Standard ID: GB/Z 1094.14-2011 (GB/Z1094.14-2011)
Description (Translated English): Power transformers -- Part 14: Design and application of liquid-immersed transformers using high-temperature insulation material
Sector / Industry: National Standard
Classification of Chinese Standard: K41
Classification of International Standard: 29.180
Word Count Estimation: 38,372
Date of Issue: 2011-12-30
Date of Implementation: 2012-05-01
Quoted Standard: IEC 60317-0-1; IEC 60317-0-2; IEC 60317-0-3; IEC 60317-0-4; IEC 60317-0-5; IEC 60317-0-6; IEC 60317-0-7; IEC 60317-1; IEC 60317-12; IEC 60317-13; IEC 60317-15; IEC 60317-16; IEC 60317-17; IEC 60317-18; IEC 60317-19; IEC 60317-20; IEC 60317-21; IEC 60317-2; IEC 60317-22; IEC 60317-23; IEC 60317-25; IEC 60317-26; IEC 60317-27; IEC 60317-28; IEC 60317-29; IEC 60317-31; IEC 60317-3; IEC 60317-32; IEC 60317-33; IEC 60317-34; IEC 60317-35; IEC 60317-36; IEC 60317-37; IEC 60317-38; IEC 60317-39; IEC 60317-40; IEC 60317-4; IEC 60317-42; IEC 60317-43; IEC 60317-44; IEC 60317-46; IEC 60317-47; IEC 60317-48; IEC 60317-49; IEC 60317-50; IEC 60317-51; IEC 60317-52; IEC 60317-53; IEC 60317-54; IEC 60317-55; IEC 60317-57; IEC 60317-58; IEC 60317-8; IEC 60554-3-1; IEC 60554-3-2; IEC 60
Adopted Standard: IEC/TS 60076-14-2009, IDT
Regulation (derived from): ?National Standard Approval Announcement 2011 No.22
Issuing agency(ies): Ministry of Health of the People's Republic of China
Summary: This standard specifies the use of high temperature insulation material or technical specifications of high temperature insulation materials combined with conventional insulation materials liquid-immersed transformers, design, tests and load and other information. For manufacturing and users. This standard applies to: design according to IEC 60076-1 power transformers, according to IEC 61378 series of standards designed converter transformer, arc furnace transformer. It also includes the use of a variety of liquid and solid insulation insulation combinations. For high-temperature insulating material traction transformers, this standard also has a guiding role.

GBZ1094.14-2011: Power transformers -- Part 14: Design and application of liquid-immersed transformers using high-temperature insulation material


---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Power transformers. Part 14. Design and application of liquid-immersed transformers using high-temperature insulation material ICS 29.180 K41 People's Republic of China national standardization of technical guidance documents Power transformers Part 14. High temperature insulation Design and Application of Liquid Immersed Transformer Powertransformers-Part 14.Designandapplicationofliquid-immersed (IEC /T S60076-14.2009, IDT) Posted on December 30,.2011 2012-05-01 implementation General Administration of Quality Supervision, Inspection and Quarantine of People's Republic of China China National Standardization Administration released Directory Foreword Ⅲ Introduction IV 1 Scope 1 2 Normative references 1 3 Terms and definitions 2 4 insulation 4 4.1 Overview 4 4.2 insulation aging and life 4 4.3 solid insulation 5 4.4 wire insulation coating 6 4.5 Insulation liquid 7 5 insulation system 9 5.1 Overview 9 5.2 insulation system type 9 6 temperature limit 12 7 Transformer Accessories and Compatibility 14 7.1 Overview 14 7.2 Casing 14 7.3 tap changer 15 7.4 Sealing material 15 7.5 tank painting 15 7.6 Cooler 15 7.7 oil pump 15 7.8 Fuel tank and oil conservator 15 7.9 Adhesive 15 7.10 current transformer 16 7.11 Thermostat 16 7.12 protection relay 16 7.13 Auxiliary Cables Special considerations when designing 16 8.1 Short circuit considerations 16 8.2 insulation requirements 16 8.3 Temperature Requirements 16 8.4 Overload 18 8.5 Harmonic Current Effect 18 8.6 Oil Protection System 18 Information Needed 18 9.1 User should provide information 18 9.2 Information to be provided by the manufacturer 19 Nameplate and supplementary information 10.1 Nameplate and warning plate 19 10.2 Transformer Manual 19 11 Test 19 11.1 Overview 19 11.2 Routine tests, type tests and special test requirements 20 11.3 Temperature rise test 20 11.4 Insulation type test 22 Monitoring, diagnosis and maintenance 12.1 Overview 22 12.2 Mineral oil impregnated transformer 22 12.3 high temperature insulation liquid immersion transformer 22 Appendix A (informative) and this part of the normative references to international documents consistent correspondence between our documents 23 Appendix B (Informative) See Table 4 and Table 5 transformer temperature 24 Appendix C (Informative) Calculation of bubble generation temperature 25 C.1 Overview 25 C.2 Basic assumptions 25 C.3 Mathematical formula for bubble generation 26 References 30

Foreword

GB 1094 "Power Transformer" is divided into the following sections. --- Part 1. General principles; --- Part 2. Temperature rise; --- Part 3. Insulation level, insulation test and external insulation air gap; --- Part 4. Power transformer and reactor lightning shock and operational impact test guidelines; --- Part 5. To withstand short-circuit ability; --- Part 6. Reactors; --- Part 7. Oil-immersed power transformer load guide; --- Part 10. Sound level determination; --- Part 10.1. Application of sound level measurement guidelines; --- Part 11. Dry-type transformers; --- Part 14. Design and application of liquid immersed transformers with high temperature insulation. This guidance document is part 14 of GB 1094. This instructional document has been drafted in accordance with the rules given in GB/T 1.1-2009. This guideline uses the translation method equivalent to IEC /T S60076-14.2009 "Power Transformer Part 14. High Design and Application of Liquid Immersion Transformer with Thermal Insulation "(in English). The Chinese documents with a consistent correspondence between the normative references in this Guidance Document are in Appendix A. The following technical amendments to IEC /T S60076-14.2009 have also been made in this Guidance Document. a) Replace "This International Standard" with "This Guidance Technical Paper"; b) Use the decimal "." instead of the comma "," as the decimal point; c) Delete the foreword of IEC /T S60076-14.2009; Please note that some of this document may be patentable. The issuing agencies of this document do not bear the responsibility of identifying these patents. This guidance document is proposed by China Electrical Equipment Industry Association. The guidance of technical documents by the National Standardization Technical Committee Transformer (SAC/TC44) centralized. The drafting of the guidance of technical documents. Shenyang Transformer Research Institute, CLP Electric Group Co., Ltd., Baoding Tianwei change Electric shares Co., Ltd., East China Power Grid Co., Ltd., Xi'an XD Power Transformer Co., Ltd., Shun Special Electric Equipment Co., Ltd., TBEA Hengyang change Compressor Co., Ltd., Pearl Electric Co., Ltd. The main drafters of this technical document are Zhang Xianzhong, Xu Zihong, Hu Zhenzhong, Jiang Yimin, Gao Chuanlong, Liu Yan and Cai Dingguo.

Introduction

For decades, as defined by IEC 60076-2, the average temperature rise of liquid immersed transformer windings has been limited to 65K/70K, with the top oil Temperature rise is limited to 60K. Historically, winding conductors in liquid immersed transformers have been insulated with cellulose paper or enamel, and other solid insulating materials Material is also a cellulose product. As for the insulating liquid, mineral oil is still the most important. These insulation materials are still dominant today. The vast majority of the operating experience accumulated by transformers over the years is based on these insulation materials and temperature rise limits. Sometimes Space and weight limitations require designers to employ higher temperature rise values to reduce transformer size and reduce transformer weight. this , Better insulating materials (solid and liquid) are required, the temperature limits of which are higher than those conventionally specified and the aging characteristics at this high temperature are still Good and have an acceptable life expectancy. Sometimes high-temperature insulation can also be used in some parts of the winding that are considered hot. Recently adopted fiber optic measurement techniques show that the hot spot temperature is sometimes higher than expected. Even in some cases much higher. In this way, old The conversion rate will be higher than expected. With this measurement, the location of the hot spot and the phase at which high temperature insulating material etc. may be used Knowledge. From wire enamels and wraps to pads, stays and structural supports and other high temperature insulation has been used for large power transformers, small distribution transformers Mobile transformers, electric vehicles (traction) transformers and rectifier transformers. Flash point is much higher than 300 ℃, suitable for high temperature than mineral oil Class K fluids have been used for decades. Their use and scope are rapidly increasing. Over the years, the transformer manufacturer in order to meet A variety of special needs of use, has been designed to make the transformer using high-temperature materials, so as to achieve the transformer light weight, high capacity density, anti- Fire ability, long life purpose. The purpose of this technical specification is to start the standardization process of developing liquid immersed transformers with high temperature insulation. From the system, solid absolutely Edge may include a variety of materials, they have different heat resistance levels. Insulating and cooling fluids can also range from mineral oils to a variety of new ones K-class liquid, but also a variety of heat capacity. Insulation systems consisting of liquid and solid insulating materials used in current standard liquid immersed transformers have occurred and developed in excess of 100 years. Therefore, its application rules and guidelines are also reliable and well researched. The corresponding high temperature insulation materials and the use of high temperature insulation Materials transformers are relatively new in application and research. Therefore, we should not be surprised at the fact that many materials are not sufficiently researched and not clearly understood. So build and maintain a text It is important to provide a starting point for discussion between the manufacturer and the user. This specification is expected to grow as the research progresses Updated. This document is not a separate document and it must be used in conjunction with the extensive information and guidance provided in other documents in the IEC 60076 series. This document therefore follows two principles. First, liquid immersed transformers are very popular, other standards in this series have made a very good standard, so in addition to the reference value or test Given the need to emphasize or compare purposes, this specification does not duplicate the details of these transformers. Second, conventional liquid-immersed transformers are insulated with sulfuric paper, laminates, wood, mineral oil, and many other common materials, Work under the limit is normal and considered to be normal or routine. All others have more than the thermal capacity used for normal insulation systems Solid or liquid insulating material, considered a high temperature material. Therefore, this "standard" or "normal" insulation system is defined as a "conventional" insulation system for comparison purposes, with their normal temperature limits Out to illustrate the difference with other high temperature system. The commonly used solid and liquid insulation with a common list of methods to facilitate the typical Can be compared, and explain the use of relatively unfamiliar materials and performance. This specification emphasizes loads, overloads, tests and accessories in the same way. Information on selected "conventional" transformers, used only Compare or emphasize the purpose. Other direct reference to the appropriate IEC file. Power transformers Part 14. High temperature insulation Design and Application of Liquid Immersed Transformer

1 Scope

This Guidance Document dictates the use of high temperature insulation materials or high temperature insulation materials and conventional insulation combination of liquid immersion type Pressure vessel specifications, design, test and load information for use by manufacturers and users. This guidance applies to technical documents. --- According to IEC 60076-1 design of power transformers; --- According to IEC 61378 series of standards designed converter transformer; --- Electric arc furnace transformer. Also includes the use of a variety of liquid insulation and solid insulation combination. For traction transformers with high temperature insulation materials, this Guidance Document also provides guidance.

2 Normative references

The following documents for the application of this document is essential. For dated references, only the dated version applies to this article Pieces. For undated references, the latest edition (including all amendments) applies to this document. IEC 60076-1.1993 power transformers Part 1. General (Powertransformers-Part 1.General) IEC 60076-2 Power Transformer Part 2. Temperature rise (Powertransformers-Part 2.Temperaturerise) IEC 60076-3 Power transformers - Part 3. Insulation levels, insulation tests and external insulation air gaps (Powertransform- ers-Part 3.Insulation levels, dielectrictestsandexternalclearancesinair) IEC 60076-5 Power Transformers Part 5. Capability to withstand short circuits (Powertransformers-Part 5.Abilityto withstandshort-circuit) IEC 60076-7-2005 Power transformers - Part 7. Oil-filled power transformer load guidelines (Powertransformers- Part 7.Loadingguideforoil-immersedpowertransformers) IEC 60085 electrical insulation heat classification (Electricalinsulation-Thermal classification) IEC 60216-1, Electrical insulating materials, heat resistance - Part 1. Evaluation of aging procedures and test results (Electrical insulatingmaterials-Propertiesofthermalendurance-Part 1.Ageingproceduresandevaluationof testresults) IEC 60296 Electrotechnical Fluid Transformers and Switches for Unused Mineral Insulating Oil (Fluidsforelectrotechnical applications-Unusedmineralinsulatingoilsfortransformersandswitchgear) IEC 60317 (all parts) Special winding wire specifications (Specificationsforpartulaulaypesofwindingwires) IEC 60554-3 (All parts) Specification for cellulosic paper for electricians - Part 3 - Specificationfor celulosicpapersforelectricalpurposes-Part 3.Specificationsforindividualmaterials) IEC 60641-3 (All parts) Specification for cardboard and platen for electricians - Part 3 - Specifications for individual materials (Pressboardand presspaperforelectricalpurposes-Part 3.Specificationsforindividualmaterials) IEC 60674-3 (All parts) Specification for plastic film for electrical applications - Part 3. Plastic material specifications electricalpurposes-Part 3.Specificationsforindividualmaterials)
......
Image     

Tips & Frequently Asked Questions:

Question 1: How long will the true-PDF of GBZ1094.14-2011_English be delivered?

Answer: Upon your order, we will start to translate GBZ1094.14-2011_English as soon as possible, and keep you informed of the progress. The lead time is typically 4 ~ 7 working days. The lengthier the document the longer the lead time.

Question 2: Can I share the purchased PDF of GBZ1094.14-2011_English with my colleagues?

Answer: Yes. The purchased PDF of GBZ1094.14-2011_English will be deemed to be sold to your employer/organization who actually pays for it, including your colleagues and your employer's intranet.

Question 3: Does the price include tax/VAT?

Answer: Yes. Our tax invoice, downloaded/delivered in 9 seconds, includes all tax/VAT and complies with 100+ countries' tax regulations (tax exempted in 100+ countries) -- See Avoidance of Double Taxation Agreements (DTAs): List of DTAs signed between Singapore and 100+ countries

Question 4: Do you accept my currency other than USD?

Answer: Yes. If you need your currency to be printed on the invoice, please write an email to Sales@ChineseStandard.net. In 2 working-hours, we will create a special link for you to pay in any currencies. Otherwise, follow the normal steps: Add to Cart -- Checkout -- Select your currency to pay.