Fire resistance test methods of ventilation ducts
| Valid |
GB 17428-1998 | 279 |
Add to Cart
|
3 days
|
Fire resistance test method of ventilation ducts
| Obsolete |
Standard ID | GB/T 17428-2009 (GB/T17428-2009) | Description (Translated English) | Fire resistance test methods of ventilation ducts | Sector / Industry | National Standard (Recommended) | Classification of Chinese Standard | C82 | Classification of International Standard | 13.220.50 | Word Count Estimation | 17,181 | Date of Issue | 2009-10-30 | Date of Implementation | 2010-04-01 | Older Standard (superseded by this standard) | GB 17428-1998 | Quoted Standard | GB/T 5907; GB/T 9978.1 | Adopted Standard | ISO 6944-1-2008, NEQ | Drafting Organization | Tianjin Fire Research Institute of Ministry of Public Security | Administrative Organization | Fire Eighth National Standardization Technical Committee Technical Committee | Regulation (derived from) | National Standard Approval Announcement 2009 No.12 (Total No.152) | Proposing organization | Ministry of Public Security of the People Republic of China | Issuing agency(ies) | General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China, China National Standardization Administration Committee | Summary | This standard specifies the level of fire resistance of ventilation ducts under standard test methods for fire conditions. Used to test the ventilation pipe to withstand the external fire (Pipeline A) and internal fire (pipe B) when the role of fire resistance. Fire test vertical pipe can refer to this standard. |
GB/T 17428-2009
Fire resistance test methods of ventilation ducts
ICS 13.220.50
C82
National Standards of People's Republic of China
Replacing GB 17428-1998
Ventilation ducts resistance test methods
(ISO 6944-1.2008, Firecontainment-Elementsofbuildingconstruction-
Part 1. Ventilationducts, NEQ)
Posted 2009-10-30
2010-04-01 implementation
Administration of Quality Supervision, Inspection and Quarantine of People's Republic of China
Standardization Administration of China released
Table of Contents
Introduction Ⅲ
1 Scope 1
2 Normative references 1
3 Terms and definitions
4 test apparatus 2
5 Test conditions 3
6 specimen 3
Installation 7 specimen 4
8 Conservation 5
9 instrument 5
10 Test Procedure 9
11 Criteria 10
12 results presentation 10
13 11 Test Report
Direct application range of 11 14 test results
References 13
Foreword
This standard ISO 6944-1.2008 "fire separation - structural member - ventilation ducts" (in English) of the degree of non-conformity
Equivalent.
This standard replaces GB 17428-1998 "fire resistance test method of ventilation ducts."
This standard and GB 17428-1998 more significant changes are as follows.
--- Increase the "warning" content, suggesting that the user of this standard should be noted that matters (Excerpts of the "scope" before);
--- Modify the scope of a chapter, to further clarify the application of the criteria objects (Chapter 1, 1998 edition and this edition);
--- Modify the normative references (1998 edition and the edition Chapter 2);
--- Increased terms and definitions (see Chapter 3);
--- Modify the requirements of the test device (5th edition 1998, chapter 4 of this edition);
--- Modify the test conditions (1998 Edition Chapter 4, Chapter 5 edition);
--- Revised requirements for specimen (1998 Edition Chapter 6, Section 6 edition);
--- Increasing the installation requirements of the specimen (see Chapter 7);
--- Increased specimen conservation requirements (see Chapter 8);
--- Increased equipment requirements (see Chapter 9);
--- Modified test procedure (1998 Edition Chapter 7, Chapter 10 edition);
--- The observation, measurement, recording and incorporated into the revised test procedure (1998 Edition Chapter 8, edition Chapter 10);
--- Modify the determination criterion condition, and its contents have been modified (1998 Edition Chapter 9, edition Chapter 11);
--- Increasing the test results are expressed (see Chapter 12);
--- Modify the content of the test report (1998 edition Chapter 10, edition Chapter 13);
--- Increasing the direct application of test results (see Chapter 14).
The standard proposed by the People's Republic of China Ministry of Public Security.
This standard by the National Standardization Technical Committee on Fire VIII Technical Committee (SAC/TC113/SC8) centralized.
This standard is drafted by. Ministry of Public Security in Tianjin Fire Research Institute.
Participated in the drafting of this standard. Guangzhou maintenance P US Building Materials Co., Yichun City, special building materials Industry Co., Ltd.
The main drafters of this standard. Solutions Fenglan, Zhaohua Li, Dong Jing, Li Xi whole, He Jianfeng, Wu Yong.
This standard replaces the previous standard release case. GB 17428-1998.
Ventilation ducts resistance test methods
Warning.
Organizations and all those involved in this test should be noted that the fire resistance test can be dangerous. It is possible to produce in the fire resistance test in the process of
Toxic and/or harmful fumes and smoke. After the specimen installation, test procedures and test cleanup process residues, or it may appear dangerous machinery
Harm and dangerous operation.
After the fire resistance test before dismantling pipes, pipe should be completely cooled reach combustible residue without the possibility of resurgence.
Deal with all potential hazards and assess the health risks and make safety notice. It should enact rules to enter the relevant personnel
Line the necessary training to ensure that the laboratory staff by the rules and operations.
1 Scope
This standard specifies the level of ventilation ducts fire resistance test methods under standard fire conditions used to test the ventilation pipe to withstand external fire
(Pipeline A) and an internal fire (duct B) fire resistance effect when. Fire Test vertical duct may refer to this standard.
This standard does not apply to.
a) fire resistance depends on the ceiling fire resistance of the pipeline;
Pipe b) with access door, unless the access door into the pipe tested together;
c) both sides or three sides of the pipeline;
d) exhaust pipes;
e) to the wall or floor attachment hanging fixture.
2 Normative references
The following documents contain provisions which, through reference in this standard and become the standard terms. For dated references, subsequent
Amendments (not including errata content) or revisions do not apply to this standard, however, encourage the parties to the agreement are based on research
Whether the latest versions of these documents. For undated reference documents, the latest versions apply to this standard.
GB/T 5907 basic fire Terminology Part 1)
GB/T 9978.1 building components resistance test methods - Part 1. General requirements (GB/T 9978.1-2008, ISO 834-1.
1999, MOD)
1) This standard will be revised in the integration of GB/T 5907-1986, GB/T 14107-1993 and GB/T 16283-1996 based on the "Fire Vocabulary" as
The general title, is divided into five parts; wherein, GB/T 5907.2 "Fire Vocabulary - Part 2. Fire Safety Vocabulary" will modify the use of
ISO 13943.2000.
3 Terms and Definitions
GB/T 5907, GB/T 9978.1 and established the following terms and definitions apply to this standard.
3.1
It used to pipe hanging in the beam or board member fixed to the wall on.
3.2
Test pipeline crossing the wall or partition.
......
|