Excerpted PDFs (Download full copy in 9 seconds upon purchase)PDF Preview: GB 15308-2006
GB 15308-2006: Foam extinguishing agent [Including 2009XG1]---This is an excerpt. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.), auto-downloaded/delivered in 9 seconds, can be purchased online: https://www.ChineseStandard.net/PDF.aspx/GB15308-2006
GB
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
ICS 13.220.10
C 84
Replacing GB 15308-1994, GB 17427-1998, GB 13463-1992
Foam extinguishing agent
(ISO 7203, Fire extinguishing media - Foam concentrates, NEQ)
Issued on. DECEMBER 14, 2006
Implemented on. JULY 01, 2007
Issued by.
General Administration of Quality Supervision, Inspection
and Quarantine of the People’s Republic of China;
Standardization Administration of the People’s Republic of
China.
Table of Contents
Foreword... 3
1 Scope... 5
2 Normative references... 5
3 Terms and definitions... 5
4 Requirements... 7
5 Test method... 17
6 Inspection rules... 42
7 Package, marking, transport and storage... 43
Annex A... 45
Annex B... 49
Foreword
Chapter 4 of this Standard is mandatory, while the rest are recommended.
Consistency BETWEEN this Standard AND ISO 7203-1.1995(E) “Extinguishing Agent -
Foam Concentrate - Low-expansion Foam Concentrate Used for Water-insoluble Liquid
Fuel Top Application”, ISO 7203-2.1995(E) “Extinguishing Agent Foam Concentrate -
Medium and High-expansion Foam Concentrate Used for Water-insoluble Liquid Fuel Top
Application” and ISO 7203-3.1999(E) “Extinguishing Agent Foam Concentrate -
Low-expansion Foam Concentrate Used for Water-insoluble Liquid Fuel Top Application”
are non-equivalent.
This Standard replaces GB 15308-1994 “General Specification for Foam Extinguishing
Agents”, GB 17427-1998 “Aqueous Film Forming Foam Extinguishing Agent”, and GB
13463-1992 “Alcohol Resistant Foam Extinguishing Agent”.
Compared with GB 15308-1994, the main changes of this Standard are as follows.
-- Add technical requirements and test methods of “Foam Extinguishing Agent for
Foam Extinguishers”;
-- Add technical requirements and test methods of “corrosion performance” and
“freezing point”;
-- Add the definitions of “lowest useful temperature”, “characteristic values”, “25%
drainage time”, “50% drainage time”, “expansion”, “foam”, “foam solution”,
“sediment”, “spreading coefficient” and “anti-burning time”;
-- Delete the definition of “temperature-sensitive foam solution”;
-- Add Annex A “small fire fighting test for foam performance and fire extinguishing
performance quality control” and Annex B “viscosity test method”.
-- Add the division of disqualification types of items;
-- Revise fire extinguishing test procedures and dividing the grades of fire extinguishing
performances of foams.
GA 31-1992 “High-expansion Foam Extinguishing Agent” and GA 219-1999 “Protein
Foam Concentrate and Fluoroprotein Foam Concentrate” shall be abolished, from the
date of implementation of this Standard.
Annex B to this Standard is normative; Annex A is informative.
This Standard was proposed by Ministry of Public Security of the People’s Republic of
China.
This Standard shall be under the jurisdiction of Third Branch Technical Committee of
National Fire Fighting Standardization Committee.
Drafting organizations of this Standard. Tianjin Fire Research Institute, Ansul, Ningbo
Nenglin Fire-fighting Equipment Co., Ltd. AND Yangzhou Jiangya Fire Extinguishing
Agents Co., Ltd.
Main drafters of this Standard. Liu Yuheng, Jin Hongbin, Dai Huihong, Song Yang, Zhang
Guobi, Zhang Yulin, Tong Xiangyou and Liu Jinsheng.
The previous versions replaced by this Standard are as follows.
-- GB 13463-1992;
-- GB 15308-1994;
-- GB 17427-1998.
Foam Extinguishing Agent
1 Scope
This Standard specifies definition, requirements, test methods, inspection rules, marks
and other contents of foam extinguishing agent.
This Standard applies to low, medium and high foam extinguishing agent and foam
extinguishing agent for fire extinguisher.
This Standard does not apply to chemical extinguishing agent.
2 Normative references
The articles contained in the following documents have become part of this document
when they are quoted herein. For the dated documents so quoted, all subsequent
modifications (including all corrections) or revisions made thereafter do not apply to this
Standard. However, the parties who reach an agreement according to this Standard are
encouraged to study whether the latest versions of these documents may be used. For
the undated documents so quoted, the latest versions (including all modification sheets)
apply to this document.
GB 4351-1997 General specifications for portable fire extinguishers [Deleted by
Modification Sheet No.1, (2009)] [Translator note. The text in BLUE indicates the
CHANGES of Modification Sheet No.1 (Approved on March 10, 2009, by National
Standardization Authority). Hereafter the same.]
GB 4351.1-2005 Portable fire extinguishers. Part 1.Performance and construction
[Added by Modification Sheet No.1, (2009)]
GB/T 6003.1-1997 Test sieves of metal wire cloth (eqv ISO 3310.1.1990)
3 Terms and definitions
Following terms and definitions apply to this Standard.
3.1 Characteristic values
Physical and chemical performance values of foam concentrate and foam solution
provided by suppliers.
3.2 25% drainage time
Time required for drainage of liquid that accounts for 25% of its mass.
3.7 High-expansion foam concentrate
Foam concentrate that applies to foam generation of 201 times or more.
3.8 Foam (fire fighting foam)
Air-filled bubbles formed by foam solution.
3.9 Foam concentrate
Concentrated liquid that may be mixed with water to form foam solution based on suitable
concentration, also known as foam concentrated solution.
3.10 Foam solution
Solution prepared with foam concentrate and water based on a predetermined
concentration, also known as foam mixed solution.
3.19 Sediment
Insoluble solid matters in foam concentrate.
3.20 Spreading coefficient
Measuring the capacity that one liquid freely spreads on the surface of another liquid.
3.21Anti-burning time
Time required from burning anti-burning tank to igniting certain fuel surface.
3.22 Lowest useful temperature
Temperature that is 5°C higher than freezing point.
4 Requirements
4.1 General requirements
4.1.1 If foam concentrate is applicable to seawater, the concentration of foam solution
prepared with seawater shall be the same with the concentration of foam solution
prepared with fresh water.
4.2 Technical requirements
4.2.1 Low-expansion foam concentrate
4.2.2 Medium and high-expansion foam solution
4.2.2.1 Performances of medium expansion foam concentrate shall meet the
requirements in Table 5.
4.2.2.2 Performances of high-expansion foam concentrate shall meet the requirements in
Table 6.
4.2.3 Alcohol-resistant foam concentrate
4.2.3.1 Physical, chemical and foam properties of low-expansion foam concentrate and
foam solution shall meet the requirements in Table 1.
4.2.3.2 Fire extinguishing performance of water insoluble liquid fuel shall meet the
requirements in Table 2 and Table 3.
4.2.3.3 Temperature sensitivity determination shall meet the requirements in Table 4.
5 Test method
5.1 Sample and temperature treatment
5.1.1 Samples before temperature treatment
All samples, regardless of being taken from one container or several containers, shall be
mixed uniformly to ensure sample representativeness. Fill the storage container with
samples and seal.
5.2.2 Test procedures
5.2.3 Freezing point
5.3 Sediments
5.3.1 Equipment
5.3.2 Sampling
Take two samples before temperature treatment; one is for direct test, while the other is
tested again after aging test and cooling.
Aging conditions. Seal the sample; keep at (60±3) °C for (24±2)h and then cool to room
temperature.
5.4.3.
5.4.1 Equipment and materials
Liquidity determination device. See figure 1.
5.4.2 Calibration
5.5 pH value
5.5.1 Instruments and reagents
5.5.2 Test procedures
5.6 Surface tension, interfacial tension and spreading coefficient
5.6.1 Instruments and reagents
5.9 Expansion and drainage time of high-medium expansion foam concentrate
5.9.1 Medium-expansion foam concentrate
6 Inspection rules
6.1 Sampling
The sample shall be representative; the sample shall be consistent with the
integral-source. For the barrel products, before sampling, products inside the barrel shall
be shaken well; for the tank products, the sample can be divided into three parts, and
sampled respectively from upper, medium and lower parts of the tank, and then mix the
sample evenly.
6.2 Exit-factory inspection
Each batch of products shall be conducted for exit-factory inspection. For low-expansion
foam liquid, the exit-factory inspection items shall be. solidifying point, pH value,
6.3 Type test
All technical indexes of corresponding distinguishing agents listed in Chapter 4 of this
Standard are the items of type test. If there is one of the following cases, the type test shall
be conducted, and specify that base-number of the products sampled shall not be less
than 2 in the period of type tests.
6.4 Judgment of inspection results
6.4.1 Judgment of exit-factory test results
The results are judged by the manufacturer according to the inspection rules.
7 Package, marking, transport and storage
7.1 Package
The foam concentrate shall be sealed inside plastic barrels, or stored in iron barrels
whose internal have been conducted anti-corrosion processing. The minimum package
shall be 25kg.
7.2 Marking
Package container of the foam concentrate shall be identified clearly and firmly.
7.3 Transport and storage
In the process of transportation, the product shall not be collided, avoiding damage of the
package.
...... Source: Above contents are excerpted from the full-copy PDF -- translated/reviewed by: www.ChineseStandard.net / Wayne Zheng et al.
|