Code for design of fire protection and prevention of alcoholic beverages factory
| Valid |
Excerpted PDFs (Download full copy in 9 seconds upon purchase)PDF Preview: GB 50694-2011
Similar standards GB/T 37850
GB 50694-2011: Code for design of fire protection and prevention of alcoholic beverages factory---This is an excerpt. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.), auto-downloaded/delivered in 9 seconds, can be purchased online: https://www.ChineseStandard.net/PDF.aspx/GB50694-2011
GB
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
UDC
P GB 50694-2011
Code for design of fire protection and prevention of alcoholic
beverages factory
Issued on: JULY 26, 2011
Implemented on: JUNE 01, 2012
Issued by. Ministry of Housing and Urban-Rural Development of PRC;
General Administration of Quality Supervision, Inspection and
Quarantine of the People's Republic of China.
Table of Contents
Foreword... 5
1 General provisions... 7
2 Terms... 7
3 Classification of fire hazards, fire resistance class and fire compartmentation... 8
4 General layout and plane arrangement... 11
4.1 General requirements... 11
4.2 Fire separation distance... 14
4.3 In-house road... 17
4.4 Fire station... 17
5 Fire and explosion protection of process system... 18
6 Store... 23
6.1 Alcoholic beverages warehouse... 23
6.2 Tank farm... 27
7 Fire water supply, fire extinguishing facilities and drain... 29
7.1 Fire water supply and fire extinguisher... 29
7.2 Fire extinguishing facility and fire chilled water system... 30
7.3 Drain... 32
8 Heating, ventilation, air conditioning and smoke exhaust... 33
9 Electric system... 35
9.1 Power supply and electrical equipment... 35
9.2 Lightning prevention and antistatic grounding... 36
9.3 Automatic fire alarm system... 38
Explanation of wording in this Code... 40
List of quoted standards... 41
Code for design of fire protection and prevention of alcoholic
beverages factory
1 General provisions
1.0.1 This Code is formulated to prevent fires in alcoholic beverages factory, reduce
fire hazards, protect personal and property safety.
1.0.2 This Code applies to the fire protection design of new construction, reconstruction,
expansion projects of alcoholic beverages factory and edible alcohol factories such as
Chinese spirits, wine, brandy, rice wine, beer, etc. It is not suitable for the fire protection
design of natural cave wine warehouses in alcoholic beverages factory.
1.0.3 The fire protection design of alcoholic beverages factory shall follow the relevant
national policies and guidelines, be safe, reliable, technologically advanced,
economically reasonable.
1.0.4 In addition to the provisions of this Code, the fire protection design of alcoholic
beverages factory shall also comply with the provisions of the current relevant national
standards.
2 Terms
2.0.1 Alcoholic beverages factory
A factory that produces alcoholic beverages. It includes factories producing various
types of alcoholic beverages such as Chinese spirits, wine, brandy, rice wine, beer,
mainly including raw material warehouse, raw material crushing workshop,
winemaking workshop, wine warehouse, blending workshop, filling and packaging
workshop, finished product warehouse and other production and storage facilities.
2.0.2 Alcohol percentage
The volume percentage of ethanol in alcoholic beverages.
2.0.3 Alcoholic beverages warehouse
An indoor place where beverages are stored in containers such as pottery jars, oak
barrels or metal storage tanks.
2.0.4 Man-made cave Chinese spirits depot
3.0.3 Unless otherwise specified in this Code, the fire resistance level, allowable
number of floors and maximum allowable building area of each fire compartment of
the factory building and warehouse shall comply with the relevant provisions of the
current national standard "Code for fire protection design of buildings" GB 50016.
3.0.4 The production rooms for blending, filling, packaging, temporary storage of
finished products, etc. in the joint factory building for the production of Chinese spirits
and brandy shall be separated from other parts by fire separation measures; when the
process conditions permit, they shall be separated by fire walls. When an automatic fire
extinguishing system and an automatic fire alarm system are installed in the production
joint plant, the maximum allowable building area of each fire compartment can be
increased to 2.5 times the area specified in the current national standard "Code for fire
protection design of buildings" GB 50016.
4 General layout and plane arrangement
4.1 General requirements
4.1.1 The site selection of the alcoholic beverages factory shall comply with the
requirements of urban and rural planning; it should be located at the edge of the
planning area or in a relatively independent safe area. The alcoholic beverages factory
shall reasonably determine the layout of different functional areas and set up fire trucks
and fire water sources, according to its production process, fire hazard and functional
requirements, combined with terrain, meteorological and other conditions.
4.1.2 The Chinese spirits storage tank farm and edible alcohol storage tank farm should
be located in a relatively independent safe area of the factory area; it should be located
on the upwind side of the factory area's minimum frequency wind direction throughout
the year. The site of the man-made cave Chinese spirits depot shall have good geological
conditions; it shall not be selected in areas with geological disaster risks.
4.1.3 Chinese spirits warehouse, man-made cave Chinese spirits depot, edible alcohol
warehouse, Chinese spirits tank farm, edible alcohol storage tank farm, brandy aging
warehouse shall be arranged separately from other production areas and office,
scientific research, living areas.
4.1.4 Except for man-made cave Chinese spirits depot and wine aging warehouse,
other category A and category B production and storage places of the alcoholic
beverages factory shall not be set up underground or semi-underground.
4.1.5 It is strictly prohibited to set up employee dormitories in the factory building;
meanwhile it shall comply with the following provisions.
1 Offices, lounges and other rooms shall not be set up in category A and category
B factory buildings. When it must be built adjacent to the factory building, its
fire resistance level shall not be lower than Level 2; it shall be separated by a
non-combustible explosion-proof wall with a fire resistance limit of not less
than 3.00 h; an independent safety exit shall be set up.
2 The offices and rest rooms set up in category C factory buildings shall be
separated from the factory buildings by non-combustible walls with a fire
resistance of not less than 2.50 h and floors with a fire resistance of not less
than 1.00 h; at least one independent safety exit shall be set up. When doors
and windows are required on the partition walls, category B fireproof doors
and windows shall be used.
4.1.6 It is strictly prohibited to set up employee dormitories in warehouses;
meanwhile it shall comply with the following provisions.
1 It is strictly prohibited to set up offices, rest rooms and other rooms in
category A and B warehouses; meanwhile they shall not be built adjacent to
category A and B warehouses.
2 The offices, rest rooms, management rooms set up in category C and category
D warehouses shall be separated from the warehouses, by non-combustible
walls with a fire resistance of not less than 2.50 h and floors with a fire
resistance of not less than 1.00 h; independent safety exits shall be set up. If
doors and windows are required on the partition walls, category B fireproof
doors and windows shall be used.
4.1.7 The filling workshop of Chinese spirits and brandy shall comply with the
following provisions.
1 It shall be separated from the blending workshop, bottle washing workshop,
packaging workshop by a non-combustible partition wall, which has a fire
resistance limit of not less than 3.00 h.
2 A passage with a width of not less than 3 m shall be left between each production
line.
3 The capacity of the finished wine filling tanks installed on each production line
shall not be greater than 3 m3.
4 When the single tank capacity of the finished wine filling tanks of each production
line is greater than 3 m3 but less than or equal to 20 m3, meanwhile the total capacity
is less than or equal to 100 m3, the filling tanks can be set on the first or second
floor of the building near the outer wall; it shall be separated from the filling
workshop, blending workshop, packaging workshop, bottle washing workshop, etc.
by a non-combustible partition wall with a fire resistance limit of not less than 3.00
h and a floor slab with a fire resistance of not less than 1.50 h; an independent
safety exit shall be set at the location where the filling tanks are set.
5 When the single tank capacity of the finished wine filling tanks of each production
line is greater than 20 m3 or the total capacity is greater than 100 m3, the filling
tanks shall be set up independently outside the building.
4.1.8 When the Chinese spirits blending workshop and its wine warehouse, the brandy
blending workshop and its aging warehouse are located in the same building, the
blending workshop shall be located on the first floor of the building near the outer wall;
it shall be divided into independent fire compartments and independent safety exits. No
door or window openings shall be made on the firewall.
4.1.9 The fire control room, fire pump room, self-provided generator room,
transformer and distribution room, etc. shall not be located in or adjacent to the
Chinese spirits storage tank farm, edible alcohol storage tank farm, Chinese spirits
warehouse, man-made cave Chinese spirits depot, edible alcohol warehouse, wine
aging warehouse, brandy aging warehouse. When set inside other buildings, they
shall be separated from other parts by non-combustible partition walls with a fire
resistance limit of not less than 2.00 h and floor slabs with a fire resistance limit of
not less than 1.50 h; the doors on the partition walls shall be class A fire doors. The
fire control room shall be equipped with a safety exit directly to the outside; the
door shall be clearly marked. The evacuation door of the fire pump room shall be
directly to the outside or close to the safety exit.
4.1.10 Transformer and distribution rooms of 10 kV and below for Chinese spirits
warehouses, edible alcohol warehouses, brandy aging warehouses, wine pump rooms
can be built adjacent to other buildings on one side, when separated by a fire wall
without door and window openings and meet the following conditions.
1 Only pipelines directly related to the transformer and distribution room pass
through the partition wall; meanwhile all holes through the wall shall be tightly
filled with fireproof blocking materials.
2 The indoor floor is 0.6 m higher than the outdoor floor of the Chinese spirits
warehouse, edible alcohol warehouse, brandy aging warehouse, wine pump room.
3 Doors and windows are set outside the explosion hazard area of the Chinese spirits
warehouse, edible alcohol warehouse, brandy aging warehouse, wine pump room.
4 The fire resistance limit of the roof panel is not less than 1.50 h.
4.1.11 When the wine pump room and air compressor room for Chinese spirits
warehouse, man-made cave Chinese spirits depot, brandy aging warehouse are
built adjacent to the warehouse, an independent safety exit shall be set up; the
warehouse shall be separated by a non-combustible partition wall without door
and window openings and with a fire resistance limit of not less than 3.00 h.
5.0.3 Open grain chutes (troughs) and other equipment shall not be used in factories
and warehouses. Mechanical equipment with dust explosion hazards should be installed
near the outer wall of single-story buildings or near the outer wall of the top floor of
multi-story buildings.
5.0.4 When transporting raw materials with dust explosion hazards, the mechanical
conveying equipment shall comply with the following requirements.
1 Belt conveyors, screw conveyors, bucket elevators and other conveying equipment
shall be equipped with magnetic separation devices and other cleaning devices at
appropriate locations; fire and explosion-proof valves shall be installed at
appropriate locations before the conveying equipment enters the silo.
2 Bucket elevators shall be installed in a separate working tower or outside the silo.
A negative pressure extraction dust removal system shall be separately installed at
the entrance of the elevator. The outer shell, head, base and connecting chute of the
elevator shall have good sealing performance. An explosion vent shall be installed
on the vertical section of the shell; a material cleaning port shall be installed at the
base; an inspection port shall be installed at the head. The elevator shall be
equipped with speed monitoring, fault alarm and shutdown devices.
3 The entire body of the screw conveyor shall be encapsulated by metal materials
and shall have good sealing performance. Measures shall be taken to prevent
blockage at the discharge port; a blockage shutdown device shall be installed.
4 The belt conveyor shall be equipped with wire protection, conveyor belt slip
detection, anti-deviation devices. Flame-retardant conveyor belts must be used and
metal buckles must not be used for connection. Suction ports shall be installed at
the feed and discharge ports of the equipment.
5 The conveyor trestle shall be made of non-combustible materials.
5.0.5 When conveying raw materials with dust explosion hazard, the air conveying
equipment shall comply with the following provisions.
1 When conveying raw materials from multiple different feeding points to one
unloading point, a vacuum conveying system shall be used; the unloader shall have
good sealing performance.
2 When conveying raw materials from one feeding point to multiple different
unloading points, a pressure conveying system may be used; the feeder shall have
good sealing performance.
3 When multiple air conveying systems are connected in parallel, each system shall
be equipped with a stop valve. The air conveying systems between different silos
shall not be interconnected. If they really need to be connected, a stop valve shall
be installed.
5.0.6 Raw material cleaning, crushing, koji making equipment shall have good sealing
performance; the internal components shall be firmly connected. Raw material crushing
equipment shall be equipped with inspection holes and cleaning holes that are easy to
operate. Non-productive electrical equipment should not be installed in the raw material
crushing workshop.
5.0.7 Raw material cooking equipment should be made of non-combustible materials;
steam heating should be used for cooking. When using wooden retort barrels, open
flame heating should not be used.
5.0.8 Distillation shall comply with the following provisions.
1 Distillation equipment should be made of non-combustible materials.
2 Distillation should be heated by steam; safety protection measures shall be taken
when open flame heating is used. In workshops using earthen pots to steam wine,
the earthen pot fire door and coal storage area must be located outside the workshop.
3 Distillation equipment and its pipelines, accessories, etc. shall have good sealing
performance.
4 When using tower distillation equipment to produce alcohol, an alcohol collector
shall be installed in the aldehyde discharge system of each tower; it shall have
sufficient volume. The outlet of the aldehyde discharge pipe should be connected
to the outdoors, meanwhile valves should not be installed.
5 The capacity of the transfer tank in the winemaking workshop shall not exceed
twice the daily output of the workshop; the storage time should not exceed 24 h.
5.0.9 Chinese spirits storage tanks, edible alcohol storage tanks, brandy aging storage
tanks shall comply with the following provisions.
1 The inlet and outlet wine pipes must be fixed and shall be connected flexibly. The
height of the wine pipe inlet from the bottom of the storage tank should not be
greater than 0.15 m; if there are difficulties, the outlet elevation of the wine pipe
shall be greater than the inlet elevation, the height difference shall not be less than
0.1 m.
2 At least two valves shall be installed on each wine pipe. The valves shall be quick-
opening valves with good sealing performance; leak-proof devices shall be
installed at the quick interface.
3 The storage tank shall be equipped with a liquid level gauge and a high liquid level
alarm device. If necessary, an automatic interlocking opening and closing liquid
inlet device or a remote opening and closing device can be installed. The storage
tank should not use a glass tube (plate) or other fragile material liquid level gauge.
4 The capacity of the emergency storage tank shall not be less than the capacity of
the single largest storage tank in the warehouse.
5 Wine samplers, tank covers, on-site tools are strictly prohibited from being made
of materials that are prone to sparks due to collision.
5.0.10 The pulping, blending, filling production process of Chinese spirits and brandy
shall comply with the following provisions.
1 When pulping and blending, it is strictly forbidden to use pure oxygen mixing
process. Compressed air can be used as the mixing medium, but the pulping and
blending work place shall have good ventilation; a negative pressure exhaust
system shall be used when necessary.
2 The wine vapor discharged from the filling port of the vacuum filler shall be
recovered by a negative pressure exhaust system and shall be directly discharged
to the outside.
3 The capping machine shall use a buffered flexible capping mechanism.
5.0.11 Categories A and B production and storage places shall use non-sparking
floors. When using insulating materials as the overall surface layer, anti-static
measures shall be taken. The inner surface of grain warehouses and raw material
crushing workshops shall be flat, smooth, easy to clean.
5.0.12 When fermentation is performed with fermented lees, sorghum wine, etc. instead
of brewing water, the height of the wine delivery pipe inlet of the fermentation tank
from the bottom of the raw material nest in the tank shall not be greater than 0.15 m.
When the rice wine decoction equipment uses a thin plate heat exchanger, the wine
vapor above the wine barrel shall flow back into the preheating section of the thin plate
heat exchanger; a recovery device shall be installed at the wine sweat outlet; its pipeline
shall have good sealing performance.
5.0.13 The ammonia refrigeration system shall be equipped with safety protection
devices and shall comply with the following provisions.
1 The ammonia compressor shall be equipped with an emergency stop button on the
unit control console.
2 The ammonia pump shall be equipped with an automatic pump stop device when
the liquid is cut off; a pressure gauge and a check valve shall be installed on the
discharge pipe; a bypass pressure relief valve shall be installed on the discharge
main pipe.
3 The low-pressure circulating liquid storage tank, ammonia liquid separator,
intercooler shall be equipped with an over-high liquid level alarm device and a
normal liquid level automatic control device; the low-pressure liquid storage tank
shall be equipped with an over-high liquid level alarm device.
4 Pressure vessels (equipment) shall be equipped with safety valves according to
product standards; safety valves shall be equipped with pressure relief pipes; the
outlet of the pressure relief pipes shall be 5 m higher than the roof of the highest
building within 50 m.
5 Emergency ammonia release devices shall be installed.
6 Pipes shall be made of seamless steel pipes; their quality shall meet the
requirements of the current national standard "Seamless steel pipes for liquid
service" GB 8163.The material shall be selected according to the minimum
working temperature in the pipe; the design pressure shall be 2.5 MPa (gauge
pressure).
7 Ammonia-specific valves and accessories shall be used; their nominal pressure
shall not be less than 2.5 MPa (gauge pressure); copper and galvanized parts shall
not be used.
5.0.14 When storage tanks, containers, process equipment need to be insulated, their
insulation materials shall be non-combustible materials. Flame-retardant foam can be
used for low-temperature cold preservation, but its protective layer shell shall be made
of non-combustible materials.
5.0.15 The design of wine pipelines shall comply with the relevant provisions of the
current national standard "Design code for industrial metallic piping" GB 50316.The
installation of pipelines for transporting Chinese spirits, edible alcohol, grape wine,
brandy, rice wine shall comply with the following provisions.
1 Wine pipelines should be laid overhead or along the ground. When trench laying
is necessary, measures shall be taken to prevent the accumulation of Chinese spirits
in the trench; sealed partitions shall be installed at the fire dikes in and out of the
factory, warehouse, wine pump room, tank farm. Wine pipelines are strictly
prohibited from being laid in the same trench as thermal pipelines; it shall not be
laid in the same trench as power cables.
2 Wine pipelines shall not pass through buildings that are not related to them. Valves
and pipeline accessories that are prone to leakage shall not be installed on wine
pipelines crossing roads. When wine pipelines cross roads, they shall be laid in
culverts or casings.
3 Wine pipelines are strictly prohibited from passing through firewalls and floors of
different fire partitions.
4 Except for the connection by thread or flange, the wine delivery pipeline shall be
connected by welding.
warehouse shall not be greater than 1000 m3; the fire separation distance between
tanks shall not be less than 50% of the diameter of the adjacent larger vertical
tank. When the capacity of a single tank is less than or equal to 100 m3 and the
capacity of a group of tanks is less than or equal to 500 m3, the tanks may be
arranged in groups; the fire separation distance between tanks shall not be less
than 0.5 m; the fire separation distance between tank groups shall not be less than
2 m. When the total capacity of the storage tanks in the Chinese spirits warehouse
and edible alcohol warehouse is greater than 5000 m3, fire walls without doors and
windows shall be used for separation.
6.1.7 When using pottery jars, wine seas, wine baskets, wine boxes, wine storage pools
and other containers to store Chinese spirits, the storage containers in the Chinese spirits
warehouse shall be stored in groups; the total storage capacity of each group should not
be greater than 250 m3.Non-combustible partitions shall be set between groups. If fire
doors are used to separate fire compartments, liquid blocking measures such as
additional barriers shall be taken in front of the doors. In areas with an earthquake
intensity of more than 6 degrees, pottery jars and other ceramic containers shall take
earthquake and collision prevention measures.
6.1.8 The setting of man-made cave Chinese spirits depots shall comply with the
following provisions.
1 Man-made cave Chinese spirits depots shall consist of lanes and caverns.
2 The total storage capacity of an man-made cave Chinese spirits depot shall
not be greater than 5000 m3; the net area of each cavern shall not be greater
than 500 m2.
3 There shall be no less than two safe exits from the tunnel to the outside of the
cave. Each cavern shall have no less than two exits to the tunnel; the horizontal
distance between the nearest edges of adjacent exits shall not be less than 5 m.
When the distance from the farthest point in the cavern to the exit does not
exceed 30 m, only one exit can be set.
4 The net width of the tunnel shall not be less than 3 m; the net height shall not
be less than 2.2 m. The horizontal distance between the nearest edges of the
exits from adjacent caverns to the tunnel shall not be less than 10 m.
5 When two caverns are connected, a fire compartment shall be set between the
caverns. The wall of the compartment shall be a fire wall; the net area of the
compartment shall not be less than 6 m2; the length of its short side shall not
be less than 2 m.
6 Non-combustible dikes and Class A fire doors shall be set between the tunnel
and the cavern, and between the cavern and the fire compartment. Fire doors
shall meet the requirements of rust and corrosion prevention; meanwhile it
shall have the function of automatic closing and controlled closing outside the
cave in case of fire.
7 The slope of the tunnel surface towards the tunnel entrance and the side ditch
shall not be less than 0.5%.
6.1.9 The storage of pottery containers such as pottery jars in man-made cave Chinese
spirits depots shall comply with the following provisions.
1 Pottery jars and other pottery containers shall be stored in different areas. The total
storage capacity of each area shall not be greater than 200 m3.Non-combustible
dikes shall be set between areas or accident storage pools shall be set up using the
terrain.
2 Pottery jars and other pottery containers in each area shall be stored in groups. The
total storage capacity of each group shall not be greater than 50 m3; the fire
separation distance between groups shall not be less than 1.2 m.
6.1.10 The load-bearing structure of Chinese spirits warehouses, edible alcohol
warehouses, brandy aging warehouses shall not use steel structures or prestressed
reinforced concrete structures.
6.1.11 Chinese spirits warehouses, man-made cave Chinese spirits depots, edible
alcohol warehouses, brandy aging warehouses shall be equipped with facilities to
prevent liquid from spilling.
6.1.12 Non-combustible fire-resistant eaves with a width of not less than 0.5 m shall be
installed above the windows of the exterior walls of multi-story Chinese spirits
warehouses, edible alcohol warehouses, brandy aging warehouses.
6.1.13 Accidental wine drainage facilities shall comply with the following provisions.
1 Accidental Chinese spirits drainage ports and valves should be installed in each
fire compartment of multi-story Chinese spirits warehouses, edible alcohol
warehouses, brandy aging warehouses. Vertical liquid guide pipes (channels) shall
be installed outside the warehouse; concrete pipes shall be used to connect the
drainage ports and liquid guide pipes (channels) to the outdoor accident liquid
storage pool.
2 Accidental Chinese spirits drainage ports and valves shall be installed in each
compartment of man-made cave Chinese spirits depots. Liquid guide pipes (ditches)
shall be installed in the cave to the outdoor accident liquid storage pool. Valves or
fire baffles shall be installed at the partitions where the liquid guide pipes (ditches)
pass through the compartments.
3 The slope of the multi-layer Chinese spirits warehouse, edible alcohol warehouse,
brandy aging warehouse, man-made cave Chinese spirits depot facing the
...... Source: Above contents are excerpted from the full-copy PDF -- translated/reviewed by: www.ChineseStandard.net / Wayne Zheng et al.
Tips & Frequently Asked QuestionsQuestion 1: How long will the true-PDF of English version of GB 50694-2011 be delivered?Answer: The full copy PDF of English version of GB 50694-2011 can be downloaded in 9 seconds, and it will also be emailed to you in 9 seconds (double mechanisms to ensure the delivery reliably), with PDF-invoice. Question 2: Can I share the purchased PDF of GB 50694-2011_English with my colleagues?Answer: Yes. The purchased PDF of GB 50694-2011_English will be deemed to be sold to your employer/organization who actually paid for it, including your colleagues and your employer's intranet. Question 3: Does the price include tax/VAT?Answer: Yes. Our tax invoice, downloaded/delivered in 9 seconds, includes all tax/VAT and complies with 100+ countries' tax regulations (tax exempted in 100+ countries) -- See Avoidance of Double Taxation Agreements (DTAs): List of DTAs signed between Singapore and 100+ countriesQuestion 4: Do you accept my currency other than USD?Answer: Yes. www.ChineseStandard.us -- GB 50694-2011 -- Click this link and select your country/currency to pay, the exact amount in your currency will be printed on the invoice. Full PDF will also be downloaded/emailed in 9 seconds.
How to buy and download a true PDF of English version of GB 50694-2011?A step-by-step guide to download PDF of GB 50694-2011_EnglishStep 1: Visit website https://www.ChineseStandard.net (Pay in USD), or https://www.ChineseStandard.us (Pay in any currencies such as Euro, KRW, JPY, AUD). Step 2: Search keyword "GB 50694-2011". Step 3: Click "Add to Cart". If multiple PDFs are required, repeat steps 2 and 3 to add up to 12 PDFs to cart. Step 4: Select payment option (Via payment agents Stripe or PayPal). Step 5: Customize Tax Invoice -- Fill up your email etc. Step 6: Click "Checkout". Step 7: Make payment by credit card, PayPal, Google Pay etc. After the payment is completed and in 9 seconds, you will receive 2 emails attached with the purchased PDFs and PDF-invoice, respectively. Step 8: Optional -- Go to download PDF. Step 9: Optional -- Click Open/Download PDF to download PDFs and invoice. See screenshots for above steps: Steps 1~3 Steps 4~6 Step 7 Step 8 Step 9
|