US$450.00 · In stock · Download in 9 secondsGB/T 38328-2019: Common specifications of high-voltage direct current circuit-breakers for high-voltage direct current transmission using voltage sourced converters (VSC-HVDC) Delivery: 9 seconds. True-PDF full-copy in English & invoice will be downloaded + auto-delivered via email. See step-by-step procedureStatus: Valid
Standard ID | Contents [version] | USD | STEP2 | [PDF] delivery | Name of Chinese Standard | Status |
GB/T 38328-2019 | English | 450 |
Add to Cart
|
0-9 seconds. Auto-delivery
|
Common specifications of high-voltage direct current circuit-breakers for high-voltage direct current transmission using voltage sourced converters (VSC-HVDC)
| Valid |
Excerpted PDFs (Download full copy in 9 seconds upon purchase)PDF Preview: GB/T 38328-2019
GB/T 38328-2019: Common specifications of high-voltage direct current circuit-breakers for high-voltage direct current transmission using voltage sourced converters (VSC-HVDC) ---This is an excerpt. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.), auto-downloaded/delivered in 9 seconds, can be purchased online: https://www.ChineseStandard.net/PDF.aspx/GBT38328-2019
GB
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
ICS 29.120.40
K 43
Common Specifications of High-voltage Direct Current
Circuit-breakers for High-voltage Direct Current
Transmission Using Voltage Sourced Converters (VSC-
HVDC)
Issued on: DECEMBER 10, 2019
Implemented on: JULY 1, 2020
Issued by. State Administration for Market Regulation;
Standardization Administration of the People’s Republic of China.
Table of Contents
Foreword... 5
Introduction... 6
1 Scope... 7
2 Normative References... 7
3 Terms and Definitions... 8
4 Normal and Special Usage Conditions... 12
5 Rated Values... 12
5.1 Overview... 12
5.2 Rated DC Voltage (UdN)... 13
5.3 Rated Insulation Level... 13
5.4 Rated DC Current (IdN)... 13
5.5 Rated Prospective Short-circuit Current... 14
5.6 Rated Cut-off Current... 14
5.7 Rated Supply Voltage of Auxiliary and Control Circuits... 14
5.8 Rated Supply Frequency of Auxiliary and Control Circuits... 14
5.9 Rated Charging Levels for Insulation and / or Opening and Closing... 14
5.10 Radio Interference Voltage Level (RIV)... 14
6 Design and Structure... 15
6.1 Overview... 15
6.2 Requirements for Liquids in DC Circuit-breakers... 15
6.3 Requirements for Gases in DC Circuit-breakers... 15
6.4 Seismic Resistance... 15
6.5 Mechanical Load of Terminal... 15
6.6 Auxiliary and Control Equipment... 15
6.7 Power Operation... 15
6.8 Energy Storage Operation... 16
6.9 Cooling Equipment... 16
6.10 Nameplate... 16
6.11 Location Indication... 16
6.12 Degree of Protection Provided by the Enclosure... 16
6.13 Specific Creepage Distance... 17
6.14 Gas and Vacuum Sealing... 17
6.15 Liquid Sealing... 17
6.16 Fire Hazard (flammability)... 17
6.17 Electromagnetic Compatibility (EMC)... 17
6.18 X-ray Emission... 17
6.19 Corrosion... 17
7 Type Test... 18
7.1 Overview... 18
7.2 Insulation Test... 18
7.3 Radio Interference Test... 20
7.4 Measurement of Main Circuit Resistance... 20
7.5 Test of Maximum Continuous Direct Current in Operation... 20
7.6 Short-time Withstand Current Test... 21
7.7 Protection Degree Verification... 21
7.8 Sealing Test... 21
7.9 Electromagnetic Compatibility (EMC) Test... 21
7.10 Mechanical Operation Test at Normal Temperature... 21
7.11 Terminal static load test... 21
7.12 Making and Interrupting Tests... 21
7.13 X-ray Test Procedures for Vacuum Arc-extinguishing Chamber... 23
7.14 Seismic Resistance Test... 23
7.15 Communication Conformance Test... 23
7.16 Cooling Equipment Test... 23
8 Exit-factory Test... 24
8.1 Overview... 24
8.2 Insulation Test of Main Circuit... 24
8.3 Test of Auxiliary and Control Circuits... 24
8.4 Measurement of Main Circuit Resistance... 24
8.5 Sealing Test... 24
8.6 Design and Appearance Inspection... 25
8.7 Mechanical Operation Test... 25
9 Selection Guidelines for DC Circuit-breakers... 25
9.1 Overview... 25
9.2 Selection of Ratings for DC Circuit-breakers... 25
9.3 Selection of Types of DC Circuit-breakers... 25
10 Information Provided during Inquiring, Bidding and Ordering... 27
10.1 Overview... 27
10.2 Inquiry and Order Information... 27
10.3 Information on the Bidding Documents... 28
11 Transportation, Storage, Installation, Operation and Maintenance Rules... 28
11.1 Overview... 28
11.2 Transportation, Storage and Installation Conditions... 28
11.3 Installation... 28
11.4 Operation... 28
11.5 Maintenance... 29
Common Specifications of High-voltage Direct Current
Circuit-breakers for High-voltage Direct Current
Transmission Using Voltage Sourced Converters
1 Scope
This Standard specifies the operating environmental conditions, terms and definitions, ratings,
design and structure, type test, exit-factory test and selection guidelines, etc. of high-voltage
DC circuit-breakers for the VSC-HVDC.
This Standard is applicable to mechanical high-voltage DC circuit-breakers, power electronic
DC circuit-breakers and hybrid DC circuit-breakers installed indoors and outdoors for the VSC-
HVDC with a voltage level of DC 6 kV and above.
This Standard does not apply to specific types of DC circuit-breakers that are otherwise
specified in product standards related to DC circuit-breakers.
2 Normative References
The following documents are indispensable to the application of this document. In terms of
references with a specified date, only versions with a specified date are applicable to this
document. In terms of references without a specified date, the latest version (including all the
modifications) is applicable to this document.
GB/T 311.1-2012 Insulation Co-ordination - Part 1.Definitions, Principles and Rules
GB/T 1984-2014 High-voltage Alternating-current Circuit-breakers
GB/T 2900.20-2016 Electrotechnical Terminology - High-voltage Switchgear and Controlgear
GB/T 7354-2018 High-voltage Test Techniques - Partial Discharge Measurements
GB/T 11022-2011 Common Specifications for High-voltage Switchgear and Controlgear
Standards
GB/T 13498-2017 Terminology for High-voltage Direct Current (HVDC) Transmission
GB/T 13540-2009 Seismic Qualification for High-voltage Switchgear and Controlgear
GB/T 16927.1-2011 High-voltage Test Techniques - Part 1.General Definitions and Test
Requirements
GB/T 20990.1-2007 Thyristor Valves for High Voltage Direct Current (HVDC) Power
Transmission - Part 1.Electrical Testing
GB/T 25091-2010 High-voltage Direct-current Disconnectors and Earthing Switches
GB/T 30425-2013 Water Cooling Equipment for Converter Valves for High Voltage Direct
Current (HVDC) Power Transmission
GB/T 34139-2017 Technical Specification of Converters for High-voltage Direct Current
(HVDC) Transmission Using Voltage Sourced Converters (VSC)
IEC 61850-10.2012 Communication Networks and Systems in Substations - Part 10.
Conformance Testing
3 Terms and Definitions
Th terms and definitions defined in GB/T 2900.20-2016, GB/T 1984-2014 and GB/T 13498-
2017, and the following are applicable to this document.
3.1 General
3.1.1 high-voltage direct current circuit-breaker
A switching device that can make, carry and interrupt DC operating current, and can make,
carry and interrupt current under abnormal circuit conditions (for example, short-circuit
conditions) within a specified time.
NOTE 1.DC circuit-breakers generally include. main conduct branch, current transfer branch and
energy absorption branch. The main conduct branch is used to carry the DC operating
current, and with the cooperation of the transfer branch, it has the capability to interrupt
the main conduct branch current; the current transfer branch is used to transfer the current
of the main conduct branch to the energy absorption branch; the energy absorption branch
is used to absorb the energy stored in the system.
NOTE 2.in accordance with the type of interrupting components, DC circuit-breakers can be
divided into mechanical DC circuit-breakers, power electronic DC circuit-breakers and
hybrid DC circuit-breakers. In accordance with the direction of operating current, DC
circuit-breakers can be divided into unidirectional DC circuit-breakers and bidirectional
DC circuit-breakers.
3.1.2 mechanical DC circuit-breaker
A DC circuit-breaker that provides artificial zero-crossing oscillating current for mechanical
switching devices to realize the interruption of DC current.
NOTE. the typical structure is that the main conduct branch is a mechanical switching device, the
current transfer branch is an inductor and a capacitor (active or passive), and the energy
absorption branch is a lightning arrester. See Figure 1.
NOTE. this voltage depends on the characteristics of the circuit and the DC circuit-breaker.
3.2.5 peak transient interruption voltage
When a DC circuit-breaker interrupts the current, the maximum voltage value generated
between the terminals of the DC circuit-breaker.
3.2.6 maximum continuous direct current in operation
The DC current value flowing through the DC circuit-breaker when the DC system continues
to be overloaded. The maximum continuous direct current in operation is determined by the
continuous overload capability of the DC system.
NOTE. GB/T 34139-2017, definition 3.2, modified.
3.2.7 short-time overload direct current in operation
When the DC system operates in a mode exceeding the rated transmission power of the system
for a short period of time (for example, 3 seconds), the DC current value flowing through the
DC circuit breaker. The overload direct current in operation is determined by the overload
capability of the DC system.
NOTE 1.GB/T 34139-2017, definition 3.3.
NOTE 2.the verification of the DC circuit-breaker’s capability of short-time overload direct
current in operation is included in the short-time withstand current type test.
NOTE 3.please refer to Appendix A for the overload current of a typical domestic flexible DC
transmission project.
3.2.8 prospective short-circuit current
The current that may flow in a circuit when a circuit fault or incorrect wiring causes a short
circuit and the DC circuit-breaker is replaced by a conductor with negligible impedance.
NOTE. GB/T 2900.20-2016, definition 3.7, modified.
3.2.9 cut-off current
The maximum instantaneous current value reached during the interruption by a DC circuit-
breaker.
3.2.10 residual current
After the interruption by a DC circuit-breaker, the value of the current flowing through the DC
circuit-breaker when the residual current interrupting device is closed.
3.2.11 rising rate of short-circuit current
5.2 Rated DC Voltage (UdN)
Under the specified operating conditions, the DC voltage of the DC circuit-breaker for normal
and continuous operation, expressed in (kV).
The rated DC voltage can be selected from the following values.
6 kV, 10 kV, 25 kV, 35 kV, 50 kV, 100 kV, 160 kV, 200 kV, 320 kV, 400 kV, 535 kV, 800 kV.
NOTE 1.the above ratings are provided with reference to GB/T 34139-2017, combined with the
voltage levels of existing flexible DC transmission projects.
NOTE 2.when there are special requirements for DC voltage, they shall be determined by the
demand-side and the supply-side through negotiation.
5.3 Rated Insulation Level
The rated insulation level of the DC circuit-breakers is provided by actual projects.
The insulation level shall include DC withstand voltage (1 min DC withstand voltage Ud1min, 3
h DC withstand voltage Ud3h, and 1 h DC withstand voltage Ud1h), rated lightning impulse
withstand voltage Up and rated operating impulse withstand voltage Us.
Among them, the withstand voltage applies to the standard reference atmosphere [temperature
(20 C), pressure (101.3 kPa) and humidity (11 g/m3)] specified in GB/T 311.1-2012.These
withstand voltages include the altitude correct at the maximum altitude of 1,000 m specified
under normal operating conditions (see 2.2 of GB/T 11022-2011). For special applicable
conditions, the withstand voltage shall be corrected in accordance with 2.3 of GB/T 11022-
2011.
NOTE 1.when there are special requirements for the rated insulation level, they shall be determined
by the demand-side and the supply-side through negotiation.
NOTE 2.please refer to Appendix A for the rated insulation level of a certain domestic flexible DC
transmission project.
5.4 Rated DC Current (IdN)
Under the specified operating conditions, the average DC current of a DC circuit-breaker that
has been continuously operated for a long time, expressed in (A).
The rated DC current can be selected from the following values.
156 A, 250 A, 500 A, 625 A, 750 A,1,000 A, 1,250 A, 1,560 A, 2,000 A, 2,500 A, 3,000 A.
NOTE 1.the above ratings are provided with reference to GB/T 34139-2017, combined with the
current levels of existing flexible DC transmission projects.
NOTE 2.when there are special requirements for DC current, they shall be determined by the
demand-side and the supply-side through negotiation.
5.5 Rated Prospective Short-circuit Current
Under the specified conditions of use and performance and the specified voltage, the
prospective steady-state value of the current in the event of a short circuit at the interruption
terminal of the DC circuit-breakers, expressed in (kA).
The rated prospective short-circuit current of the DC circuit-breakers can be selected from the
following values.
8 kA, 10 kA, 12.5 kA, 16 kA, 20 kA, 25 kA, 31.5 kA, 40 kA, 50 kA, 63 kA.
NOTE 1.the above currents are selected from the R10 series specified in GB/T 762-2002.
NOTE 2.when there are special requirements for the rated prospective short-circuit current, they
shall be determined by the demand-side and the supply-side through negotiation.
5.6 Rated Cut-off Current
Under the specified conditions of use and performance and the specified voltage, the maximum
instantaneous current value of a DC circuit-breaker when it interrupts at the rated prospective
short-circuit current, expressed in (kA).
The rated cut-off current can be selected from the following values.
4 kA, 5 kA, 6.3 kA, 8 kA, 10 kA, 12.5 kA, 16 kA, 20 kA, 25 kA, 31.5 kA.
NOTE 1.the above currents are selected from the R10 series specified in GB/T 762-2002.
NOTE 2.when there are special requirements for the rated cut-off current, they shall be determined
by the demand-side and the supply-side through negotiation.
5.7 Rated Supply Voltage of Auxiliary and Control Circuits
4.9 of GB/T 11022-2011 is applicable.
5.8 Rated Supply Frequency of Auxiliary and Control Circuits
The standard value of rated supply frequency is AC 50 Hz or DC.
5.9 Rated Charging Levels for Insulation and / or Opening and Closing
4.12 of GB/T 11022-2011 is applicable.
5.10 Radio Interference Voltage Level (RIV)
When applying the highest test voltage, the radio interference voltage level does not exceed
2,000 V.
6.2.7.3 and 6.2.8.4 of GB/T 11022-2011 are applicable, with the following supplements. during
the inter-terminal test, the lightning arrester of the energy absorption branch is only equipped
with a lightning arrester jacket, or the lightning arrester is disconnected.
7.2.3 Operational impulse withstand voltage test
6.2.8.3 of GB/T 11022-2011 is applicable, with the following supplements. during the inter-
terminal test, the lightning arrester of the energy absorption branch is only equipped with a
lightning arrester jacket, or the lightning arrester is disconnected.
NOTE. it is advisable to carry out dry test, and wet test may also be carried out for outdoor DC
circuit-breakers.
7.2.4 DC voltage withstand test
The DC circuit-breakers shall be subjected to DC voltage withstand test between terminals and
terminals to ground. Chapter 5 of GB/T 16927.1-2011 and 8.3.1 of GB/T 20990.1-2007are
applicable, with the following modifications.
a) Inter-terminal DC voltage withstand test. between the two main terminals of the test
object, start to increase the voltage from not greater than 50% of 1 min test voltage
Ud1min, within 10 seconds, increase the voltage to Ud1min, and maintain for 1 minute,
then, drop to 1 h test voltage Ud1h, and maintain for 1 hour, then, drop to zero. Use
voltage of opposite polarity to repeat the above-mentioned test. During the test, the
lightning arrester of the energy absorption branch is only equipped with a lightning
arrester jacket, or the lightning arrester is disconnected.
b) Terminal-to-ground DC voltage withstand test. between the short-circuited main
terminal of the test object and the ground, start to increase the voltage from not greater
than 50% of 1 min test voltage Ud1min, within 10 seconds, increase the voltage to Ud1min,
and maintain for 1 minute, then, drop to 3 h test voltage Ud3h, and maintain for 3 hours,
then, drop to zero. Use voltage of opposite polarity to repeat the above-mentioned test.
NOTE. it is advisable to carry out dry test, and wet test may also be carried out for outdoor DC
circuit-breakers.
7.2.5 Partial discharge test
8.3.1 of GB/T 20990.1-2007 is applicable, with the following supplements.
In the partial discharge test, the partial discharge is measured in accordance with GB/T 7354-
2018 during the last 1 hour of the 3-h test specified in the ground DC voltage test. The number
of partial discharges of 300 pC shall be recorded in accordance with the provisions of Appendix
B of GB/T 20990.1-2007.Use voltage of opposite polarity to repeat the above-mentioned test.
Throughout the recording period, the average pulses above 300 pC shall not exceed 15 times
per minute; among them, the pulses above 500 pC shall not exceed 7 times per minute, the
pulses above 1,000 pC shall not exceed 3 times per minute, and the pulses above 2,000 pC shall
not exceed 1 time per minute.
NOTE. if an increasing trend in the number or level of partial discharge is observed, the test time
may be extended by the demand-side and the supply-side through negotiation.
7.2.6 Status check test
If, after the making and interrupting tests, the insulation performance between the terminals of
the DC circuit-breaker cannot be sufficiently and reliably verified by visual inspection, and
there are no other provisions in the relevant product standards, an inter-terminal DC voltage
withstand test may be carried out, and the test voltage is 80% of the 1 min DC withstand voltage
Ud1min and is maintained for 1 minute. Or other test methods may be determined by the demand-
side and the supply-side through negotiation.
7.3 Radio Interference Test
Applicable to DC circuit breakers with a rated DC voltage of 6 kV and above.
The test shall be carried out in accordance with the provisions of 6.9.1.1 in GB/T 11022-2011,
and shall be carried out through the following procedures.
Apply a voltage of UdN to the test object and maintain it for at least 5 minutes. Then, gradually
reduce the voltage to 0.3UdN, then, gradually increase to the initial value, and finally, reduce to
0.3UdN step by step. At each voltage level, radio interference measurements shall be carried out,
and a curve of the radio interference level recorded in the last voltage drop series against the
externally applied voltage shall be drawn. Thus, the obtained curve is the radio interference
characteristic of the test equipment. The voltage level difference is approximately 0.1UdN.
If the radio interference level at 1.1UdN does not exceed the value specified in 5.10, the test
object shall be deemed to have passed the test.
7.4 Measurement of Main Circuit Resistance
Applicable to mechanical switches of the main conduct branch. 6.4 of GB/T 11022-2011 is
applicable.
7.5 Test of Maximum Continuous Direct Current in Operation
6.5 of GB/T 11022-2011 is applicable, with the following supplements.
On the main conduct branch, carry out the test of maximum continuous direct current in
operation. The test current is not less than the maximum continuous DC current that may occur
in the DC circuit-breaker application system or the equivalent 50 Hz AC current. The test results
shall satisfy the requirements of 4.5 in GB/T 11022-2011, and no component damage or failure
shall occur after the test is completed.
Please refer to Appendix B for the test circuit schematic diagram and test current waveform
diagram.
In any interrupting test, all parts of the DC circuit-breaker shall operate in accordance with the
correct logic, and no malfunction or refusal to operate shall occur.
The test sample shall be able to withstand the transient interruption voltage after interrupting
the test current and shall not suffer from heavy breakdown.
7.12.3.3 Status of the device after the test
After the test is completed, the test object shall ensure normal mechanical and electrical
properties and be subjected to corresponding tests if necessary.
7.12.3.4 Recorded data
At least the following data shall be recorded during the test.
---cut-off current;
---peak transient interruption voltage;
---cut-off time;
---interruption time;
---make time;
---rising rate of short-circuit current;
---rising rate of transient interruption voltage.
7.13 X-ray Test Procedures for Vacuum Arc-extinguishing Chamber
6.11 of GB/T 11022-2011 is applicable (when applicable).
7.14 Seismic Resistance Test
The test shall be carried out in accordance with the provisions of GB/T 13540-2009 (when
applicable).
7.15 Communication Conformance Test
For the communication conformance test of substation automation systems and DC circuit-
breakers, IEC 61850-10.2012 is applicable (when applicable).
7.16 Cooling Equipment Test
The test shall be carried out in accordance with the provisions of GB/T 30425-2013 (when
applicable).
8 Exit-factory Test
8.1 Overview
Exit-factory test is to find defects in materials and structures, as well as errors in the assembly
process. They will not deteriorate the performance and reliability of the test object. Exit-factory
test shall be carried out on each manufactured product at any suitable and feasible place in the
manufacturer’s factory, so as to ensure that the product is consistent with the equipment that
has passed the type test. After consultation with the user, the exit-factory test can be carried out
on site.
If the DC circuit-breaker is not fully assembled before transport, then, all transport units shall
be individually tested. In this case, the manufacturer shall demonstrate the validity of these tests.
Products exiting the factory shall be accompanied by an exit-factory test report.
Each component of the DC circuit-breaker shall comply with the requirements of the respective
standards and be tested in accordance with these requirements.
8.2 Insulation Test of Main Circuit
8.2.1 Lightning impulse voltage test
6.2.7.3 and 6.2.8.4 of GB/T 11022-2011 are applicable, with the following modifications.
When the interrupting device is in the closed position, the lightning impulse withstand voltage
to ground shall be applied between the terminal and the ground.
When the interrupting device is in the open position, the lightning impulse withstand voltage
between fractures shall be applied between the terminals.
NOTE. during the test, disconnect the lightning arrester of the energy absorption branch.
8.2.2 DC withstand voltage test
Regarding the DC withstand voltage test, 7.2.4 is applicable.
8.3 Test of Auxiliary and Control Circuits
7.3 of GB/T 11022-2011 is applicable.
8.4 Measurement of Main Circuit Resistance
It is applicable to mechanical switches of the main conduct branch. 7.4 of GB/T 11022-2011 is
applicable.
8.5 Sealing Test
7.5 of GB/T 11022-2011 is applicable.
...... Source: Above contents are excerpted from the full-copy PDF -- translated/reviewed by: www.ChineseStandard.net / Wayne Zheng et al.
Tips & Frequently Asked QuestionsQuestion 1: How long will the true-PDF of English version of GB/T 38328-2019 be delivered?Answer: The full copy PDF of English version of GB/T 38328-2019 can be downloaded in 9 seconds, and it will also be emailed to you in 9 seconds (double mechanisms to ensure the delivery reliably), with PDF-invoice. Question 2: Can I share the purchased PDF of GB/T 38328-2019_English with my colleagues?Answer: Yes. The purchased PDF of GB/T 38328-2019_English will be deemed to be sold to your employer/organization who actually paid for it, including your colleagues and your employer's intranet. Question 3: Does the price include tax/VAT?Answer: Yes. Our tax invoice, downloaded/delivered in 9 seconds, includes all tax/VAT and complies with 100+ countries' tax regulations (tax exempted in 100+ countries) -- See Avoidance of Double Taxation Agreements (DTAs): List of DTAs signed between Singapore and 100+ countriesQuestion 4: Do you accept my currency other than USD?Answer: Yes. www.ChineseStandard.us -- GB/T 38328-2019 -- Click this link and select your country/currency to pay, the exact amount in your currency will be printed on the invoice. Full PDF will also be downloaded/emailed in 9 seconds.
How to buy and download a true PDF of English version of GB/T 38328-2019?A step-by-step guide to download PDF of GB/T 38328-2019_EnglishStep 1: Visit website https://www.ChineseStandard.net (Pay in USD), or https://www.ChineseStandard.us (Pay in any currencies such as Euro, KRW, JPY, AUD). Step 2: Search keyword "GB/T 38328-2019". Step 3: Click "Add to Cart". If multiple PDFs are required, repeat steps 2 and 3 to add up to 12 PDFs to cart. Step 4: Select payment option (Via payment agents Stripe or PayPal). Step 5: Customize Tax Invoice -- Fill up your email etc. Step 6: Click "Checkout". Step 7: Make payment by credit card, PayPal, Google Pay etc. After the payment is completed and in 9 seconds, you will receive 2 emails attached with the purchased PDFs and PDF-invoice, respectively. Step 8: Optional -- Go to download PDF. Step 9: Optional -- Click Open/Download PDF to download PDFs and invoice. See screenshots for above steps: Steps 1~3 Steps 4~6 Step 7 Step 8 Step 9
|