Standard ID GA 767-2008 (GA767-2008)
Description (Translated English) General technical requirements of fire control center
Sector / Industry Public Security (Police) Industry Standard
Classification of Chinese Standard C81
Classification of International Standard 13.220.10
Word Count Estimation 10,190
Date of Issue 2008-04-16
Date of Implementation 2008-07-01
Regulation (derived from) Announcement of the Ministry of Public Security on Abolishing 440 Standards of Public Security Industry
Issuing agency(ies) Ministry of Public Security
Summary This standard specifies the general requirements of the fire control room, fire safety management, control and display requirements, information recording requirements, information transmission requirements. This standard is applicable to the centralized fire alarm system, the fire control room or the fire control center in the control center alarm system as specified in GB 50116.

GA 767-2008: General technical requirements of fire control center

---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
General technical requirements of fire control center ICS 13.220.10 C81 People's Republic of China Public Security Industry Standards Fire control room General technical requirements 2008-04-16 release 2008-07-01 implementation People's Republic of China Ministry of Public Security

Table of Contents

Preface Ⅰ 1 Scope 1 2 Normative references 1 3 General requirements 1 4 Fire Safety Management 1 5 control and display requirements 2 6 The information recording claim 4 7 information transfer requirements 4 Appendix A (normative) building fire protection facilities operating status information 5 Appendix B (normative) Fire Safety Management Information 6

Foreword

The standard Chapter 3 ~ Chapter 7 content is mandatory, the rest are recommended. This standard was proposed by the Ministry of Public Security Fire Department. This standard by the National Standardization Technical Committee on Fire Sixth Technical Committee (SAC/TC113/SC6) centralized. This standard is drafted by. Ministry of Public Security Shenyang Fire Research Institute. This standard participated in the drafting unit. Liaoning Province Public Security Fire Department, Zhejiang Province Public Security Fire Department, Xi'an System Sensor Electronics Co., Ltd., the Gulf Security Technology Co., Ltd., Shanghai Songjiang Electronic Instrument Factory, Beijing Leader Huaxin Electronics Co., Ltd., Beijing Lion Island Fire Electronics Co., Hebei Beida Jade Bird Universal Fire Equipment Co., Ltd., Nanjing Fire Equipment Co., Ltd., China and Angola Fire Safety Engineering Limited, Beijing Lihua Fire Engineering Company. Drafters of this standard. Guotie Nan, Zhu Liping, Ding Hongjun, Ma Hang, Pan Gang, Shen Wen, Qu Li, Zhang Ying Cong, Liu Fang, Zhao Qingping, Marcin, Yuping. Fire control room General technical requirements

1 Scope

This standard specifies the general requirements for fire control room, fire safety management, control and display requirements, information recording requirements, information transmission Claim. This standard applies to GB 50116 stipulated centralized fire alarm system, alarm system control center in the fire control room or fire control center.

2 Normative references

The following documents contain provisions which, through reference in this standard and become the standard terms. For dated references, subsequent Amendments (not including errata content) or revisions do not apply to this standard, however, encourage the parties to the agreement are based on research Whether the latest versions of these documents. For undated reference documents, the latest versions apply to this standard. Automatic GB 50116 fire alarm system design specifications GA 587 building fire protection facilities maintenance and management

3 General requirements

3.1 fire control room should be at least fire alarm controller, fire linkage controller, fire control room graphical display device or combination of devices composition. 3.2 Fire control room should be able to monitor and display the building fire protection facilities operating status information, display of fire safety management information, and city fire Remote monitoring center (hereinafter referred to as the control center) transport-related information. Building fire run dynamic information in Appendix A; Fire Safety Management Information, see Appendix B. 3.3 Fire control room to control fire safety systems and equipment, display, information transmission and information records should meet the requirements of this standard. 3.4 two or more fire control room when the network on a fire control room should be able to display a fire control room fire protection systems and equipment Status information, and on the next level fire control room control; the next level fire control room should be able to fire safety systems and equipment controlled Status information is transmitted to a fire control room; you can transfer each other the same level of fire control room display status information, but not each other Phase control. 3.5 fire control room fire fighting equipment should be in line with national product on market access system. Other requirements for the fire control room should be consistent Existing national standards. Should meet the system compatibility requirements between 3.6 fire control system.

4 Fire Safety Management

4.1 Fire control room data 4.1.1 The fire control room should be built (structure) of the total floorplan after completion, building fire floorplan building fire System diagram and safe exit layout, key parts of the map and the like. 4.1.2 The fire control room should be fire safety management rules and regulations, emergency fire plan, emergency evacuation and so on. 4.1.3 The fire control room should be fire safety organization chart, including fire safety responsibilities, administrator, full-time duty firefighters and other content. 4.1.4 The fire control room should be employee fire safety training records, emergency drills record Fire and emergency evacuation of. 4.1.5 fire control room should be on duty, fire safety inspection records situation and inspection conditions. 4.1.6 fire control room should fire a list of facilities, including the type of fire-fighting facilities, number, status, and so on.