 test principle
After the laboratory pretreatment to be analyzed samples, injected into the gas chromatography-mass spectrometry instrument, after a pair of analytical samples with good
Good separation of the capillary column into the mass spectrum, the total ion chromatogram, using the total ion chromatogram and extraction of ion current chromatography
The characteristic of the flammable liquid is determined qualitatively by distinguishing the characteristic peaks.
5 test equipment
5.1 Gas Chromatography - Mass Spectrometer
A combination of a capillary chromatograph that separates flammable liquids and a mass spectrometer that identifies flammable liquids.
5.2 syringes
5.2.1 Liquid syringe. Volume injector in the range of 0.1 μL to 10.0 μL.
|