GB/T 19237-2021 PDF English
US$405.00 · In stock · Download in 9 secondsGB/T 19237-2021: Compressed natural gas dispenser for vehicles Delivery: 9 seconds. True-PDF full-copy in English & invoice will be downloaded + auto-delivered via email. See step-by-step procedureStatus: Valid GB/T 19237: Evolution and historical versions
| Standard ID | Contents [version] | USD | STEP2 | [PDF] delivery | Name of Chinese Standard | Status |
| GB/T 19237-2021 | English | 405 |
Add to Cart
|
0-9 seconds. Auto-delivery
|
Compressed natural gas dispenser for vehicles
| Valid |
| GB/T 19237-2003 | English | 439 |
Add to Cart
|
3 days
|
Compressed natural gas dispenser for vehicle
| Obsolete |
Excerpted PDFs (Download full copy in 9 seconds upon purchase)PDF Preview: GB/T 19237-2021
GB/T 19237-2021: Compressed natural gas dispenser for vehicles---This is an excerpt. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.), auto-downloaded/delivered in 9 seconds, can be purchased online: https://www.ChineseStandard.net/PDF.aspx/GBT19237-2021
GB
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
ICS 43.080
T 47
Replacing GB/T 19237-2003
Compressed natural gas dispenser for vehicles
ISSUED ON: MARCH 09, 2021
IMPLEMENTED ON: OCTOBER 01, 2021
Issued by: State Administration for Market Regulation;
Standardization Administration of the PRC.
Table of Contents
Foreword ... 3
1 Scope ... 5
2 Normative references ... 5
3 Terms and definitions ... 7
4 Requirements ... 8
5 Test methods ... 20
6 Inspection rules ... 31
7 Marking, label, instructions for use ... 33
8 Sealing, packaging, transportation, storage ... 34
Appendix A (Informative) Working principle of compressed natural gas
dispenser for vehicles ... 36
Appendix B (Normative) Mass method high-pressure gas flow standard device
... 37
Appendix C (Normative) Standard meter method high-pressure gas flow
standard device ... 40
Compressed natural gas dispenser for vehicles
1 Scope
This Standard specifies the requirements, test methods, inspection rules,
marking, label, instructions for use and sealing, packaging, transportation, and
storage of compressed natural gas dispenser for vehicles.
This Standard applies to the design, manufacture and acceptance of
compressed natural gas dispenser for vehicles with rated working pressures of
20 MPa and 35 MPa.
2 Normative references
The following documents are indispensable for the application of this document.
For the dated references, only the editions with the dates indicated are
applicable to this document. For the undated references, the latest edition
(including all the amendments) are applicable to this document.
GB/T 191 Packaging - Pictorial marking for handling of goods
GB/T 2423.1 Environmental testing for electric and electronic products - Part
2: Test methods - Tests A: Cold
GB/T 2423.2 Environmental testing for electric and electronic products - Part
2: Test methods - Tests B: Dry heat
GB/T 2423.4 Environmental testing for electric and electronic products - Part
2: Test method - Test Db: Damp heat, cyclic (12 h+12 h cycle)
GB/T 3683 Rubber hoses and hose assemblies - Wire-braid-reinforced
hydraulic types for oil-based or water-based fluids - Specification
GB 3836.1 Explosive atmospheres - Part 1: Equipment - General
requirements
GB 3836.2 Explosive atmospheres - Part 2: Equipment protection by
flameproof enclosures d
GB 3836.3 Explosive atmospheres - Part 3: Equipment protection by
increased safety “e”
GB 3836.4 Explosive atmospheres - Part 4: Equipment protection by intrinsic
GB 50156 Code for design and construction of filling station
JJG 996 Verification Regulation of Compressed Natural Gas Dispensers
JTG B01 Technical Standard of Highway Engineering
SY/T 6535 The underground storage well for high-compression gas
TSG 21-2016 Supervision Regulation on Safety Technology for Stationary
Pressure Vessel
3 Terms and definitions
The following terms and definitions apply to this document.
3.1
Compressed natural gas dispenser for vehicles
Special equipment for fuelling (defuelling) compressed natural gas into (from)
the gas storage vessel for vehicles, and with functions such as metering and
pricing.
Note: Compressed natural gas dispenser for vehicles is abbreviated as dispenser. A
dispenser with a maximum flow rate of not more than 30 kg/min is called a small-
flow dispenser. A dispenser with a maximum flow rate greater than 30 kg/min and
not greater than 70 kg/min is called medium-flow dispenser. A dispenser with a
maximum flow rate greater than 70 kg/min is called a large-flow dispenser. Medium-
flow dispensers and large-flow dispensers are also called fuelling (defuelling)
columns.
3.2
Minimum measured amount
The minimum filling amount which can meet the metrological performance
requirements of the dispenser during one gas filling process.
3.3
Minimum specified indication deviation
The minimum mass resolution of the filling volume displayed by the dispenser
indicating device.
3.4
b) The unit of the payment amount for the dispenser is yuan. The unit of the
unit price is yuan per kilogram (yuan/kg).
4.2.2 Value indicating function
The dispenser shall have a value indicating function.
The requirements for the value indicating function of the dispenser are as
follows:
a) The reading of the indicated value shall be correct, easy to read, and clear.
b) The minimum specified indication deviation of the filling volume shall be
expressed in the form of 1×10n, 2×10n or 5×10n kg; where n is a positive
integer or a negative integer or zero.
c) The dispenser shall display the filling volume, unit price, and payment
amount:
1) The integer place of a single filling volume shall be no less than 3 digits;
the decimal place shall be 2 digits;
2) The integer place of the payment amount for a single filling volume shall
be no less than 3 digits; the decimal place shall be 2 digits;
3) The integer place of the unit price shall be no less than 2 digits; the
decimal place shall be 2 digits;
4) The integer place of accumulative filling volume shall be no less than 6
digits; the decimal place shall be 2 digits.
d) The unit of measurement symbol of the dispenser shall be close to the
indicated value.
e) When the dispenser has 2 or more display values, the display of each
indicated value shall correspond respectively.
f) During the filling process, the dispenser shall continuously display the
indicated value of the gas filling amount.
4.2.3 Return-to-zero function
The dispenser shall have the functions of automatic and manual return-to-zero
for indicated value. During the filling period, the indicated value shall not return
to zero.
4.2.4 Metering adjustment function
4.3.9 Power supply adaptability
The dispenser shall be able to maintain normal operation in a power supply
environment, where the amplitude of the nominal voltage variation is -15% to
+10% and the frequency change is ±1 Hz.
4.3.10 Electromagnetic compatibility
4.3.10.1 General
The complete dispenser shall be subjected to the following five electromagnetic
compatibility tests. During and after the electromagnetic compatibility tests, the
dispenser shall meet the following requirements:
a) Within the limit ranges specified in this Standard, the dispenser shall
maintain normal performance, or temporarily reduces or loses its function
and performance; but be able to recover on its own. Or, it temporarily
reduces or loses its function and performance; and requires operator
intervention or system reset.
b) For the equipment under test with data storage or with standard interfaces
that can be used for data transmission, data must not be lost during and
after the test. The stored program must not be changed. The state is not
allowed to change. The level of each point on the interface is not allowed
to change.
4.3.10.2 Electrostatic discharge immunity
According to GB/T 17626.2-2018 test level 4 (contact discharge: test voltage 8
kV; air discharge: test voltage 15 kV), test the dispenser.
4.3.10.3 Radiated, radio-frequency, electromagnetic field immunity
According to GB/T 17626.3-2016 test level 2 (test field strength is 3 V/m; the
frequency range is 80 MHz~1000 MHz), test the dispenser.
4.3.10.4 Electrical fast transient/burst immunity
According to GB/T 17626.4-2018 test level 3 (at the power port and the ground
port, the peak value of the open-circuit output test voltage is 2 kV; the pulse
repetition frequency is 5 kHz. At the signal port and control port, the peak value
of the open-circuit output test voltage is 1 kV; the pulse repetition frequency is
5 kHz), test the dispenser.
4.3.10.5 Surge immunity
According to GB/T 17626.5-2019 test level 3 (line-line open-circuit test voltage
e) No bypass piping shall be attached downstream of the mass flowmeter in
the dispenser.
4.4.2 Electronic count controller
The electronic count controller is the calculation, display and control device of
the dispenser. It shall be able to accept the flow signal transmitted by the mass
flowmeter and the pressure signal transmitted by the pressure sensor; and
according to the set and preset parameters of the dispenser, perform
calculation, display and control.
4.4.3 Accessory devices
4.4.3.1 Fuelling nozzle
The requirements for fuelling nozzle are as follows:
a) The fuelling nozzle shall meet the relevant requirements of GB/T 19236;
b) A dispenser, which is equipped with more than one fuelling nozzle, shall
be marked with the fuelling nozzle number.
4.4.3.2 Fuelling (defuelling) hoses
The requirements for fuelling (defuelling) hoses are as follows:
a) The fuelling (defuelling) hoses shall have resistance to natural gas
corrosion; shall meet the relevant requirements in GB/T 3683 and GB/T
5563;
b) The electrostatic conduction performance of the fuelling (defuelling) hose
assemblies shall meet the relevant requirements in GB/T 10543;
c) The length of fuelling (defuelling) hoses shall not be greater than 6 m.
4.4.3.3 Breakaway valve
4.4.3.3.1 A breakaway valve shall be provided on the fuelling (defuelling) hose
of the dispenser.
4.4.3.3.2 The separation tension range of the breakaway valve of the small-flow
dispenser should be 400 N~600 N. The separation tension range of the
breakaway valve of the fuelling (defuelling) column should be 600 N~900 N.
4.4.3.3.3 After the breakaway valve is separated under the action of external
force, it shall be ensured that both ends are self-sealed immediately.
4.4.3.3.4 The two parts, which the breakaway valve is automatically divided into
An emergency shut-off valve shall be installed on the upstream piping of the
dispenser, which is used to quickly shut off the filling process by manual
operation in an emergency.
The requirements for the emergency shut-off valve are as follows:
a) The emergency shut-off valve shall be installed in an obvious position of
the dispenser; so that it can cut off the gas source in time in the event of
an accident;
b) The opening and closing of the emergency shut-off valve shall be flexible
and reliable, without internal leakage and external leakage;
c) From fully open to fully closed, the rotation angle of the handle of the
emergency shut-off valve shall not be greater than 90°.
4.4.3.8 Pressure sensor
A pressure sensor shall be installed at the outlet of the piping of the dispenser,
to detect the pressure at the outlet of the piping; to ensure that, when the filling
pressure of the gas cylinder reaches the end pressure, the dispenser shall
automatically stop refilling. The pressure sensor shall obtain a valid explosion-
proof conformity certificate.
4.4.3.9 Pressure gauge
A pressure gauge shall be installed on the piping of the dispenser, to detect the
pressure in the piping. The range of the pressure gauge should be 1.5 to 2 times
the rated working pressure. Its measurement accuracy shall not be lower than
class 1.5.
4.4.3.10 Piping and its components
The requirements for piping and its components are as follows:
a) The compressed natural gas piping in the dispenser shall be made of high-
pressure stainless steel seamless steel pipes. Its performance shall meet
the relevant requirements of GB/T 14976.
b) The material of the piping components in the dispenser, which are in
contact with the compressed natural gas, shall be compatible with the
compressed natural gas medium.
c) The compressed natural gas piping in the dispenser can be connected
with equipment and valves by using ferrule, flange or taper pipe thread.
The thread type shall be matched with the connecting valve.
requirements for contact current in GB 4943.1.
5.2.4.2 The dielectric strength of the dispenser is tested in accordance with the
requirements for dielectric strength in GB 4943.1.
5.2.4.3 The connecting resistance between the protective earth terminal of the
dispenser and the parts that need to be grounded shall be tested in accordance
with the requirements for connecting resistance in GB 4943.1.
5.2.4.4 The corrosion resistance of the conductive parts, which are in contact
with the protective earth terminal and the connection end of the dispenser, shall
be tested in accordance with the requirements for corrosion resistance in GB
4943.1.
5.2.5 Test of metrological performance
5.2.5.1 Test of indication error
5.2.5.1.1 Test medium
The indication error test of the filling volume of the dispenser can use
compressed natural gas, compressed air or nitrogen as the test medium.
5.2.5.1.2 Test equipment
The requirements for the test equipment are as follows:
a) The indication error test of the filling volume of the dispenser shall use the
mass method high-pressure gas flow standard device (see Appendix B);
or can use the standard meter method high-pressure gas flow standard
device (see Appendix C). When there are objections to the test results,
the mass method is the arbitration method.
b) The expanded uncertainty (coverage factor k=2) of the measurement
result of the indication error of the high-pressure gas flow standard device
shall not exceed 1/3 of the absolute value of the maximum allowable error
of the dispenser.
5.2.5.1.3 Test method
5.2.5.1.3.1 Rated working pressure, flow-test region, filling pressure
control range, and number of tests
According to the rated working pressure of the dispenser, the different flow-test
regions are tested, which are R(1), R(2) and R(3), respectively. The
correspondence BETWEEN the rated working pressure of dispenser AND the
flow-test region and the filling pressure control range of gas cylinder is shown
It shall be carried out in accordance with the requirements of GB/T 17626.11-
2008.
5.2.11 Test of explosion-proof performance
In accordance with the obtained complete-machine explosion-proof conformity
certificate and test report and related attachments, check whether the
explosion-proof electrical components used in the complete machine are
consistent with the approved explosion-proof technical documents.
5.2.12 Durability test
5.2.12.1 Test medium
The durability test of the dispenser can use compressed natural gas,
compressed air or nitrogen as the test medium.
5.2.12.2 Test method
The durability test method is as follows:
a) According to the use requirements of the dispenser, select the flow-test
region R(2); repeatedly fill the gas cylinder with the test medium 2000
times;
b) During each filling process, all solenoid valves shall be opened and closed;
c) According to the test methods in 5.2.5.1 and 5.2.5.2, test the dispenser
again.
5.2.13 Test of transportation adaptability
Put the dispensers, which have passed the exit-factory inspection, under the
packaging and transportation conditions. Use the truck transportation test. The
test road configuration is carried out in accordance with the requirements of
JTG B01 for secondary highway 200 km, tertiary highway 100 km, and speed
30 km/h~40 km/h. It is also possible to place the dispenser on the vibration test
bench for simulated transportation test. According to the requirements of GB/T
4798.2, the mechanical environmental condition level is 2M2 (steady-state
sinusoidal vibration frequency 10 Hz; acceleration amplitude 10 m/s2). The
vibration time is up and down 2 h, left and right 1 h, front and back 1 h. After the
test, open the box to inspect whether the parts are loose or damaged. Then
according to the methods of 5.1, 5.2.1, 5.2.2, 5.2.3, 5.2.4, 5.2.5.1 and 5.2.5.2,
inspect and test item by item.
5.3 Test of components
c) Exhaust the gas in the separated two parts and reconnect them.
5.3.3.4 Test of safety valve
5.3.3.4.1 Test medium
The safety valve test of the dispenser can use compressed natural gas,
compressed air or nitrogen as the test medium.
5.3.3.4.2 Test method
The test method of the safety valve is as follows:
a) Connect the inlet of the dispenser to the gas source;
b) In the case of turning off the fuelling nozzle, gradually increase the
pressure to reach the constant pressure of the safety valve. The safety
valve shall be able to open immediately and release the pressure. When
the pressure drops below the constant pressure, it shall be automatically
closed.
6 Inspection rules
6.1 Exit-factory inspection
6.1.1 The dispenser shall be subjected to the exit-factory inspection one by one
by the quality inspection department of the manufacturing company. Only after
passing the inspection and the product conformity certificate is issued, can it
leave the factory.
6.1.2 Inspection items: See Table 4.
6.1.3 Determination rule: If all the exit-factory inspection items are qualified, the
product is determined conformity. If there are nonconformity items in the exit-
factory inspection, it shall be re-inspected after rework. If there are still
nonconformity items, the product shall be determined as nonconformity.
6.2 Type inspection
6.2.1 In any of the following situations, type inspection shall be carried out:
a) When the new product is finalized;
b) When there are major changes in product design, process, and materials
used that may affect product performance;
c) When the exit-factory inspection result is significantly different from the
mechanism shall be set.
8.2 Packaging
8.2.1 The packaging of the dispenser shall include accompanying documents
such as the product conformity certificate, product packing list, product exit-
factory inspection report, and product instructions for use.
8.2.2 The packaging protection and packaging pictorial marking for handling of
the dispenser shall meet the relevant requirements of GB/T 191 and GB/T
13384. At least the following contents shall be included on the outer packing
box:
a) Name of the sending station and name, address, and postal code of the
manufacturing company;
b) Name of the receiving station and name, address, and postal code of the
receiving organization;
c) Product name and model;
d) Explosion-proof conformity certificate mark and number;
e) Implementation standard number;
f) Net weight and gross weight of the product;
g) Geometric dimensions of the outer packing box (length×width×height);
h) Pictorial markings such as "Avoid rain", "Upward", "Do not roll".
8.3 Transportation
Suitable for general transportation means. During loading-unloading and
transportation, the direction signs shall be paid attention to. The inclination of
the packing box shall not exceed 30°.
8.4 Storage
Packaged or unpackaged dispensers shall be placed in a dry, ventilated and
covered place. There shall be no harmful gases corrosive to metals in the
storage place of the dispenser.
Appendix B
(Normative)
Mass method high-pressure gas flow standard device
B.1 Expanded uncertainty
The expanded uncertainty (coverage factor k=2) of the measurement result of
the indication error of the mass method high-pressure gas flow standard device
shall not exceed 1/3 of the absolute value of the maximum allowable error of
the dispenser.
B.2 Test medium
The test medium requirements are as follows:
a) Compressed natural gas, compressed air or nitrogen can be used as the
test medium;
b) When the test medium is compressed air, it is required that the dust
particle size be less than 5 μm; the oil content be less than 5 mg/m3; the
atmospheric dew point be less than -50 °C.
B.3 Fixed gas storage facilities
The requirements for fixed gas storage facilities are as follows:
a) Fixed gas storage facilities shall use gas cylinder groups or gas storage
wells.
b) The rated working pressure of fixed gas storage facilities shall meet the
relevant requirements of GB 50156.
c) The fixed gas cylinder group should use large-volume gas cylinders of the
same specification and model.
d) The gas cylinder group shall be fixed on an independent support. The gas
cylinder group on the ground should be placed horizontally.
e) The design and construction of gas storage wells shall meet the relevant
requirements of SY/T 6535. The gas storage wellhead shall be easy to
open for testing.
f) According to the operating pressure, the fixed gas storage facilities should
Appendix C
(Normative)
Standard meter method high-pressure gas flow standard device
C.1 Expanded uncertainty
The expanded uncertainty (coverage factor k=2) of the measurement result of
the indication error of the standard meter method high-pressure gas flow
standard device shall not exceed 1/3 of the absolute value of the maximum
allowable error of the dispenser.
C.2 Test medium
The test medium requirements are as follows:
a) Compressed natural gas, compressed air or nitrogen can be used as the
test medium;
b) When the test medium is compressed air, it is required that the dust
particle size be less than 5 μm; the oil content be less than 5 mg/m3; the
atmospheric dew point be less than -50 °C.
C.3 Fixed gas storage facilities
The requirements for fixed gas storage facilities are as follows:
a) Fixed gas storage facilities shall use gas cylinder groups or gas storage
wells.
b) The rated working pressure of fixed gas storage facilities shall meet the
relevant requirements of GB 50156.
c) The fixed gas cylinder group should use large-volume gas cylinders of the
same specification and model.
d) The gas cylinder group shall be fixed on an independent support. The gas
cylinder group on the ground should be placed horizontally.
e) The design and construction of gas storage wells shall meet the relevant
requirements of SY/T 6535. The gas storage wellhead shall be easy to
open for testing.
f) According to the operating pressure, the fixed gas storage facilities should
...... Source: Above contents are excerpted from the full-copy PDF -- translated/reviewed by: www.ChineseStandard.net / Wayne Zheng et al.
Tips & Frequently Asked QuestionsQuestion 1: How long will the true-PDF of English version of GB/T 19237-2021 be delivered?Answer: The full copy PDF of English version of GB/T 19237-2021 can be downloaded in 9 seconds, and it will also be emailed to you in 9 seconds (double mechanisms to ensure the delivery reliably), with PDF-invoice. Question 2: Can I share the purchased PDF of GB/T 19237-2021_English with my colleagues?Answer: Yes. The purchased PDF of GB/T 19237-2021_English will be deemed to be sold to your employer/organization who actually paid for it, including your colleagues and your employer's intranet. Question 3: Does the price include tax/VAT?Answer: Yes. Our tax invoice, downloaded/delivered in 9 seconds, includes all tax/VAT and complies with 100+ countries' tax regulations (tax exempted in 100+ countries) -- See Avoidance of Double Taxation Agreements (DTAs): List of DTAs signed between Singapore and 100+ countriesQuestion 4: Do you accept my currency other than USD?Answer: Yes. www.ChineseStandard.us -- GB/T 19237-2021 -- Click this link and select your country/currency to pay, the exact amount in your currency will be printed on the invoice. Full PDF will also be downloaded/emailed in 9 seconds. Question 5: Should I purchase the latest version GB/T 19237-2021?Answer: Yes. Unless special scenarios such as technical constraints or academic study, you should always prioritize to purchase the latest version GB/T 19237-2021 even if the enforcement date is in future. Complying with the latest version means that, by default, it also complies with all the earlier versions, technically.
How to buy and download a true PDF of English version of GB/T 19237-2021?A step-by-step guide to download PDF of GB/T 19237-2021_EnglishStep 1: Visit website https://www.ChineseStandard.net (Pay in USD), or https://www.ChineseStandard.us (Pay in any currencies such as Euro, KRW, JPY, AUD). Step 2: Search keyword "GB/T 19237-2021". Step 3: Click "Add to Cart". If multiple PDFs are required, repeat steps 2 and 3 to add up to 12 PDFs to cart. Step 4: Select payment option (Via payment agents Stripe or PayPal). Step 5: Customize Tax Invoice -- Fill up your email etc. Step 6: Click "Checkout". Step 7: Make payment by credit card, PayPal, Google Pay etc. After the payment is completed and in 9 seconds, you will receive 2 emails attached with the purchased PDFs and PDF-invoice, respectively. Step 8: Optional -- Go to download PDF. Step 9: Optional -- Click Open/Download PDF to download PDFs and invoice. See screenshots for above steps: Steps 1~3 Steps 4~6 Step 7 Step 8 Step 9
|