GB/T 24919-2010_English: PDF (GB/T24919-2010)
Standard ID | Contents [version] | USD | STEP2 | [PDF] delivered in | Standard Title (Description) | Status | PDF |
GB/T 24919-2010 | English | 139 |
Add to Cart
|
3 days [Need to translate]
|
Installation, operation, maintenance of industrial valves -- General requirements
| Valid |
GB/T 24919-2010
|
Standard ID | GB/T 24919-2010 (GB/T24919-2010) | Description (Translated English) | Installation, operation, maintenance of industrial valves. General requirements | Sector / Industry | National Standard (Recommended) | Classification of Chinese Standard | J16 | Classification of International Standard | 23.060.01 | Word Count Estimation | 6,666 | Date of Issue | 2009-08-09 | Date of Implementation | 2010-12-31 | Quoted Standard | GB/T 13927; JB/T 9092 | Drafting Organization | Hefei General Machinery Research Institute | Administrative Organization | National Technical Committee of Standardization valve | Regulation (derived from) | National Standard Approval Announcement 2010 No.3 (Total No.158) | Proposing organization | China Machinery Industry Federation | Issuing agency(ies) | Administration of Quality Supervision, Inspection and Quarantine of People's Republic of China; Standardization Administration of China | Summary | This standard specifies the industrial metal valve installation, generally require maintenance, use. This standard applies to the gates, closing reading, Festival mayonnaise stuffy, ball, parade wide, diaphragm, cocks wide, backstop Court, safety valve, valve, trap, regulating valves and other valves. |
GB/T 24919-2010
Installation, operation, maintenance of industrial valves. General requirements
ICS 23.060.01
J16
National Standards of People's Republic of China
Industrial Valve installation maintenance general requirements
Instalation, operation, maintenanceofindustrialvalves-
Posted 2009-08-09
2010-12-31 implementation
Administration of Quality Supervision, Inspection and Quarantine of People's Republic of China
Standardization Administration of China released
Foreword
The standard proposed by China Machinery Industry Federation.
The standard valve by the National Standardization Technical Committee (SAC/TC188) centralized.
This standard was drafted. Hefei General Machinery Research Institute, Suzhou Neway Valve Co., Ltd., Wuhan Boiler Group Valve Co., Ltd.
The main drafters. Zhang Jiwei, high Kaike, Feng Yan.
Industrial Valve installation maintenance general requirements
1 Scope
This standard specifies the general requirements for industrial metal valve installation, use and maintenance.
This standard applies to gate, globe valves, throttle valves, ball valves, butterfly valves, diaphragm valves, plug valves, check valves, safety valves, pressure reducing valves, steam traps,
Control valves and other types of valves.
2 Normative references
The following documents contain provisions which, through reference in this standard and become the standard terms. For dated references, subsequent
Amendments (not including errata content) or revisions do not apply to this standard, however, encourage the parties to the agreement are based on research
Whether the latest versions of these documents, undated reference documents, the latest versions apply to this standard.
GB/T 13927 Industrial valves pressure test (GB/T 13927-2008, ISO /DIS5208.2007, MOD)
Inspection and testing JB/T 9092 valve
3 Definition of Terms
The following terms and definitions apply to this standard.
3.1
Connection Type connectionmode
Way valve end of the pipe or equipment connections, including flanged, threaded connections, welded connections, clamp connections.
3.2
Driven approach drivingmeans
Actuate the valve operation mode, there are self-operated and external drive. Self refers to the valve for the internal medium pressure, temperature, etc. formed
Hard drive spool and other moving parts; rely on external forces driving means driving the valve disc and other moving parts, including manual, electric, pneumatic, hydraulic, electromagnetic
Drive and how they drive joint.
3.3
Working standard duty
Working standard valve includes a normally open, normally closed, short-time working, continuous duty, intermittent duty cycle.
3.4
Valve failure valvefailure
Valve failure including seal failure, failure of the operation, such as the failure function. Seal failure and leakage including internal leakage. Action includes a drive failure Loss
Ling, stem stuck spool killed like. Depending on the function failure of valves and different, such as adjusting the flow rate is not accurate, reduced pressure instability, security
Pressure valve is not required to take-off and so on.
4 Installation
4.1 Pre-installation check
4.1.1 Valve installation should be checked before the valve product certification, installation instructions, etc. are complete.
4.1.2 should be visually inspected prior to valve installation shall meet the following requirements.
a) an outer surface shall not have cracks, blisters, mechanical damage, corrosion, dirt and other defects;
b) shall not fall off the nameplate, the technical parameters and system design requirements on the nameplate conform;
c) both ends of the valve should be protective cover protection;
......
|