HOME   Cart(0)   Quotation   About-Us Policy PDFs Standard-List
www.ChineseStandard.net Database: 189759 (19 Oct 2025)

GB 17429-2011 English PDF

US$439.00 · In stock
Delivery: <= 4 days. True-PDF full-copy in English will be manually translated and delivered via email.
GB 17429-2011: Fire indicating panel
Status: Valid

GB 17429: Evolution and historical versions

Standard IDContents [version]USDSTEP2[PDF] delivered inStandard Title (Description)StatusPDF
GB 17429-2011English439 Add to Cart 4 days [Need to translate] Fire indicating panel Valid GB 17429-2011
GB 17429-1998English719 Add to Cart 5 days [Need to translate] General technical conditions for fire indicating panels Obsolete GB 17429-1998

PDF similar to GB 17429-2011


Standard similar to GB 17429-2011

GB 15322.1   GB 14287.3   GB 14287.1   GB 20517   GB 16808   GB/T 45839   

Basic data

Standard ID GB 17429-2011 (GB17429-2011)
Description (Translated English) Fire indicating panel
Sector / Industry National Standard
Classification of Chinese Standard C81
Classification of International Standard 13.220.20
Word Count Estimation 19,178
Date of Issue 2011-07-29
Date of Implementation 2012-01-01
Older Standard (superseded by this standard) GB 17429-1998
Quoted Standard GB 156; GB 4706.1; GB/T 9969; GB 12978; GB 16838; GB/T 17626.2; GB/T 17626.3; GB/T 17626.4; GB/T 17626.5; GB/T 17626.6; GB/T 17626.11
Regulation (derived from) Announcement of Newly Approved National Standards No. 12 of 2011
Issuing agency(ies) General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China, Standardization Administration of the People's Republic of China
Summary This Chinese standard specifies the requirements for fire display panel, face trial, prosecutors face rules and signs. This standard applies to general industrial and civil buildings installation of fire display panel, installed in other environments with specific properties fire display panel, in addition to special requirements otherwise provided by the relevant standards, with reference to the implementation of this standard.

GB 17429-2011: Fire indicating panel

---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Fire indicating panel ICS 13.220.20 C81 National Standards of People's Republic of China Replacing GB 17429-1998 Fire Display Panels Issued on. 2011-07-29 2012-01-01 implementation Administration of Quality Supervision, Inspection and Quarantine of People's Republic of China Standardization Administration of China released

Table of Contents

Preface Ⅰ 1 Scope 1 2 Normative references 1 3 Requirements 1 4 Test 7 14 5 Inspection Rules 6 flag 14

Foreword

The standard Chapter 3, Chapter 5, Chapter 6, are mandatory, the rest are recommended. This standard was drafted in accordance with GB/T 1.1-2009 given rules. This standard replaces GB 17429-1998 "fire display panel General technical conditions." This standard compared with GB 17429-1998, the main changes are as follows. --- Original standard basic function test broken fire alarm display function test, the fault display function test, supervision alarm display function Can test, self-test function tests, information display and query functions and power test function tests (see 42, 1998 version 4.3.); --- Increased leakage current test, conducted disturbances induced by radio-frequency fields immunity test, surge (impact) immunity test, voltage sag, Short interruptions and voltage variations immunity tests, vibration (sinusoidal) (endurance) test and other test items (see 4.4,4.7,4.10, 4.11 and 4.16); --- Delete the current test, high temperature test, impact test and low temperature storage test (the 1998 edition 4.4,4.12,4.15 and 4.17); --- Increased the use of the specification and testing requirements of the rules (see 3.5 and 5). Please note that some of the content of this document may involve patents. Release mechanism of the present document does not assume responsibility for the identification of these patents. The standard proposed by the People's Republic of China Ministry of Public Security. This standard by the National Standardization Technical Committee on Fire fire detection and alarm Technical Committee (SAC/TC113/SC6) centralized. This standard is drafted by. Ministry of Public Security Shenyang Fire Research Institute. The main drafters of this standard. Wang Yane, with Rui Tao, Xie Feng, Wang Yu-line, Li Xiaobai, Guo Jinlong, Li Huijing, Yan Ru. This standard replaces the standards previously issued as follows. --- GB 17429-1998. Fire Display Panels

1 Scope

This standard specifies the requirements for fire display panel, testing, inspection rules and signs. This standard applies to general industrial and civil buildings installation of fire display panel, installed in other environments with special properties Fire Display Panels, except as otherwise provided by the special requirements of the relevant standards, with reference to the implementation of this standard.

2 Normative references

The following documents for the application of this document is essential. For dated references, only the dated version suitable for use herein Member. For undated references, the latest edition (including any amendments) applies to this document. GB 156 standard voltage Part 1 GB 4706.1 Safety of household and similar electrical appliances. General requirements GB/T 9969 General Instructions industrial products GB 12978 fire electronic products inspection rules GB 16838 fire electronic products environment test methods and severities GB/T 17626.2 Electromagnetic compatibility Testing and measurement techniques - Electrostatic discharge immunity test GB/T 17626.3 electromagnetic compatibility test and measurement technology RFEMS test GB/T 17626.4 Electromagnetic compatibility Testing and measurement techniques - Electrical fast transient burst immunity test GB/T 17626.5 electromagnetic compatibility test and measurement technology surge (impact) immunity test GB/T 17626.6 Electromagnetic compatibility Testing and measurement techniques Immunity to conducted disturbances induced field GB/T 17626.11 Electromagnetic compatibility Testing and measurement techniques - Voltage dips, short interruptions and voltage variations immunity tests

3 Requirements

3.1 General Fire Display Panels shall comply with the relevant requirements of this chapter, according to the provisions of Chapter 4 were tested to confirm compliance to the requirements of this chapter. 3.2 overall performance 3.2.1 fire display panel can be used as the main power supply 220V, 50Hz AC power supply can also be used directly or eliminate fire alarm controller Anti-DC power supply device power output, the power supply line input terminals should be located. 3.2.2 fire display panel using the main power supply is 220V, 50Hz AC power supply, it should be equipped with backup power. 3.2.3 Fire Display Panels directly from the fire alarm controllers or fire-fighting equipment supply output DC power supply, DC voltage should be consistent Provisions of GB 156, priorities DC 24V. 3.2.4 Fire Display Panels should power the other components. 3.2.5 fire display panel should not have control other components. 3.2.6 fire display panel buttons and lights should have Chinese features labeled. 3.2.7 fire display panel when using the text display information, should use Chinese display. 3.3 Basic Functions 3.3.1 Fire alarm display Fire alarm signal 3.3.1.1 fire display panel should be able to receive fire alarm controller connected thereto issued and fire alarm control Fire alarm signal shall be able to manually; send out a fire alarm sound and light signals within 3s after a fire alarm signal emitted by the display of fire site Eliminate, and then when there is a fire alarm signal input, should start again; fire alarm signal light should be kept to the fire alarm controller reset. 3.3.1.2 When the fire alarm signal received is a manual fire alarm button alarm fire display panel should be able to show that the fire alarm signal Number of manual fire alarm button alarm. 3.3.1.3 fire display panel should always have special fire lights, fire display panel is in fire alarm state, the LED should light up. 3.3.1.4 fire display panel should be able to show all fire alarms within its set area-wide information. Fire alarm signal using the display At rest, such as fire alarm can not display all the information should be displayed first fire alarm, fire alarm information should be able to follow the manual to be investigated, Each time a query manually, only the query part of a fire alarm and related information, inquiries end within 1min, should automatically return to display the first fire Disaster warning information; when automatic cycle display subsequent fire alarm message to be displayed every time a complete fire alarm information, The first fire alarm should be at the top of the monitor or use a separate monitor individual display, manual query should take precedence. 3.3.1.5 fire display panel to show that the agreed time time the fire alarm, the time should fire alarm controller display. 3.3.1.6 In addition to fire alarm controller reset operation, any operation on the display panel of the fire should not affect the incoming and outgoing packets fire An alarm signal. 3.3.2 Fault display 3.3.2.1 using the main power supply is 220V, 50Hz AC power supply fire display panel, in the event of the following conditions should be made in the 100s Failed sound and light signals, and displays the type of fault; fault acoustic signal should sound the fire alarm signal is significantly different; fault signal should sound expert Move eliminated, then there is a fault signal input, should start again; fault signal light should be kept to troubleshoot or fire alarm controller reset. a) to the backup power supply and standby power charger for charging between the cable circuit, short circuit; b) when the cable open circuit, short circuit and standby power backup power supply and its load between the separate power supply voltage is not sufficient to ensure the fire was Shows the disk is working properly; c) main power supply undervoltage. Fire Display Panels 3.3.2.2 with fault display function should have special total failure indicator, when there is a fault signal is present, the indicator It should be lit. 3.3.2.3 has received the fire alarm controller came fire detectors, manual fire alarm buttons and other fire alarm trigger member Fault sound, light signals emitted within 3s after fire fault signal function display panel, should signal a fault in the fire alarm controller indicating it Barrier site of occurrence; fault acoustic signal should sound the fire alarm signal is significantly different; failure acoustic signal should be able to eliminate the manual, then a fault signal output Pops, should start again; fault signal light and fire alarm controller should be appropriate in a consistent state. 3.3.2.4 fire with fault display function display panel should be able to show all their fault information within the scope of the set area, in the same time was not All information is shown when a fault, fault information is not displayed in the manual should be investigated. 3.3.2.5 any fault shall not affect the normal operation of the non-defective part. 3.3.3 Regulatory alarm display 3.3.3.1 Regulatory alarm display functionality requires a fire only for having this feature display panel. Fire Display Panels 3.3.3.2 have regulatory alarm display should have special regulatory total indicator, as long as the alarm signal output regulation Into the light should be lit. 3.3.3.3 have regulatory fire alarm display function display panel should be able to receive supervision alarm signals coming from the fire alarm control and fire Disaster alarm controller issued after the issue of regulatory supervision alarm signals within 3s alarm sound and light signal indicating that the regulatory site alarm; alarm supervision Letter No fire alarm sound signal should be a clear distinction; when supervision alarm signal should be able to eliminate the manual, and then there are regulatory alarm signal input, should again Start; light alarm signal should be supervision and fire alarm controller corresponding state agreement. 3.3.3.4 have regulatory fire alarm display function display panel should be able to display all alarm information within its regulatory scope of the set area, not When the alarm can simultaneously display all regulatory information, regulatory alarms should be investigated manually, not shown. 3.3.4 Self-test function Fire Display Panels should manually check their audio devices, and all indicators on the front panel displays the operating status. Self Test Among more than 1min or not automatically stop the self-test, if the input signal should automatically indicate the corresponding status, and displays the corresponding information. 3.3.5 information display and query functions 3.3.5.1 fire display panel or information to display should fire alarm, supervisory alarm, fault arranged in descending order display class, high-grade The information should be displayed by priority, low level of information should not affect the display of high-grade information display, information display should be consistent with the corresponding state and easy To identify. 3.3.5.2 When the fire display panel is at a high level of information to display, you should be able to manually query other low-level information. 3.3.5.3 each grade and should not be displayed alternately. 3.3.6 Power Capability 3.3.6.1 using the main power supply is 220V, 50Hz AC power supply fire display panel should have the following features. a) should have a main power supply and backup power conversion. When the main power fails, it should automatically switch to standby power; when the main power is restored , Should automatically switch to the main power supply; there should be main and backup power supply status indicator; main and backup power conversion should not affect the fire show Normal operation of the disc; b) the main power supply should be able to ensure continuous operation 4h fire display panel in fire alarm state, and should have over-current protection measures; c) When the AC power supply voltage fluctuation range within the rated voltage (220V) 85% to 110% range, a frequency of 50Hz ± 1Hz, the Fire Display Panels should be able to work properly; d) standby power in the discharge to the termination voltage condition, charging 24h, its capacity should be able to provide fire display panel in the normal monitoring state After work 8h, working in fire alarm status 30min. 85% to 110% of the range 3.3.6.2 using fire alarm controllers or fire-fighting equipment powered fire display panel rated voltage Should be able to work in fire alarm state should be able to work continuously 4h. 3.4 The main portion (device) member performance 3.4.1 Main unit (device) member selection The main portion of the fire display panel (device) member, should comply with the relevant standards of styling products. 3.4.2 Indicator 3.4.2.1 should be a red light indicates the status of the fire alarm, supervisory alarm status; yellow light indicates a fault status; green indicator means It shows the power the state and normal state. 3.4.2.2 Application of Chinese lights clearly marked its features. 3.4.2.3 In no more than 500lx ambient light conditions, in front of 22.5 ° angle range, status and power LEDs should 3m place clearly visible; the other indicators should be clearly visible at 0.8m. 3.4.3 Monitor Not more than 500lx ambient light conditions, in front of 22.5 ° viewing angle, display characters or words should Legible at 0.8m. 3.4.4 Audio Device 3.4.4.1 Under normal operating conditions, sound device SPL (A weighted) at 1m directly in front of it should be greater than 65dB, less than 115dB. 3.4.4.2 at 85% of rated voltage power supply conditions, fire display panel sound device should work correctly. 3.4.5 Fuse Fuses for overcurrent protection devices or other power lines, the rated current value should generally be less than its maximum operating current 2 times. Near the fuses or other overcurrent protection devices should be clearly marked at its value. 3.4.6 Terminals 3.4.6.1 On each of the terminals should be clear, firmly marked their numbers or symbols corresponding use shall be stated in the relevant documents. 3.4.6.2 main power supply with 220V, 50Hz AC power supply should be protected by fire display panel ground terminal and ground logo. 3.4.7 charger and backup power 3.4.7.1 standby power of positive and negative connecting wires should be color-coded red should be positive, negative shall be black or blue. 3.4.7.2 standby power charge current should not exceed the battery manufacturer's specified rating. 3.4.8 Switches and buttons Switches and buttons should be on or near the location of the Chinese clearly indicate its function. 3.4.9 Operation Level Operating Level fire display panel should meet the requirements of Table 1. Enter Ⅱ, Ⅲ grade operating functional status should be used operation number or key for Level operations into the Ⅲ functional status of the operation or the number keys can be used to enter the operating level Ⅱ functional status, but for operational functions like entering grade Ⅱ State operation can not be used to enter numbers or key operating functions Ⅲ grade status. Table 1 fire display panel operating level allocation table No. Action Project Operation Level Ⅰ Ⅱ Ⅲ

1 eliminate acoustic signal OMM

2 query information OMM

3 Self-Test PMM

4 Enter or change the data PPM

5 turned on and off or adjust the power PPM

6 modify or change software and hardware PPM

Note. P --- disable in this level of operation; O --- choose whether the present level of operation; M --- available for this level and this level following. 3.5 User's Guide Fire Display Panels should be a corresponding Chinese instructions. Instructions content should be consistent with GB/T 9969 requirements and product Consistent performance. 3.6 Insulation resistance Insulation resistance value of the external insulation requirements between live terminal and chassis shall be not less than 20MΩ; use 220V, 50Hz AC power supply Insulation resistance value-powered fire display panel of the chassis between the power input and shall be not less than 50MΩ. Leakage current 3.7 Using 220V, 50Hz AC power supply fire display panel at 1.06 times the rated voltage, the leakage current should be less than 0.5mA. 3.8 Electric strength Use between 220V, 50Hz AC power supply fire display panel power plug (or power terminals) and the chassis should be able to withstand frequent Rate of 50Hz, the effective value of the AC voltage 1250V lasted 1min the electric strength test. During the test, the breakdown should not occur; After the test, the basic functions should be consistent with the previous test. 3.9 Electromagnetic compatibility Fire Display Panels should be able to adapt to the requirements of the tests specified in Table 2 under the conditions. During the test, it should maintain a normal monitoring state; test After basic functions should be consistent with the previous test. Table 2 EMC test conditions Name of test Test conditions Radio frequency electromagnetic Anti-radiation field Interference Test Field strength V/m Frequency Range MHz Scan rate ten Octave per second Modulation amplitude working condition 10 80 ~ 1000 ≤1.5 × 10-3 80% (1kHz, Sine) Normal prison Depending on the state of RF induction field Conducted disturbances Immunity Test DBμV Frequency range MHz voltage modulation amplitude working condition 0.15 ~ 80 140 80% (1kHz, sine) Normal monitoring status Anti-static discharge Interference Test Discharge voltage kV Discharge polarity Discharge interval Each point of discharge Power Ups Working condition Air discharge (insulator shell) 8 Contact discharge (shell conductor) 6 Positive and negative ≥1 10 Normal prison Depending on the state of Electrical fast transient Variable burst anti- Interference Test Voltage peak kV repeat frequency kHz polarity time min Working condition AC power cord. 2 × (1 ± 0.1) Other cables. 1 × (1 ± 0.1) AC power cord. 2.5 × (1 ± 0.2) Other cable. 5 × (1 ± 0.2) Positive and negative each time Normal prison Depending on the state of Surge (impact) Immunity Test Surge (impact) voltage kV polarity duration ms The number of trials work status AC power cord - Line. 1 × (1 ± 0.1) AC power cord - to. 2 × (1 ± 0.1) Other cable lines - to. 1 × (1 ± 0.1) Positive and negative 10 (decline 100%) AC power cord. 5 Other cables. 20 Normal monitoring status TABLE 2 (cont.) Name of test Test conditions Voltage dips, Short interruptions and Voltage changes Immunity Test Test time Rated voltage period The number of trials work status 10 (40% supply voltage) 1 (0V) Normal monitoring status 3.10 transient power tolerance Fire Display Press the main power panel "power (9s) ~ power (1s)" fixed program continuously off 500 times. During the test, should remain positive Often monitoring state; After the test, the basic functions should be consistent with the previous test. 3.11 Climate tolerance Fire Display Panels shall withstand the test under live table 3 as specified in climate conditions. During the test, should remain normal surveillance State; After the test, should be no damage to the coating and corrosion, the basic functions should be consistent with the previous test. Table 3 climate conditions Name of test Test conditions Low temperature (running) test temperature duration Working condition 0 ± 3 16 normal surveillance state Damp (run) test temperature Relative humidity duration Working condition 40 ± 2 90 ~ 95 4 normal surveillance state 3.12 Mechanical environmental resistance Fire Display Panels should be able to withstand the live test as specified in Table 4 Mechanical environmental conditions. During the test, the power-on state Fire Display Panels should maintain a normal monitoring state; after the test should not have mechanical damage and tighten loose parts, the basic functions should be before the test be consistent. Table 4 Mechanical ambient conditions Name of test Test conditions Vibration (sinusoidal) (Running) test Loop frequency range Hz Acceleration amplitude m/s2 Sweep rate oct/min Each axis Sweep times The vibration direction of the work of state 10 ~ 150 0.981 1 1 X, Y, Z normal monitoring state Vibration (sinusoidal) (Durability Test Loop frequency range Hz Acceleration amplitude m/s2 Sweep rate oct/min Each axis Sweep times The vibration direction of the work of state 10 ~ 150 4.905 1 20 X, Y, Z is not energized Table 4 (Continued) Name of test Test conditions Crash Test Collision energy The number of collisions working condition 0.5 ± 0.04 3 normal surveillance state

4 Test

4.1 General 4.1.1 Test Procedure Fire Display Panels test procedure are shown in Table 5. Table 5 Fire Display Panels Test Procedure Reg number of pilot projects Sample No. 4.1.5 Test 1 Check before √ √ 2 4.2 Basic function test √ √ 3 4.3 Insulation resistance test √ 4 4.4 leakage current test √ 5 4.5 Electric strength test √ 6 4.6 RFEMS test √ 7 4.7 RF field immunity test conducted disturbances induced √ 8 4.8 Electrostatic discharge immunity test √ 9 4.9 Electrical fast transient burst immunity test √ 10 4.10 surge (impact) immunity test √ 11 4.11 Voltage dips, short interruptions and voltage variations immunity tests √ 12 4.12 Power transient test √ 13 4.13 low temperature (operation) test √ 14 4.14 Damp heat (run) test √ 15 4.15 vibration (sinusoidal) (run) test √ 16 4.16 vibration (sinusoidal) (endurance) test √ Crash Test √ 17 4.17 4.1.2 Test Samples Test sample (hereinafter referred to as samples) for two samples shall be numbered before the test. 4.1.3 Test atmospheric conditions If there is no description of the relevant provisions, the various tests were carried out under the following atmospheric conditions. --- Temperature. 15 ℃ ~ 35 ℃; --- Humidity. 25% RH ~ 75% RH; --- Atmospheric pressure. 86kPa ~ 106kPa. 4.1.4 Tolerance If there is no description of the relevant provisions, the tolerance of the test data are ± 5%. 4.1.5 Check before test The specimen before the test should be carried out and the appearance of the main unit (unit) members examination before the test if the following requirements. a) text, symbols and signs clear and complete; b) the specimen surface without corrosion, coating loss and blistering, no scratches, cracks, burrs and other mechanical damage; c) no loosening the fastening portion; d) overall performance should meet the requirements of 3.2; e) The main unit (device) member should be able to meet the performance requirements of 3.4; f) instructions shall satisfy the requirements of 3.5. 4.2 Basic function test 4.2.1 Fire alarm display function test 4.2.1.1 The sample with the manufacturer of fire alarm control (fire alarm controller should be connected according to the manual fire alarm test requires Buttons and fire detectors) are connected to power, the sample in the normal monitoring state. 4.2.1.2 Setting a fire alarm, a fire alarm signal from the recording issued fire alarm controller to send out a fire alarm signal sample Intervals, observe and record the sample status, and information display case; after manual sample silencer, and then set another fire alarm Signal, observe and record the sample again to start the fire alarm signal conditions and the information display case. 4.2.1.3 In the manual fire alarm button alarm status, observe and record the sample information display case. 4.2.1.4 manual reset fire alarm controller, observe and record the state of the sample instructions and information display cases. 4.2.1.5 When the sample is manually operated to set a fire alarm signal, observe and record the samples and send out a fire alarm signal receiving Happening. 4.2.1.6 In the case of multiple fire alarm information exists, to view and record the sample information display case. 4.2.2 Fault display function test 4.2.2.1 The fire alarm sample and the manufacturer's controller is connected to power, it is in the normal monitoring state. 4.2.2.2 For the main power supply is 220V, 50Hz AC power supply of the sample, are provided in 3.3.2.1 a), b), c) three kinds of failure Situation, observe and record the status indication and specimen information display case. 4.2.2.3 so that the fire alarm controller Fault signaling a fire alarm trigger member, recording a fault from the fire alarm controller To signal a fault signal sample intervals, observe and record the state of the sample instructions and informatio...