US$85.00 · In stock · Download in 9 secondsGB/T 12326-2008: Power quality - Voltage fluctuation and flicker Delivery: 9 seconds. True-PDF full-copy in English & invoice will be downloaded + auto-delivered via email. See step-by-step procedureStatus: Valid GB/T 12326: Evolution and historical versions
| Standard ID | Contents [version] | USD | STEP2 | [PDF] delivery | Name of Chinese Standard | Status |
| GB/T 12326-2008 | English | 85 |
Add to Cart
|
0-9 seconds. Auto-delivery
|
Power quality - Voltage fluctuation and flicker
| Valid |
| GB 12326-2000 | English | 719 |
Add to Cart
|
5 days
|
Specifications for hydrographic survey
| Obsolete |
| GB 12326-1990 | English | RFQ |
ASK
|
3 days
|
Quality of electric energy supply--Admissible voltage fluctuation and flicker
| Obsolete |
Excerpted PDFs (Download full copy in 9 seconds upon purchase)PDF Preview: GB/T 12326-2008
GB/T 12326-2008: Power quality - Voltage fluctuation and flicker---This is an excerpt. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.), auto-downloaded/delivered in 9 seconds, can be purchased online: https://www.ChineseStandard.net/PDF.aspx/GBT12326-2008
GB
NATIONAL STANDARD
ICS 27.100
F 020
Replacing GB 12326-2000
Power quality - Voltage fluctuation and flicker
Issued on. JUNE 18, 2008
Implemented on. MAY 1, 2009
Issued by. General Administration of Quality Supervision, Inspection and
Quarantine;
Standardization Administration Committee.
Table of Contents
Foreword... 3
1 Scope... 5
2 Normative references... 5
3 Terms and definitions... 5
4 Limits of voltage fluctuation... 7
5 Limits of flicker... 7
6 Measurement and estimation of voltage fluctuation... 9
7 Flicker measurement and calculation... 11
8 Superposition and transfer of flicker... 12
Annex A (Normative) Flicker measurement and calculation formulas... 15
Annex B (Informative) Estimation method for total supply capacity StHV of high
voltage (HV)... 19
Annex C (Informative) Estimation method for flicker of electric arc... 20
Annex D (Informative) Statistical method of flicker qualification rate... 21
Bibliography... 22
1 Scope
This Standard specifies the limits and test, calculation and evaluation methods
of voltage fluctuation and flicker.
This Standard is applicable to the rapid change of the voltage of the common
connection point caused by the fluctuating load under the normal operation
mode of the AC 50Hz power system and the occasion where people may
obviously feel the light flicker.
2 Normative references
The following standards contain the provisions which, through reference in this
Standard, constitute the provisions of this Standard. For dated references,
subsequent amendments (excluding corrections) or revisions do not apply to
this Standard. However, the parties who enter into agreement based on this
Standard are encouraged to investigate whether the latest versions of these
documents are applicable. For undated reference documents, the latest
versions apply to this Standard.
GB/T 156-2007 Standard voltage (IEC 60038.2002, MOD)
GB 17625.2 Electromagnetic compatibility (EMC) - Limits - Limitation of
voltage changes, voltage fluctuations and flicker in public low-voltage supply
systems, for equipment with rated current ≤ 16 A (GB 17625.2-2007, IEC
61000-3-3.2005, IDT)
GB/Z 17625.3 Electromagnetic compatibility--Limits--Limitation of voltage
fluctuations and flicker in low-voltage power supply systems for equipment
with rated current greater than 16A (GB/Z 17625.3-2000, idt IEC 61000-3-
5.1994)
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1 point of common coupling; PCC
the connection of more than one user in an electrical system
3.2 fluctuating load
the load of varying power periodically or un-periodically taken from the supply
network during production (or operation); for example, steel-making electric arc
furnace, rolling mill, arc welding machine
3.3 voltage fluctuation
a series of changes or successive changes in R.M.S. (valid value)
3.4 R.M.S. voltage shape; U(t)
time function of periodic R.M.S. (valid value) per half fundamental wave voltage
3.9 long term severity; Plt
calculated from the short-term flicker value Pst; reflects the magnitude of the
flicker for a long time (several hours) (see Annex A); the basic recording period
for long-term flicker is 2 h
3.10 cumulative probability function; CPF
the abscissa represents the measured value, and the ordinate represents the
percentage of time over the corresponding abscissa value for the total
measured time (see Figure 2)
4 Limits of voltage fluctuation
For the voltage fluctuation caused by point of common coupling in power
system for any fluctuating load user, its limits are related to voltage change
frequency and voltage level. For low voltage fluctuation frequency (e.g. r ≤ 1000
times/h) or regular periodic voltage fluctuation, its voltage fluctuation frequency
and voltage fluctuation value can be determined by the measurement of R.M.S.
voltage shape U(t). The limits of voltage fluctuation are shown in Table 1.
5 Limits of flicker
5.1 For point of common coupling of power system, in the smaller mode of
normal operation of the system, taking a week (168 h) as the measurement
cycle, all long-term flicker values Plt shall meet the requirements of Table 2 for
flicker limits.
5.2 Usually, the flicker value caused by point of common coupling in power
system alone of any fluctuating load user shall meet the following requirements.
5.2.4 The third level regulation. For the single fluctuating load user which does
not comply with the regulations of the second level, if it still exceeds its flicker
limits after treatment, it shall relax the limit appropriately, based on PCC point
actual flicker conditions and development forecast of grid. However, the flicker
value of PCC point must comply with the provisions of 5.1.
6 Measurement and estimation of voltage fluctuation
The voltage fluctuation can be described by R.M.S. voltage shape U(t). The
relative voltage change d and rate of occurrence of voltage changes r are
indicators to measure the voltage fluctuation size and speed.
The relative voltage change d can be defined as.
8 Superposition and transfer of flicker
8.1 The flicker and background flicker caused by n fluctuating loads are
superimposed on the same node. Its short term severity can be calculated by
the following formula.
8.2 The transfer of flicker on different bus bars in power system is shown as
Figure 2.It can be calculated by the following simplified formula.
...... Source: Above contents are excerpted from the full-copy PDF -- translated/reviewed by: www.ChineseStandard.net / Wayne Zheng et al.
Tips & Frequently Asked QuestionsQuestion 1: How long will the true-PDF of English version of GB/T 12326-2008 be delivered?Answer: The full copy PDF of English version of GB/T 12326-2008 can be downloaded in 9 seconds, and it will also be emailed to you in 9 seconds (double mechanisms to ensure the delivery reliably), with PDF-invoice. Question 2: Can I share the purchased PDF of GB/T 12326-2008_English with my colleagues?Answer: Yes. The purchased PDF of GB/T 12326-2008_English will be deemed to be sold to your employer/organization who actually paid for it, including your colleagues and your employer's intranet. Question 3: Does the price include tax/VAT?Answer: Yes. Our tax invoice, downloaded/delivered in 9 seconds, includes all tax/VAT and complies with 100+ countries' tax regulations (tax exempted in 100+ countries) -- See Avoidance of Double Taxation Agreements (DTAs): List of DTAs signed between Singapore and 100+ countriesQuestion 4: Do you accept my currency other than USD?Answer: Yes. www.ChineseStandard.us -- GB/T 12326-2008 -- Click this link and select your country/currency to pay, the exact amount in your currency will be printed on the invoice. Full PDF will also be downloaded/emailed in 9 seconds. Question 5: Should I purchase the latest version GB/T 12326-2008?Answer: Yes. Unless special scenarios such as technical constraints or academic study, you should always prioritize to purchase the latest version GB/T 12326-2008 even if the enforcement date is in future. Complying with the latest version means that, by default, it also complies with all the earlier versions, technically.
How to buy and download a true PDF of English version of GB/T 12326-2008?A step-by-step guide to download PDF of GB/T 12326-2008_EnglishStep 1: Visit website https://www.ChineseStandard.net (Pay in USD), or https://www.ChineseStandard.us (Pay in any currencies such as Euro, KRW, JPY, AUD). Step 2: Search keyword "GB/T 12326-2008". Step 3: Click "Add to Cart". If multiple PDFs are required, repeat steps 2 and 3 to add up to 12 PDFs to cart. Step 4: Select payment option (Via payment agents Stripe or PayPal). Step 5: Customize Tax Invoice -- Fill up your email etc. Step 6: Click "Checkout". Step 7: Make payment by credit card, PayPal, Google Pay etc. After the payment is completed and in 9 seconds, you will receive 2 emails attached with the purchased PDFs and PDF-invoice, respectively. Step 8: Optional -- Go to download PDF. Step 9: Optional -- Click Open/Download PDF to download PDFs and invoice. See screenshots for above steps: Steps 1~3 Steps 4~6 Step 7 Step 8 Step 9
|