HOME   Cart(0)   Quotation   About-Us Policy PDFs Standard-List
www.ChineseStandard.net Database: 189760 (18 Oct 2025)

GA/T 798-2008 English PDF

Standard IDContents [version]USDSTEP2[PDF] delivered inStandard Title (Description)StatusPDF
GA/T 798-2008English479 Add to Cart 3 days [Need to translate] Vapor exhaust and fire resisting check damper Obsolete GA/T 798-2008

PDF similar to GA/T 798-2008


Standard similar to GA/T 798-2008

GB/T 9978.1   GB/T 7633   GA/T 537   

Basic data

Standard ID GA/T 798-2008 (GA/T798-2008)
Description (Translated English) Vapor exhaust and fire resisting check damper
Sector / Industry Public Security (Police) Industry Standard (Recommended)
Classification of Chinese Standard C82
Classification of International Standard 13.220.50
Word Count Estimation 12,150
Date of Issue 2008-08-26
Date of Implementation 2008-10-01
Quoted Standard GB/T 191; GB 9969.1; GB/T 13306; GB/T 13384; GB/T 14436; GB 15930-2007
Issuing agency(ies) Ministry of Public Security
Summary This standard specifies the terms and definitions, classification, code and model markings, materials and structures, requirements, test methods, inspection rules, marking, packaging, storage and transportation of exhaust fume fire prevention check valves (hereinafter referred to as check valves) Instructions and storage. This standard is applicable to the non-return valve provided on the common exhaust pipe of the kitchen exhaust fume collection pipe and the toilet in the building.

GA/T 798-2008: Vapor exhaust and fire resisting check damper

---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Vapor exhaust and fire resisting check damper ICS 13.220.50 C82 People's Republic of China public safety industry standards Exhaust gas fire check valve 2008-08-26 released 2008-10-01 implementation Ministry of Public Security of People's Republic of China released Directory Foreword Ⅲ 1 Scope 1 2 Normative references 1 3 Terms and definitions 1 4 classification, code and model mark 2 5 Materials and Structure 2 6 Requirements 2 6.1 Appearance 2 6.2 valve opening angle 3 6.3 Reset function 3 6.4 temperature sensor 3 6.5 Warning sign or signal of fault status 3 6.6 Kai, close reliability 3 6.7 Corrosion resistance 3 6.8 air leakage at ambient temperature 3 6.9 Fire resistance 3 7 test method 3 7.1 Appearance 3 7.2 valve opening angle 4 7.3 Reset Function 4 7.4 temperature sensor 4 7.5 Warning sign or signal of fault status 4 7.6 Kai, close reliability 5 7.7 Corrosion resistance 5 7.8 air leakage at ambient temperature 5 7.9 fire resistance 5 8 inspection rules 5 8.1 factory inspection 5 8.2 type test 6 9 signs, packaging, storage and transportation, user manual and storage 8 9.1 mark 8 9.2 Packaging, storage and transportation, user manual 8 9.3 Storage 8 Appendix A (Informative) Check valve opening angle measurement and calculation methods 9

Foreword

Appendix A of this standard is an informative annex. This standard proposed by the Ministry of Public Security Fire Station. This standard by the National Standardization Technical Committee Fire Building Components fire resistance Technical Committee (SAC/TC113/SC8) centralized. This standard is drafted by. Ministry of Public Security Tianjin Institute of Fire. Participated in the drafting of this standard. Nanjing super-green building materials Co., Ltd.. The main drafters of this standard. Wang Yiqing, Song Huan pupil, Dong Xuejing, Li Xiquan, Sun Weidong, Hang Zhao, Zhao Qingsong. This standard is released for the first time. Exhaust gas fire check valve

1 Scope

This standard specifies the exhaust fume fire check valve (hereinafter referred to as check valve) terms and definitions, classification, code and model markings, materials And structure, requirements, test methods, inspection rules, signs, packaging, storage and transportation, user manual and storage. This standard applies to the building kitchen exhaust fume centralized pipe and bathroom exhaust pipe set on the common check valve.

2 Normative references

The following documents contain provisions which, through reference in this standard and become the standard terms. All dated references, which are subsequently owned Amendments (not including errata content) or revisions do not apply to this standard, however, encourage the parties to reach an agreement based on this standard research Whether you can use the latest versions of these files. For undated references, the latest version applies to this standard. GB/T 191 Packaging - Pictorial signs (GB/T 191-2008, ISO 780..1997, MOD) GB 9969.1 Industrial Products Manual General GB/T 13306 signs GB/T 13384 mechanical and electrical product packaging General technical conditions GB/T 14436 Industrial product assurance documents General Fire protection valves for building ventilation and smoke extraction systems

3 Terms and definitions

GB 15930-2007 established and the following terms and definitions apply to this standard. 3.1 Installed in the kitchen exhaust hood or bathroom exhaust fan back to the end of a common fire-rated exhaust pipe inlet, the fan was working Open state (exhaust emissions), the fan does not work in a natural off state (to prevent the exhaust gas backflow), indoor or shared duct temperature reached regulation Set value can be automatically shut down, and within a specified time to meet the fire resistance requirements, play the role of smoke valve fire. 3.2 Check valve in the open state, when the temperature sensing element to the state when the valve is closed. 3.3 Check valve in the exhaust fan to stop working, the valve will naturally fall off and closed state. 3.4 Check valve in the non-return state, when the temperature sensing element to the state when the valve is closed. In this state of the valve, without reset, will be Can not be opened by fan power. 3.5 In the check valve inlet pressure higher than the outlet pressure, the difference between import and export pressure.