Specification for 1100kV gas-insulated metal-enclosed switchgear
| Obsolete |
GB/Z 24836-2009
|
PDF similar to GBZ24836-2009
Basic data | Standard ID | GB/Z 24836-2009 (GB/Z24836-2009) | | Description (Translated English) | Specification for 1100kV gas-insulated metal-enclosed switchgear | | Sector / Industry | National Standard | | Classification of Chinese Standard | K43 | | Classification of International Standard | 29.240.10 | | Word Count Estimation | 52,576 | | Date of Issue | 2009-11-30 | | Date of Implementation | 2010-05-01 | | Quoted Standard | GB 1207-2006; GB 1208-2006; GB 1984-2003; GB 1985-2004; GB/T 2423.1; GB/T 2423.2; GB/T 2423.3; GB/T 2423.4; GB/T 2423.10; GB/T 2423.17; GB/T 2900.20-1994; GB/T 4109-2008; GB 4824; GB/T 5095.2-1997; GB/T 5582-1993; GB/T 7354; GB/T 8905; GB/T 11022-1999; GB/T 11287-2000; GB/T 12022; GB/T 13540-1992; GB/T 16927.1; GB/T 17626.1; GB/T 17626.4; GB/T 17626.12; GB/T 22381-2008; GB/T 22382-2008; DL/T 593-2006; DL/T 728-2000; IEC 60480; IEC 60815; IEC 61000-4-11; IEC 61000-4-17; IEC 61000-4-29; IEC 61000-5; IEC 61000 - 6-5; IEC 61462; IEC 61634; IEC 61672-1; IEC 61672-2; IEC 61810-7; IEC 62155; ISO 3231; IEC 60255-21-3 | | Regulation (derived from) | ?National Standard Approval Announcement 2009 No.14 (Total No.154) | | Issuing agency(ies) | Ministry of Health of the People's Republic of China | | Summary | This standard specifies the 1 100 kV gas-insulated metal-enclosed switchgear conditions of use, ratings, design and structure, trial, selection guidelines, transport, storage, installation, such as operation and maintenance requirements. |
GBZ24836-2009: Specification for 1100kV gas-insulated metal-enclosed switchgear---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Specification for 1100kV gas-insulated metal-enclosed switchgear
ICS 29.240.10
K43
People's Republic of China national standardization of technical guidance documents
1100 犽 犞 gas-insulated metal-enclosed switchgear
specifications
Posted.2009-11-30
2010-05-01 implementation
General Administration of Quality Supervision, Inspection and Quarantine of People's Republic of China
China National Standardization Administration released
Directory
Foreword V.
1 Scope 1
2 Normative references 1
3 Terms and definitions 3
4 normal and special conditions of use 5
4.1 normal conditions of use 5
4.2 special conditions of use 5
5 rating 5
5.1 Equipment rated voltage (Ur) 6
5.2 Rated insulation level 6
5.4 Rated current and temperature rise 6
5.5 Rated short-time withstand current (Ik) 6
5.6 Rated peak withstand current (Ip) 6
5.8 Rated sub-gate device and the auxiliary power supply and control circuit voltage (Ua) 7
5.9 Combined sub-gate device and auxiliary power supply and control circuit rated frequency 7
5.10 Rated filling level of gas or liquid for insulation and/or operation 7
Design and structure
6.1 pairs of switchgear and control equipment liquid medium requirements 7
6.2 pairs of switchgear and control equipment in the gas medium requirements 7
6.3 Switchgear and control equipment grounding 7
6.4 Auxiliary and control equipment 8
6.5 Power operation 8
6.6 Energy Storage Operation 8
6.7 Human-independent operation 8
6.8 Release operation 8
6.9 Low pressure and high pressure lockout and monitoring device 8
6.10 nameplate 8
6.11 interlocking device 9
6.12 position indication and action count 9
6.13 enclosure protection level 9
6.14 creepage distance 9
6.15 Gas and vacuum tightness 9
6.16 liquid tightness 10
6.17 Flammability 10
6.18 Electromagnetic compatibility (EMC) 10
6.19 Corrosion 10
6.20 Pressure coordination and monitoring 10
6.21 Internal Faults 11
6.22 housing 12
6.23 separator 12
6.24 Pressure Release 13
6.25 Noise 14
6.26 Interface 14
6.27 telescopic section 14
6.28 observation window and repair platform 14
7 type test 15
7.1 Overview 15
7.2 Insulation test 16
7.3 Radio interference voltage (r.i.v.) Test 18
7.4 loop resistance measurement 19
7.5 temperature rise test 19
7.6 Short-time withstand current and peak withstand current test 19
7.7 Degree of protection verification 20
7.8 Gas tightness test and gas state measurement 20
7.9 Electromagnetic compatibility test (EMC) 20
7.10 Auxiliary and control loop additional test 23
7.11 Verification of closing and breaking capacity 25
7.12 Mechanical and Environmental Testing 26
7.13 Case Verification Test 26
7.14 Partition pressure test 27
7.15 Internal fault test under arcing condition 27
7.16 Insulator test 27
7.17 Earth Connection Corrosion Test 28
8 factory test 28
8.1 Main circuit insulation test 28
8.2 Auxiliary and control loop test 29
8.3 Measurement of the main circuit resistance 29
8.4 Tightness test and gas status check 29
8.5 Design and Visual Inspection 29
8.6 Mechanical operation and mechanical properties test 29
8.7 Enclosure pressure test 29
8.8 Control devices auxiliary circuits, equipment and interlocking test 30
8.9 Pressure Test of Separator 30
9 switchgear and control equipment selection guide 30
9.1 Selection of rating 30
9.2 Continuous and temporary overload caused by changing operating conditions 30
10 Inquiries, Tenders and Ordering Information to be Provided 30
10.1 Inquiry and Order Information 30
10.2 Tender Information 30
Transport, storage, installation, operation and maintenance
11.1 Conditions for transport, storage and installation 31
11.2 Installation 31
11.3 Operation 34
11.4 Maintenance 34
12 safety 34
Impact of the product on the environment 34
Appendix A (Normative) Test method for gas-insulated metal-enclosed switchgear under internal arc fault condition 35
A. 1 Introduction 35
A. 2 short circuit current arc test 35
A. 3 Combination and validation of independent experiments 36
Appendix B (Normative) Field test techniques and practical considerations 37
B. 1 Test voltage generator 37
B. 2 discharge location 37
B. 3 special test procedures 37
B. 4 partial discharge measurement 38
B. 5 Electrical Adjustment 38
B. Repeatability test 38
B. 7 partial discharge detection method 39
Appendix C (Informative) Calculation of Internal Faults 41
Appendix D (Informative) Queries, Tenders and Orders Required Information 42
D. 1 Introduction 42
D. 2 normal and special conditions of use 42
D. 3 rating 42
D. Design and Structure
D. 5 bus duct 44
D. Circuit breaker
D. 7 Isolating switch and earthing switch 44
D. 8 bushing 44
D. 9 cable connection 45
D. 10 transformer connection 45
D. Current Transformer 45
D. Voltage transformer
D. Questionnaire and Tender Information 45
Reference 46
Foreword
This guidance document is based on IEC 62271-203..2003 (3rd edition of IEC 60517) "High Voltage Switchgear and Control Equipment
Part 203. Gas-insulated metal-enclosed switchgear with a rated voltage above 52 kV "and the State Grid Corporation of Southeast Jindong - Jingmen - Nanyang
1000kV UHV AC pilot demonstration project 1100kV gas-insulated metal-enclosed switchgear contract and the development of the contract, in some
According to the actual needs of 1000kV system in our country, it is added and modified.
This Guidance Document shall be used in conjunction with GB/T 11022-1999. Unless otherwise specified in this Guidance Document, this Guidance
Technical documents to implement the provisions of GB/T 11022-1999.
Appendix A, Appendix B of this guidance document are normative appendix, Appendix C and Appendix D are informative appendix.
This Guidance Document is proposed by China Electricity Council.
This Guidance Document is administered by China Electricity Council.
The guidance of technical documents by the UHV AC Transmission Standardization Technical Committee, China Electric Power Research Institute responsible for the interpretation.
The guidance of technical documents drafted by. State Grid Corporation, China Electric Power Research Institute.
The guidance of technical documents participated in the drafting unit. Xi'an Institute of High Voltage Electric, East China Power Grid Co., Ltd., Tsinghua University, Xi'an Jiaotong University
Xi'an High Voltage Electric Co., Ltd., Henan Ping High Electric Co., Ltd., New Northeast Electric (Shenyang) Co., Ltd. high-voltage switch is limited
the company.
The main drafters of this technical guidance document. Shu Yin Biao, Cui Jingchun, Ding Yang, Gu Nihong, Wang Chengyu, Wang Shaowu, Guo Yuanyuan, Yuan,
Cui Bo source.
Drafters of this Guidance Document include Sun Gang, Li Peng, Liu Botao, Liu Zhaolin, Xu Guozheng, Ma Zhiying, Zhang Meng, Xia Wen, Han Shumo,
Zhao Hongfei, Sun Yongheng, Zhang Duo.
1100 犽 犞 gas-insulated metal-enclosed switchgear
specifications
1 Scope
This Guidance Document specifies the conditions of use, ratings, design and construction of 1100kV gas-insulated metal-enclosed switchgear,
Test, selection guidelines, transportation, storage, installation, operation and maintenance requirements.
This guidance applies to 1100kV outdoor installation, frequency of 50Hz unipolar closed SF6 gas insulated metal closed
Off equipment.
In order to facilitate the use of this guidance document, the terms "GIS" and "switchgear" are used to describe "gas insulated metal enclosed switch
equipment".
The gas-insulated metal enclosed switchgear covered by this technical document consists of individual components that can be directly connected
And these components can only be operated this way.
As required, this Guidance Document complements and supplements the relevant standards for the individual components that make up GIS.
2 Normative references
The following documents contain provisions which, through reference in this Guidance Document, become the provisions of this Guidance Note document. All dated
Reference documents, all subsequent amendments (not including errata content), or revisions do not apply to this guidance document, however, drums
Recipients of the agreement based on this guidance document are encouraged to study whether the latest versions of these documents are applicable. All undated references
The latest version of this document applies to this guidance document.
GB 1207-2006 Electromagnetic voltage transformers (IEC 60044-2..2003, MOD)
Current transformers GB 1208-2006 (IEC 60044-1..2003, MOD)
GB 1984-2003 high voltage AC circuit breakers (IEC 62271-100..2001, MOD)
GB 1985-2004 high-voltage AC isolation switch and earthing switch (IEC 62271-102..2002, MOD)
GB/T 2423.1 Environmental testing for electric and electronic products Part 2. Test methods Test A. Low temperature (GB/T 2423.1-
2008, IEC 60068-2-1..2007, IDT)
GB/T 2423.2 Environmental testing for electric and electronic products Part 2. Test methods Test B. high temperature (GB/T 2423.2-
2008, IEC 60068-2-2..2007, IDT)
GB/T 2423.3 Environmental testing for electric and electronic products Part 2. Test methods Test Cab. constant hot and humid test
(GB/T 2423.3-2006, IEC 60068-2-78..2001, IDT)
GB/T 2423.4 Environmental testing for electric and electronic products Part 2. Test methods Test Db alternating hot and humid (12h + 12h
Loop) (GB/T 2423.4-2008, IEC 60068-2-30..2005, IDT)
GB/T 2423.10 Environmental testing for electric and electronic products Part 2. Test methods Test Fc. Vibration (sinusoidal)
(GB/T 2423.10-2008, IEC 60068-2-6..1995, IDT)
GB/T 2423.17 Environmental testing for electric and electronic products Part 2. Test methods Test Ka. Salt spray (GB/T 2423.17-
2008, IEC 60068-2-11. 1981, IDT)
GB/T 2900.20-1994 Electrotechnical terminology high-voltage switchgear (neqIEC 60050 (IEV). 1984)
GB/T 4109-2008 Insulating sleeves with an AC voltage above 1000V (IEC 60137, MOD)
GB 4824 Industrial, Scientific and Medical (ISM) radio frequency electromagnetic interference characteristics and measurement methods (GB 4824-2004,
CISPR11..2003, IDT)
|