GB/T 25388.2-2021 English PDFUS$409.00 · In stock
Delivery: <= 4 days. True-PDF full-copy in English will be manually translated and delivered via email. GB/T 25388.2-2021: Wind turbines generator system - Double-fed converter - Part 2: Test method Status: Valid GB/T 25388.2: Historical versions
Basic dataStandard ID: GB/T 25388.2-2021 (GB/T25388.2-2021)Description (Translated English): Wind turbines generator system - Double-fed converter - Part 2: Test method Sector / Industry: National Standard (Recommended) Classification of Chinese Standard: F11 Word Count Estimation: 22,285 Issuing agency(ies): State Administration for Market Regulation, China National Standardization Administration GB/T 25388.2-2021: Wind turbines generator system - Double-fed converter - Part 2: Test method---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.Wind turbines generator system - Double-fed converter - Part 2.Test method ICS 27.180 F11 National Standards of People's Republic of China Replace GB/T 25388.2-2010 Wind power generator double-fed converter Part 2.Test method Part 2.Testmethod Released on 2021-03-09 2021-10-01 implementation State Administration of Market Supervision and Administration Issued by the National Standardization Management Committee Table of contentsForeword Ⅲ 1 Scope 1 2 Normative references 1 3 Test conditions 1 3.1 Test environment conditions 1 3.2 Equipment 2 4 Test method 2 4.1 Test platform 2 4.2 Test items and content 3 4.2.1 Electrical safety test 3 4.2.2 Grid-connected control test 3 4.2.3 Loading test 3 4.2.4 Power grid adaptability test 4 4.2.5 Fault voltage ride-through capability test 4 4.2.6 Efficiency test 4 4.2.7 Total power factor test 5 4.2.8 Total harmonic distortion rate measurement test 5 4.2.9 Each harmonic current measurement test 5 4.2.10 DC current content measurement test 5 4.2.11 DC voltage ripple coefficient measurement test 5 4.2.12 Current unbalance test 6 4.2.13 Overload test 6 4.2.14 Measurement of the differential mode voltage Umax on the machine side 6 4.2.15 Measurement test of common mode voltage on the machine side 6 4.2.16 Measurement of dU/dt value of voltage change rate at the motor side 7 4.2.17 Stability operation test 7 4.2.18 Torque control accuracy test 7 4.2.19 Reactive power accuracy test 7 4.2.20 Temperature rise test 7 4.2.21 Protection function test 8 4.2.22 Immunity test 11 4.2.23 Electromagnetic emission test 12 4.2.24 Communication test 12 4.2.25 Low temperature working test 12 4.2.26 High temperature work test 12 4.2.27 Constant humidity test 12 4.2.28 Alternating damp heat test 12 4.2.29 Protection performance test 12 4.2.30 Vibration test 12 4.2.31 Noise test 12 4.2.32 Additional test 13 5 Test report 13 Appendix A (informative appendix) Topology diagram of power grid adaptability test platform 14 Appendix B (informative appendix) schematic diagram of fault voltage generating device 15 Wind power generator double-fed converter Part 2.Test method1 ScopeThis part of GB/T 25388 specifies the test of AC, DC, and AC voltage converters for doubly-fed wind turbines (hereinafter referred to as "units") Conditions and test methods. This part applies to AC-DC-AC voltage converters of doubly-fed variable-speed constant-frequency wind turbines, that is, doubly-fed converters (hereinafter referred to as "variable Streamer").2 Normative referencesThe following documents are indispensable for the application of this document. For dated reference documents, only the dated version applies to this article Pieces. For undated reference documents, the latest version (including all amendments) is applicable to this document. GB/T 2423.1-2008 Environmental testing of electric and electronic products Part 2.Test method Test A. Low temperature GB/T 2423.2-2008 Environmental testing of electric and electronic products Part 2.Test method Test B. High temperature GB/T 2423.3-2016 Environmental Test Part 2.Test Method Test Cab. Constant Humidity Test GB/T 2423.4-2008 Environmental testing of electrical and electronic products Part 2.Test method Test Db Alternating damp heat (12h 12h cycle) GB/T 2423.56-2018 Environmental Test Part 2.Test Method Test Fh. Broadband Random Vibration and Guidelines GB/T 3859.1-2013 General requirements for semiconductor converters and power grid commutated converters Part 1-1.Basic requirements specification GB/T 4208 Shell protection grade (IP code) GB/T 12668.3-2012 Adjustable speed electric drive system Part 3.Electromagnetic compatibility requirements and specific test methods GB/T 17626.3 Electromagnetic compatibility test and measurement technology Radio frequency electromagnetic field radiation immunity test GB/T 17626.4 Electromagnetic compatibility test and measurement technology Electrical fast transient pulse group immunity test GB/T 17626.5 Electromagnetic compatibility test and measurement technology surge (impact) immunity test GB/T 17626.6 Electromagnetic compatibility test and measurement technology Radio frequency field induced conducted disturbance immunity GB/T 25388.1 Double-fed converter for wind turbines Part 1.Technical conditions GB/T 36994 Test Procedure for Adaptability of Wind Turbine Power Grid GB/T 36995 Test Procedure for Fault Voltage Ride Through Ability of Wind Turbine Generator3 Test conditions3.1 Test environment conditions The test environment conditions of the converter should meet the following requirements. a) Temperature. 15℃~35℃; b) Relative humidity. 45%~75%; c) Atmospheric pressure. 86kPa~106kPa; d) Altitude. ≤2000m. Value, the converter should be able to stop immediately. After the shutdown is completed, the converter should be able to report the correct fault information without any abnormality. The fault is eliminated and After reset, the normal grid-connected state can be restored. Or refer to the simulation test platform in 4.1, start the converter to complete the grid connection, and simulate the method of feedback signal inversion of the protection device, The converter should be able to stop immediately. After the shutdown is completed, the converter should be able to report the correct fault information without any abnormality. The fault is cleared and reset After that, the normal grid-connected state can be restored. 4.2.21.1.3 Phase loss protection According to the simulation test platform in 4.1, disconnect a phase cable of the AC terminal on the grid side and the machine side under the shutdown state. Main power of the upper system, variable current The device should be able to report the correct fault information, and it is forbidden to start the machine without any abnormality. After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.1.4 Phase sequence error protection According to the simulation test platform in 4.1, switch the two-phase cable on the grid side or the machine side under the state of shutdown and power failure. The main power of the system, the converter should The correct fault information can be reported, and the machine is forbidden to start without any abnormality. After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.1.5 Instantaneous overcurrent protection test According to the simulation test platform in 4.1, in the shutdown state, the hardware protection threshold is modified to reduce the instantaneous overcurrent hardware Protection threshold threshold. Start the converter to complete the grid connection, and adjust the AC terminal current of the grid-side converter and the machine-side converter respectively to trigger the working current The instantaneous overcurrent protection threshold, the converter should be able to stop immediately. After the shutdown is completed, the converter should be able to report the correct fault information without any abnormal. After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.1.6 DC overvoltage protection According to the simulation test platform in 4.1, when the power is off, the hardware protection threshold is modified to reduce the DC overvoltage hardware protection. Protection threshold threshold. Start the converter to complete the grid connection, make the DC bus voltage higher than the threshold threshold, trigger the DC overvoltage fault, the converter should be able to Shut down immediately. After the shutdown is completed, the converter should be able to report the correct fault information without any abnormality. After the fault is eliminated and reset, it can be restored Normal grid-connected state. 4.2.21.1.7 DC undervoltage protection According to the simulation test platform in 4.1, when the power is off, the hardware protection threshold is modified to increase the DC undervoltage hardware protection. Protection threshold threshold. Start the converter to complete the grid connection, so that the DC bus voltage is lower than the threshold threshold, and the DC undervoltage fault is triggered. The converter should be able to Shut down immediately. After the shutdown is completed, the converter should be able to report the correct fault information without any abnormality. After the fault is eliminated and reset, it can be restored Normal grid-connected state. 4.2.21.2 Type 2 fault protection 4.2.21.2.1 Voltage unbalance protection According to the simulation test platform in 4.1, turn on the main power of the system and start the grid-connected operation of the converter. Adjust the output voltage of the power grid simulator to make the If the unbalance degree of the pressure-negative sequence exceeds the software protection threshold, the converter should be able to reduce the load and shut down according to the set slow shutdown strategy. After the shutdown is completed, the flow is changed The device should be able to report the correct fault information without any abnormalities. After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.2.2 Power grid over-frequency protection According to the simulation test platform in 4.1, turn on the main power of the system and start the grid-connected operation of the converter. Adjust the output grid frequency of the grid simulator to make If the grid frequency exceeds the software protection threshold, the converter should be able to reduce load and stop according to the set slow shutdown strategy. After the shutdown is complete, the converter should The correct fault information can be reported without any exceptions. After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.2.3 Grid under-frequency protection According to the simulation test platform in 4.1, turn on the main power of the system and start the grid-connected operation of the converter. Adjust the output grid frequency of the grid simulator to make If the grid frequency is lower than the software protection threshold, the converter should be able to reduce load and stop according to the set slow shutdown strategy. After the shutdown is complete, the converter should The correct fault information can be reported without any exceptions. After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.2.4 Overcurrent protection According to the simulation test platform in 4.1, under the state of shutdown and power failure, reduce the overcurrent software protection by modifying the software protection threshold method Threshold threshold. Start the converter to complete the grid connection, and adjust the AC terminal current of the grid-side converter and the machine-side converter respectively, so that the working current triggers over-voltage Current protection threshold, the converter should be able to reduce load and stop according to the set slow shutdown strategy. After the shutdown is completed, the converter should be able to report the correct fault Information without any exceptions. After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.2.5 Generator over-speed protection According to the simulation test platform in 4.1, turn on the main power of the system and start the grid-connected operation of the converter. Adjust the generator speed to exceed the over-speed protection threshold When the time, the converter should be able to reduce the load and stop according to the set slow stop strategy. After the shutdown is completed, the converter should be able to report the correct fault information, and no Any abnormalities. After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.2.6 Generator underspeed protection According to the simulation test platform in 4.1, turn on the main power of the system and start the grid-connected operation of the converter. Adjust the generator speed to be lower than the underspeed protection threshold When the time, the converter should be able to reduce the load and stop according to the set slow stop strategy. After the shutdown is completed, the converter should be able to report the correct fault information, and no Any abnormalities. After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.2.7 Communication fault protection According to the simulation test platform in 4.1, the main power of the system is connected, and the grid-connected operation of the converter is started through the simulation main control. Disconnect the converter from the analog main The converter should be able to reduce load and stop according to the set slow stop strategy. After the shutdown is completed, the converter should be able to report the correct fault message Information, and there is no abnormality. After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.2.8 Cooling system failure protection According to the simulation test platform in 4.1, turn on the main power of the system and start the grid-connected operation of the converter. Stop the operation of the cooling system of the converter, change the flow The generator should be able to reduce load and stop according to the set slow stop strategy. After the shutdown is completed, the converter should be able to report the correct fault information without any difference. often. After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.2.9 Over temperature protection According to the simulation test platform in 4.1, under the state of shutdown and power failure, lower the over-temperature protection threshold by modifying the software protection threshold. limit. Start the converter to complete the grid connection, so that the ambient temperature, coolant temperature, device temperature, etc. exceed the corresponding temperature protection threshold, and the converter should be able to According to the set slow stop strategy, the load will be reduced and the stop will be stopped. After the shutdown is completed, the converter should be able to report the correct fault information without any abnormality. Therefore After the fault is eliminated and reset, the normal grid-connected state can be restored. 4.2.21.2.10 Surge over-voltage protection According to the simulation test platform in 4.1, remove the converter surge protection device or absorption device, the converter should be able to correctly identify and prompt Alarm. 4.2.22 Immunity test 4.2.22.1 Electrostatic discharge immunity test The converter can be operated under light load, and the test shall be carried out in accordance with the provisions of GB/T 17626.6 and under the following conditions. a) Test voltage. contact discharge 6kV, air discharge 8kV; b) Test port. the whole shell; c) The number of discharges at each sensitive point test point. 10 times for each of the positive and negative polarity, and the interval between each discharge is at least 1s; d) Performance criterion. It is judged in accordance with the relevant regulations of GB/T 25388.1. 4.2.22.2 Radio frequency electromagnetic field radiation immunity test The converter can be operated under light load, and the test shall be carried out in accordance with the provisions of GB/T 17626.3 and under the following conditions. a) Frequency range. 80MHz~1000MHz; b) Test field strength. 10V/m; c) 1kHz sine wave, 80% amplitude modulation; d) Test port. the whole shell; e) Antenna polarization direction. horizontal and vertical direction; f) Performance criterion. It is judged in accordance with the relevant regulations of GB/T 25388.1. 4.2.22.3 Electric fast pulse group immunity test The converter can be operated under light load, in accordance with the provisions of GB/T 17626.4 and tested under the following conditions. a) Test voltage. ±2kV (power line), ±1kV (signal line); b) Test port. input and output power port, signal line; c) Repetition frequency. 5kHz/100kHz; d) Duration. 1min; e) Performance criterion. It is judged in accordance with the relevant regulations of GB/T 25388.1. 4.2.22.4 Surge voltage immunity test The converter can be operated under light load, in accordance with the provisions of GB/T 17626.5 and tested under the following conditions. a) Test voltage. ±2kV (common mode), ±1kV (differential mode); b) Test port. input and output power port, signal line; c) Polarity. positive and negative; d) Test times. 5 times for positive and negative polarity; e) Repetition rate. once per minute; f) Performance criterion. It is judged in accordance with the relevant regulations of GB/T 25388.1. 4.2.22.5 Conducted disturbance immunity test The converter can be operated under light load, and the test shall be carried out in accordance with the provisions of GB/T 17626.6 and under the following conditions. a) Frequency range. 0.15MHz~80MHz; b) Test field strength. 10V (modulation); c) 1kHz sine wave, 80% amplitude modulation; d) Test port. external port; e) Injection method. CDN or current clamp, electromagnetic clamp; f) Performance criterion. It is judged in accordance with the relevant regulations of GB/T 25388.1. 4.2.23 Electromagnetic emission test 4.2.23.1 Conducted emission test The converter should be operated under normal full load or light load, in accordance with the provisions of GB/T 12668.3-2012 and under the following conditions test. a) Test frequency band. 150kHz~30MHz; b) Test port. input and output power port, signal line; c) Test limit. According to the C3 limit of 6.5.2 in GB/T 12668.3-2012. 4.2.23.2 Radiation emission test The converter should operate under normal full-load or light-load grid-connected working conditions, in accordance with the provisions of GB/T 12668.3-2012 and in the following conditions Test under pieces. a) Test frequency band. 30MHz~1000MHz; b) Test port. shell port; c) Test limit. According to the C3 limit of 6.5.2 in GB/T 12668.3-2012. 4.2.24 Communication test According to the simulation test platform in 4.1, the converter and the unit control system can carry out communication tests. The main content of the test should include opening Machine process, control process (instruction issuance), shutdown process, protection and reset process, data and status exchange, etc. 4.2.25 Low temperature working test The test method is carried out in accordance with "Test A" in GB/T 2423.1-2008. 4.2.26 High temperature work test The test method is carried out in accordance with "Test B" in GB/T 2423.2-2008. 4.2.27 Constant humidity test The test method is carried out in accordance with "Test Cab" in GB/T 2423.3-2016. 4.2.28 Alternating damp heat test The test method is carried out in accordance with "Test Db" in GB/T 2423.4-2008. 4.2.29 Protection performance test The test method is to carry out the protective performance test in accordance with the provisions of GB/T 4208. 4.2.30 Vibration test The test method is carried out in accordance with "Test Fh" in GB/T 2423.56-2018. 4.2.31 Noise test The converter should operate stably under the conditions of rated grid voltage, rated grid frequency, converter rated output power, and grid-side unit power factor Perform a noise test under. The automatic switching fan i......Tips & Frequently Asked Questions:Question 1: How long will the true-PDF of GB/T 25388.2-2021_English be delivered?Answer: Upon your order, we will start to translate GB/T 25388.2-2021_English as soon as possible, and keep you informed of the progress. The lead time is typically 2 ~ 4 working days. The lengthier the document the longer the lead time.Question 2: Can I share the purchased PDF of GB/T 25388.2-2021_English with my colleagues?Answer: Yes. The purchased PDF of GB/T 25388.2-2021_English will be deemed to be sold to your employer/organization who actually pays for it, including your colleagues and your employer's intranet.Question 3: Does the price include tax/VAT?Answer: Yes. Our tax invoice, downloaded/delivered in 9 seconds, includes all tax/VAT and complies with 100+ countries' tax regulations (tax exempted in 100+ countries) -- See Avoidance of Double Taxation Agreements (DTAs): List of DTAs signed between Singapore and 100+ countriesQuestion 4: Do you accept my currency other than USD?Answer: Yes. If you need your currency to be printed on the invoice, please write an email to Sales@ChineseStandard.net. In 2 working-hours, we will create a special link for you to pay in any currencies. Otherwise, follow the normal steps: Add to Cart -- Checkout -- Select your currency to pay.Question 5: Should I purchase the latest version GB/T 25388.2-2021?Answer: Yes. Unless special scenarios such as technical constraints or academic study, you should always prioritize to purchase the latest version GB/T 25388.2-2021 even if the enforcement date is in future. Complying with the latest version means that, by default, it also complies with all the earlier versions, technically. |