US$130.00 · In stock · Download in 9 secondsGB/T 37155.2-2019: Technical guidance of protection and control system on regional power grid - Part 2: Information interface and communication Delivery: 9 seconds. True-PDF full-copy in English & invoice will be downloaded + auto-delivered via email. See step-by-step procedureStatus: Valid
Standard ID | Contents [version] | USD | STEP2 | [PDF] delivery | Name of Chinese Standard | Status |
GB/T 37155.2-2019 | English | 130 |
Add to Cart
|
0-9 seconds. Auto-delivery
|
Technical guidance of protection and control system on regional power grid - Part 2: Information interface and communication
| Valid |
Excerpted PDFs (Download full copy in 9 seconds upon purchase)PDF Preview: GB/T 37155.2-2019
GB/T 37155.2-2019: Technical guidance of protection and control system on regional power grid - Part 2: Information interface and communication ---This is an excerpt. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.), auto-downloaded/delivered in 9 seconds, can be purchased online: https://www.ChineseStandard.net/PDF.aspx/GBT37155.2-2019
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
ICS 29.240
K 45
Technical guidance of protection and control system
on regional power grid - Part 2: Information interface
and communication
ISSUED ON: MAY 10, 2019
IMPLEMENTED ON: DECEMBER 01, 2019
Issued by: State Administration of Market Regulation;
Standardization Administration of the People's Republic of
China.
Table of Contents
Foreword ... 3
1 Scope ... 4
2 Normative references ... 4
3 Terms and definitions, abbreviations ... 4
4 In-station information ... 5
5 Inter-station communication ... 6
Annex A (informative) Step example of inter-station information configuration
process ... 11
Technical guidance of protection and control system
on regional power grid - Part 2: Information interface
and communication
1 Scope
This Part of GB/T 37155 specifies the information protection communication
principles and information interfaces based on IEC 61850 of protection and
control system on regional power grid, as well as the requirements of inter-
station communication principles, communication interfaces, communication
protocols and inter-station information configuration methods.
This Part applies to protection and control system on regional power grid, of
which the voltage level is 110 kV and below. The same type of protection and
control system on regional power grid with other voltage levels and the same
power grid reliability problem may refer to this Part.
2 Normative references
The following referenced documents are indispensable for the application of
this document. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any
amendments) applies.
GB/T 2900.49 Electrotechnical terminology - Power system protection (IEC
60050-448:1995, IDT)
IEC 61850 (all parts) Communication networks and systems in sub-stations
ISO/IEC 9314-3:1990 Information processing systems - Fibre distributed
data interface (FDDI) - Part 3: Physical layer medium dependent (PMD)]
3 Terms and definitions, abbreviations
3.1 Terms and definitions
For the purpose of this document, the terms and definitions defined in GB/T
2900.49 and following apply.
electrical signals of analog quantity and switching value in the station and
converts them to SV and GOOSE signals and sends upstream to the
station domain control substation; the GOOSE trip command or control
command sent downstream by the station domain control substation is
converted to analog signal by the intelligent acquisition device for
operational control.
d) It uses SV and/or GOOSE transmission mechanism to transmit analog
quantity and switching value information between the station domain
control substation and the area control master station.
4.2 Station domain control substation information interface
The station domain control substation information interface shall follow the
following principles:
a) The station domain control substation should have an interface to obtain
information such as power, voltage and current RMS values of the station
through station control layer equipment.
b) The station domain control substation shall have a process layer
communication interface, and can obtain analog quantity and switching
value through process layer equipment or intelligent acquisition device.
c) The in-station data transmission shall meet the requirements of SV and/or
GOOSE transmission mechanism.
5 Inter-station communication
5.1 Inter-station (between distribution terminals) communication
principles
The substation inter-station communication shall follow the following principles:
a) The inter-station communication should adopt peer to peer
communication network topology, and have ring protection function and
network self-healing capability.
b) The inter-station communication data interface shall be compatible with
transmission equipment such as SDH/MSTP, PTN, OTN, EPON.
c) The inter-station communication shall support the transmission of analog
quantity and switching value data, and the data shall be guaranteed in
real time.
d) The regional power grid with regional differential protection function shall
Annex A
(informative)
Step example of inter-station information configuration process
The inter-station information configuration process is implemented by referring
to the following steps (taking Figure A.1 as an example):
a) Station 2 exports the SED2 file containing the inter-station information and
sets the engineering configuration permission attribute of the
communication interval of this station. For example, in Figure A.1, the
station domain control substation AA2 exports the SED file containing the
communication interval IED AA2F1, i.e. SED2, and sets the engineering
configuration permission engRight attribute of AA2F1 to “data flow”,
allowing engineering configuration; the engRight attribute of other interval
IED is set to “fix”, not allowing configuration.
b) Station 1 imports the SED2 file and completes the inter-station information
connection between the communication interval of this station and the
communication interval of station 2. For example, in Figure A.1, the
regional control master station AA1 imports the SED2 file of the substation
AA2, and completes the virtual terminal connection between the
communication interval AA1F2 of this station and the communication
interval AA2F1 of station 2.
c) Station 1 completes the inter-station information configuration of the
communication interval of this station, sets the engineering configuration
permission attribute of the communication interval of this station, exports
the SED1 file. For example, in Figure A.1, the master station AA1 uses the
IED configuration tool to complete the virtual terminal configuration of the
communication interval AA1F2 of this station, and derives a SED1 file with
the same ID (identification) as the SED2 but has been instantiated. The
engRight attribute of the communication interval AA1F2 of this station is
set to “fix”, and the engRight attribute of the communication interval
AA2F1 of station 2 is still “data flow”.
d) Station 2 imports the SED1 file and completes the inter-station information
configuration and in-station information configuration of the
communication interval of this station. For example, in Figure A.1, the
substation AA2 imports the SED1 file, implements the inter-station
information configuration of the communication interval AA2F1 of this
station, and uses the IED configuration tool to complete the in-station
information configuration.
...... Source: Above contents are excerpted from the full-copy PDF -- translated/reviewed by: www.ChineseStandard.net / Wayne Zheng et al.
Tips & Frequently Asked QuestionsQuestion 1: How long will the true-PDF of English version of GB/T 37155.2-2019 be delivered?Answer: The full copy PDF of English version of GB/T 37155.2-2019 can be downloaded in 9 seconds, and it will also be emailed to you in 9 seconds (double mechanisms to ensure the delivery reliably), with PDF-invoice. Question 2: Can I share the purchased PDF of GB/T 37155.2-2019_English with my colleagues?Answer: Yes. The purchased PDF of GB/T 37155.2-2019_English will be deemed to be sold to your employer/organization who actually paid for it, including your colleagues and your employer's intranet. Question 3: Does the price include tax/VAT?Answer: Yes. Our tax invoice, downloaded/delivered in 9 seconds, includes all tax/VAT and complies with 100+ countries' tax regulations (tax exempted in 100+ countries) -- See Avoidance of Double Taxation Agreements (DTAs): List of DTAs signed between Singapore and 100+ countriesQuestion 4: Do you accept my currency other than USD?Answer: Yes. www.ChineseStandard.us -- GB/T 37155.2-2019 -- Click this link and select your country/currency to pay, the exact amount in your currency will be printed on the invoice. Full PDF will also be downloaded/emailed in 9 seconds.
How to buy and download a true PDF of English version of GB/T 37155.2-2019?A step-by-step guide to download PDF of GB/T 37155.2-2019_EnglishStep 1: Visit website https://www.ChineseStandard.net (Pay in USD), or https://www.ChineseStandard.us (Pay in any currencies such as Euro, KRW, JPY, AUD). Step 2: Search keyword "GB/T 37155.2-2019". Step 3: Click "Add to Cart". If multiple PDFs are required, repeat steps 2 and 3 to add up to 12 PDFs to cart. Step 4: Select payment option (Via payment agents Stripe or PayPal). Step 5: Customize Tax Invoice -- Fill up your email etc. Step 6: Click "Checkout". Step 7: Make payment by credit card, PayPal, Google Pay etc. After the payment is completed and in 9 seconds, you will receive 2 emails attached with the purchased PDFs and PDF-invoice, respectively. Step 8: Optional -- Go to download PDF. Step 9: Optional -- Click Open/Download PDF to download PDFs and invoice. See screenshots for above steps: Steps 1~3 Steps 4~6 Step 7 Step 8 Step 9
|