NB/T 33018-2015: PDF in English (NBT 33018-2015) NB/T 33018-2015
NB
ENERGY INDUSTRY STANDARD
OF THE PEOPLE’S REPUBLIC OF CHINA
ICS 29.200
K 81
Record No.. 49592-2015
Technical specifications of EV charging and battery
swap infrastructure power supply system
ISSUED ON. APRIL 2, 2015
IMPLEMENTED ON. SEPTEMBER 1, 2015
Issued by. National Energy Administration of China
Table of Contents
Foreword ... 3
1 Scope ... 4
2 Normative references ... 4
3 Terms and definitions ... 5
4 Construction principles ... 5
5 Power-supply requirements ... 5
6 Electric energy quality ... 7
7 Electric energy metering ... 7
8 Power-supply monitoring ... 7
9 Safety requirements ... 7
10 Marks ... 8
Technical specifications of EV charging and battery
swap infrastructure power supply system
1 Scope
This Standard specifies the Construction principles, power requirements, power
quality, energy metering, power supply monitoring, safety requirements and
identification for EV charging and battery swap infrastructure power supply
system.
This Standard is applicable to the design and construction of power-supply
system of electric vehicle charging station and battery swap station. Centralized
AC charging piles can be implemented with reference to this Standard.
2 Normative references
The following referenced documents are indispensable for the application of
this document. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any
amendments) applies.
GB 13955, Installation and operation of residual current operated protective
devices
GB/T 29316, Power quality requirements for electric vehicle charging/battery
swap infrastructure
GB/T 29317, Terminology of electric vehicle charging/battery swap
infrastructure
GB 50052, Code for Design Electric Power Supply Systems
GB 50053, Code for Design of 20kV & Under Electric Substation
GB/T 50065, Code for Earthing Design of AC Electrical Installations
GB 50229, Code for design of fire protection for fossil fuel power plants and
substations
DL/T 448, Technical administrative code of electric energy metering
DL/T 620, Guide Rule for Wildfire Risk Forecasting Technique in Overhead
a) when the distribution capacity is greater than or equal to 100kVA, it is
recommended to use 10kV (20kV) power supply mode, and the power
supply directly meets N-1 requirements;
b) when the power distribution capacity is less than 100kVA, the low-voltage
power supply mode is adopted.
5.2.2 Radiated power supply shall be used for chargers, battery box swap
equipment, monitoring systems, and other important electrical equipment.
5.3 Selection of transformer
5.3.1 When two transformers are installed, the capacity of each transformer
is not directly less than 70% of the total load of the charging station/battery
swap station.
5.3.2 Transformers installed indoors shall not be oil-immersed transformers.
5.3.3 Distribution transformer windings shall use Dyn11 connection.
5.4 Electrical design
5.4.1 The design of the power distribution room shall meet the requirements
of GB 50053.
5.4.2 The wiring method of the 10kV side busbar of the power supply system
shall adopt single busbar or single busbar segmentation wiring.
5.4.3 Charging and battery swap equipment shall not share the same 0.38kV
outlet with other equipment in the station.
5.4.4 10kV side entry switch shall use circuit breaker or load switch. When
using a circuit breaker, it shall configure the microcomputer protection.
5.4.5 The system with 10kV dual power supply can be configured with
automatic backup power supply and shall have blocking function.
5.5 Grounding method
5.5.1 The setting of the grounding device of the power-supply system shall
meet the requirements of GB/T 50065.
5.5.2 0.38kV side grounding form shall use TN-S.
5.5.3 Electrical equipment in the charging station/battery swap station shall
be reliably grounded.
5.6 Equipment layout