Home Cart Quotation About-Us
www.ChineseStandard.net
SEARCH

GB/T 50493-2019 (GB 50493-2009) PDF English

US$85.00 · In stock · Download in 9 seconds
GB 50493-2009: Specification for design of combustible gas and toxic gas detection and alarm for petrochemical industry
Delivery: 9 seconds. True-PDF full-copy in English & invoice will be downloaded + auto-delivered via email. See step-by-step procedure
Status: Obsolete

GB 50493: Historical versions

Standard IDUSDBUY PDFDeliveryStandard Title (Description)Status
GB/T 50493-2019899 Add to Cart 5 days Specification for design of combustible gas and toxic gas detection and alarm for petrochemical industry Valid
GB 50493-200985 Add to Cart Auto, 9 seconds. Specification for design of combustible gas and toxic gas detection and alarm for petrochemical industry Obsolete

Similar standards

GB/T 50761   HG/T 20513   GB 50128   GB/T 50483   

GB 50493-2009: Specification for design of combustible gas and toxic gas detection and alarm for petrochemical industry


---This is an excerpt. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.), auto-downloaded/delivered in 9 seconds, can be purchased online: https://www.ChineseStandard.net/PDF.aspx/GB50493-2009
NATIONAL STANDARD OF THE PEOPLE’s REPUBLIC OF CHINA p GH 50493-2009 Specification for Design of Combustible Gas and Toxic Gas Detection and Alarm for Petrochemical Industry Issued on: MARCH 19, 2009 Implemented on: OCTOBER I, 2009 .Jointly Issued by Ministry of Housing and Urban-Rural Construction of the People’s Republic of China General Administration of Quality Supervision, lns1•ection and Quarantine of the People’s Republic of China

Table of Contents

General Provisions... 1 2 Terms ... 2 3 General Requirements ... 4 4 Determination of Detection Points .. 6 4.1 General Rules ... 6 4.2 Process Unit ... 6 4.3 Storage and Transportation Fa巳iliti巳s ... 7 4.4 Other Combustible Gas or Toxic Gas Diffusion and Accumulation Site ... 8 5 Combustible Gas And Toxic Gas Detection Alarm System ... 9 5.1 Technical Performance... 9 5.2 Selection of Detector... 9 5.3 Selection oflndication Alarm Device ... 1 0 6 Detectors and Indication Apparatus Installation ... 1 2 6.1 Detector Installation ... 1 2 6.2 Indication Appara饥is and Onsite Alarm Installation ... 12 Appendix A Properties of General Combustible Gas and Vapor ... 1 3 Appendix B Properties of General Toxic Gas and Vapor ... 1 7 Appendix C Technical Performance Table of Detector for General Gasses ... 18 Explanation of Wording in This Code ... 19 1 General Provisions 1.0.1 This standard is formulated with a view to preventing personal injury, and fire and explosion accidents, and ensuring the safety of petrochemical enterprises. 1.0.2 This standard is applicable to the combustible gas and toxic gas detection and alarm design of new, expended or rebuilt works for petrochemical enterprises. 1.0.3 Besides the provisions of this standard, the combustible gas and toxic gas detection and alarm design for petrochemical industry shall meet the requirements of the current related national standards.

2 Terms

2.0.1 Combustible gas It is referred to Class A combustible gas or the combustible gas generated after Class A and B flammable liquid gasi马ring. 2.0.2 Toxic gas It is referred to the Gasses which cause acute or chronic health harms on workers by body contact in the employment activities. The scope of toxic gas in this standard is toxic vapour toxic gas listed in “ acute toxic substances" (Wei Fa Jian Fa [2003] No.142). The general toxic vapours or toxic gases are as. nitrogen dioxide, hydrogen sulfide, benzene, hydrogen cyanide, ammonia, chlorine gas, carbon monoxide, acrylonitrile, vinyl chloride and phosgene. 2.0.3 Source of release It is referred to the Position or site which releases explosive gas mixture or toxic gas. 2.0.4 Detector It is referred to the electronic unit which can convert the concentration of combustible gas and toxic gas into electrical signal, and it is composed of sensor and transducer. 2.0.5 Indication apparatus It is referred to the electronic devices which receive the output signal of detector and send Indication, alarm and control signals. 2.0.6 Sensible range It is referred to the range of the detected gas that can be detected by detector under the test condition. 2.0. 7 Alarm set value It is referred to the pre-set alarm concentration value of warning device. 2.0.8 Response time It is referred to the time from detector contacting gas to stably indicating value under test condition. 90% of the time to reach the stable indicated value is adopted as response time; 10% of the time to restore to stable indicated value is adopted as recovery time. 2.0.9 Vertical height It is referred to the vertical distance from the detection opening of detector to the appointed reference object 2.0.10 Lower explosion limit (LEL) It is re也rred to the concentration value (V %) of combustible gas at lower explosion limit

3 General Requirements

3.0.1 When possible combustible gas and toxic gas leak is detected in the area for process unit producing or using combustible gas and toxic gas, and for storage and transportation facilities, combustible gas and toxic gas detector shall be arranged according to the following prov1s1ons. 1 Combustible gas or combustible gas with toxic gas is leaked, and the concentration of combustible gas may reach 25% of the lower explosion limit nut the toxic gas cannot reach maximum allowable Concentration. At this time, combustible gas detector shall be equipped; 2 Combustible gas or combustible gas with toxic gas is leaked, and the concentration of combustible gas may reach the lower explosion limit nut the toxic gas cannot reach 25% of maximum allowable Concentration. At this time, toxic gas detector shall be equipped; 3 In the place where combustible gas and toxic gas are stored together, the concentration of combustible gas may reach 25% of lower explosion limit, and the concentration of toxic gas may also reach maximum allowable Concentration. At this point, combustible gas and toxic gas detectors shall be all equipped; 4 When a gas is both combustible gas and toxic gas, only toxic gas detector shall be equipped. 3.0.2 Two-level alarm shall be adopted for the detection system of combustible gas and toxic gas. When the toxic gas and combustible gas detectors simultaneously alarm in same detection area, the following principles shall be complied with. 1 In same level alarm, toxic gas alarm shall be preferential; 2 Level 2 alarm has priority over level 1 alarm. 3.0.3 If the process has special requirements, or runs normally, staffs must not ent巳r hazardous area, continual detection, Indication and alarm should be taken for the release source of combustible gas and toxic gas, and alarm should be recorded and printed. 3.0.4 Alarm Signal shall be sent to site warning device and indication apparatus at attended control room or site operation room, and audible and visual alarm shall be available . 3.0.S The arrangement of the site warning devices in equipment zone shall be determined according to the following factors. area of equipment zone, arrangement of equipment and structure, physico-chemical properties of release source and site air flow character. Site warning device may be sounder or alarm lamp. 3.0.6 Combustible gas detector shall be the products which the measuring instrument production certification, explosion protection performance certification and fire control certification are approved by the institution designated by the country. 3.0. 7 Toxic gas detector specified by the laws of the country shall be the products which the measuring instrument production certification is approved by the institution designated or

4 Determination of Detection Points

4.1 General Rules 4.1.1 The detection points of combustible gas and toxic gas detectors shall be arranged on the positions where gas is easy to accumulate and sampling or detection is convenient, according to the following conditions. gas physicochemical property, characteristic of release source, production yard layout, geographic conditions, environmental climate and operating and patrol examining route. 4.1.2 Detection points shall be arranged for the following release sources with possible combustible gas or toxic gas leak. 1 Sealing of gas compressor and liquor pump; 2 Liquid and gas sampling ports; 3 Liquor drainage opening or vent; 4 Flange and valving for equipment and pipes. 4.2 Process Unit 4.2.1 When release sources are located on the equipment sections of open-Air or open-type facility Layout, the distance from detection point and release source shall meet the following requirements. 1 When the detection point is located on windward Side of the all-the-year least frequency wind direction, the distance from combustible gas detection point to release source should not be larger than 1 Sm, and the distance from toxic gas detection point to release source should not be larger than 2 m; 2 When the detection point is located on leeside of the all-the-year least 仕equency wind direction, the distance from combustible gas detection point to release source should not be larger than Sm, and the distance from toxic gas detection point to release source should not be larger than 2 m; 4.2.2 When combustible gas release source is located on semi-open workshop building of closing or imperfect local ventilation, a detector may be ranged per I Sm, and the distance from the detector to any release source within this coverage should not be larger than 7.Sm. The distance from Toxic gas detector to the release source should not be larger than lm. 4.2.3 When lighter-than-air combustible gas or Toxic gas release source is located on semi- open workshop building of closing or imperfect local ventilation, detector shall be arranged over the release source, beside combustible g... ......