HOME   Cart(0)   Quotation   About-Us Policy PDFs Standard-List
www.ChineseStandard.net Database: 189760 (18 Oct 2025)

GA 703-2007 English PDF

Standard IDContents [version]USDSTEP2[PDF] delivered inStandard Title (Description)StatusPDF
GA 703-2007English279 Add to Cart 3 days [Need to translate] Fire safety requirement for the place combined with habitation, production, storage and busioness Obsolete GA 703-2007

PDF similar to GA 703-2007


Standard similar to GA 703-2007

GB 13495.1   GB 8624   GB/T 8626   GA/T 974.4   

Basic data

Standard ID GA 703-2007 (GA703-2007)
Description (Translated English) Fire safety requirement for the place combined with habitation, production, storage and busioness
Sector / Industry Public Security (Police) Industry Standard
Classification of Chinese Standard C80
Classification of International Standard 13.220.20
Word Count Estimation 7,734
Date of Issue 2007-06-13
Date of Implementation 2007-08-01
Quoted Standard GB 20517; GB 50016; GB 50084; GB 50116; GB 50140; GB 50222; GB 50354
Issuing agency(ies) Ministry of Public Security
Summary This standard specifies the conditions for the combination of accommodation, production, storage and operation (commonly known as "triple play", hereinafter referred to as the "joint site"), and provides for fire separation measures, evacuation measures, fire fighting facilities, And other fire safety technical requirements. This standard applies to residential and production storage and operation of the place of fire safety management.

GA 703-2007: Fire safety requirement for the place combined with habitation, production, storage and busioness


---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Fire safety requirement for the place combined with habitation, production, storage and busioness ICS 13.220.20 C80 People's Republic of China Public Security Industry Standards Accommodation and combined production and storage business premises Fire Safety Requirements Posted 2007-06-13 2007-08-01 implementation People's Republic of China Ministry of Public Security

Table of Contents

Preface Ⅰ Introduction Ⅱ 1 Scope 1 2 Normative references 1 3 Terms and definitions 4 basic provisions 1 5 fire separation measures 2 6 Auxiliary evacuation facilities 2 7 automatic fire extinguishing and fire alarm 2 8 fire source control 2 Other requirements 9 3

Foreword

4.1,4.2,4.3 this standard are mandatory, the rest are recommended. This standard was proposed by the Ministry of Public Security Fire Department. This standard by the National Standardization Technical Committee of the Ninth Fire Technical Committee (SAC/TC113/SC9) centralized. This standard was drafted. Ministry of Public Security Fire Bureau, the Shanghai Public Security Fire Department, Zhejiang Province Public Security Fire Department, Jiangsu Province Public Security Fire Total Team, Ministry of Public Security in Tianjin Fire Research Institute. The main drafters of this standard. Guotie Nan, Zhu Liping, MA Heng, she thinks, Shen Wen, Ji Chun Yin, Chen Youdi, Zhaoqing Ping, Feng Wang Bi, Xiong Jun, Zhu Ming, Yu Feng Jing, Song Shuxin, Tian Liang, Ni Zhaopeng, Zong deposit. This standard is the first release.

Introduction

Provided at both plants, warehouses, shopping malls in the staff quarters, or engaged in the production, storage, management and other activities in residential and other civil construction, and Failing to stay part and take the necessary fire separation and fire-fighting facilities and other parts, so that this type of building fire safety requirements Incompatible with the nature of the use of the building, has a high fire risk. In order to implement the national fire prevention guidelines and policies to prevent and reduce fire Disaster, to protect personal safety, provide the basis for management of fire hazards, the development of this standard. Accommodation and combined production and storage business premises Fire Safety Requirements

1 Scope

This standard accommodation combined with production and storage business premises (commonly known as "triple play", hereinafter referred to as "combined premises") qualification, and Provisions of the combined properties of fire separation measures, evacuation facilities, fire facilities, as well as the source of fire control, fire safety technical requirements. This standard applies to both the production and storage of accommodation and management of fire safety in combination treatment sites.

2 Normative references

The following documents contain provisions which, through reference in this standard and become the standard terms. For dated references, subsequent Amendments (not including errata content) or revisions do not apply to this standard, however, encourage the parties to the agreement are based on research Whether the latest versions of these documents. For undated reference documents, the latest versions apply to this standard. GB 20517 independent smoke detection alarm GB 50016 architectural design code for fire protection GB 50084 sprinkler system design specifications GB 50116 automatic fire alarm system design specifications GB 50140 Building fire extinguishers configuration design specifications GB 50222 interior decoration of buildings for fire protection design GB 50354 interior decoration of buildings for fire prevention installation and acceptance

3 Terms and Definitions

The following terms and definitions apply to this standard. 3.1 Accommodation and production, storage management and other mixed use one or several properties disposed within the same communication space.

4 basic provisions

4.1 combined properties should not be set within the following construction. a) There are A and B fire hazard production and storage management architecture; b) fire resistance rating of the building for the three and three below the building; c) plant and warehouse; d) building area of more than 2500m2 market shopping malls and other public buildings; e) underground construction. 4.2 combined with one of the following circumstances should not place window and door openings firewall and fire resistance of not less than 1.5h floor will Accommodation portion and non-residential part is completely separated, accommodation and non-residential portion should be set independent of the evacuation facilities; when it is difficult entirely separate, Staff accommodation should not be set. a) combination of place building height greater than 15m; Construction area b) is greater than the combined properties of 2000m2;