JB/T 8734.2-2016 (JB/T8734.2-2016, JBT 8734.2-2016, JBT8734.2-2016) & related versions
Standard ID | Contents [version] | USD | STEP2 | [PDF] delivered in | Standard Title (Description) | See Detail | Status | Similar PDF |
JB/T 8734.2-2016 | English | 209 |
Add to Cart
|
3 days
|
Polyvinyl chloride insulated cables and wires and cords of rated voltages up to and including 450/750V - Part 2: Insulated cables and wires for fixed wiring
|
JB/T 8734.2-2016
| Valid |
JBT 8734.2-2016
|
JB/T 8734.2-2012 | English | 120 |
Add to Cart
|
0-9 seconds. Auto delivery.
|
Polyvinyl chloride insulated cables and wires and cords of rated voltages up to and including 450/750 V - Part 2: Insulated cables and wires for fixed wiring
|
JB/T 8734.2-2012
| Obsolete |
JBT 8734.2-2012
|
JB/T 8734.2-1998 | English | 199 |
Add to Cart
|
2 days
|
Polyvinyl chloride insulated cables and wires and cords of rated voltages up to and including 450/750V. Part 2: Insulated cables and wires for fixed wiring
|
JB/T 8734.2-1998
| Obsolete |
JBT 8734.2-1998
|
JB/T 8734.2-2016: PDF in English (JBT 8734.2-2016) JB/T 8723.2‐2012
Translated English of Chinese Standard. JB/T8723.2‐2012
JB
ICS 29.060.20
K 13
Record No.. 36477-2012
INDUSTRY STANDARD
OF THE PEOPLE’S REPUBLIC OF CHINA
Replacing JB/T 8734.2-1998
Polyvinyl chloride insulated cables and wires and
cords of rated voltages up to and including 450/750V -
Part 2. Insulated cables and wires for fixed wiring
ISSUED ON. MAY 24, 2012
IMPLEMENTED ON. NOVEMBER 01, 2012
Issued by. Ministry of Industry and Information Technology of the
People’s Republic of China
Table of Contents
Foreword ... 3
1 Scope ... 5
2 Normative references ... 5
3 Operating characteristics ... 6
4 Models ... 6
5 Specifications ... 7
6 Technical requirements ... 7
6.1 General principle ... 7
6.2 Conductor ... 7
6.3 Insulation ... 7
6.4 Insulated core cabling ... 7
6.5 Sheath ... 7
6.6 Appearance dimension ... 8
7 Inspection ... 11
Foreword
JB/T 8734 Polyvinyl chloride insulated cables and wires and cords of rated voltages up to
and including 450/750V consists of 6 parts as follows.
— Part 1. General requirements;
— Part 2. Insulated cables and wires for fixed wiring;
— Part 3. Cords and cables for connecting;
— Part 4. Insulated wires for internal wiring of equipment;
— Part 5. Screened wires;
— Part 6. Lift cables.
This is part 2 of JB/T 8734.
This part is drafted according to the rules specified in GB/T 1.1-2009.
This part will replace JB/T 8734.2-1998 Polyvinyl chloride insulated cables and wires and
cords of rated voltages up to and including 450/750V Part 2. Insulated cables and wires
for fixed wiring. Compared with JB/T 8734.2-1998, main technical changes of this part are
as follows.
— Change the chapter’s name and relevant reference standards in Normative
References (see Chapter 2; Chapter 2 in 1998 edition);
— Add the nominal cross-section area and corresponding requirements for cable
conductor (see Table 2; Table 5 and Table 6);
— Change the upper limit of BVR cables with nominal cross-section areas of 10 mm²
and 16 mm² (see Table 5; Table 5 in 1998 edition).
This part was proposed by China Machinery Industry Federation.
This Standard shall be under the jurisdiction of National Technical Committee
(SAC/TC213) on Wire and Cables of Standardization Administration of China.
The responsible drafting organization of this part. Shanghai Cable Research Institute.
The participating drafting organizations of this part. Baosheng Science and Technology
Innovation Co., Ltd, Nanchang Cables Co., Ltd, Shanghai Nanyang-Fujikura Cable Co.,
Ltd, Shanghai Laogang Shenling Electric Cable Co., Ltd, Shenzhen Liajiaxiang Science &
Technology Co., Ltd, Guangzhou Cable Factory, Kunming Cables Co., Ltd, Hunan Jinbei
Cable Co., Ltd, Tianjin Jinshan Electric Wire & Cable Ltd, and ShangHai Panda Wire &
Cable Co., Ltd.
The main drafting staffs of this part. Lu Yanhong, Chen Jinmei, Yin Binxia, Xu Qiao, Gu
Youming, Huang Donglian, He Shaoqing, He Wenjun, Ai Weimin, Zheng Guojun, Zhou
Xiaorong, Xiao Jidong, Yan Yongchang, Ding Xiaoqing, and Wu Min.
This standard replaces the following historical edition.
— JB/T 8734.2-1998.
Polyvinyl chloride insulated cables and wires and cords of
rated voltages up to and including 450/750V - Part 2.
Insulated cables and wires for fixed wiring
1 Scope
This Part of JB/T 8734 specifies the operating characteristics, models, specifications,
technical requirements, and inspection of cables and wires for fixed wiring.
This Part applies to copper core or aluminum core polyvinyl chloride insulated cables and
wires that are used in AC rated voltage U0/U up to and including 450/750V.
2 Normative references
The articles contained in the following documents have become part of this document
when they are quoted herein. For the dated documents so quoted, all the modifications
(Including all corrections) or revisions made thereafter shall be applicable to this
document.
GB/T 2951.11-2008 Common test methods for insulating and sheathing materials of
electric and optical cables - Part 11. Methods for general application - Measurement of
thickness and overall dimensions - Tests for determining the mechanical properties
GB/T 2951.12-2008 Common test methods for insulating and sheathing materials of
electric and optical cables - Part 12. Methods for general application - Thermal ageing
methods
GB/T 2951.14-2008 Common test methods for insulating and sheathing materials of
electric and optical cables - Part 14. Methods for general application - Test at low
temperature
GB/T 2951.31-2008 Common test methods for insulating and sheathing materials of
electric and optical cables - Part 31. Methods specific to PVC compounds - Pressure
test at high temperature - Test for resistance to cracking
GB/T 2951.32-2008 Common test methods for insulating and sheathing materials of
electric and optical cables - Part 32. Methods specific to PVC compounds - Loss of
mass test - Thermal stability test
GB/T 5023.2-2008 Polyvinyl chloride insulated cables of rated voltages up to and
including 450/750V - Part 2. Test methods
GB/T 18380.12-2008 Test on electric and optical fibre cables under fire conditions -
Part 12. Test for vertical flame propagation for a single insulated wire or cable -
Procedure for 1kW pre-mixed flame
JB/T 8734.1-2012 Polyvinyl chloride insulated cables and wires and cords of rated
voltages up to and including 450/750V - Part 1. General requirements
3 Operating characteristics
3.1 The rated voltages U0/U of wires and cables are 450/750V and 300/500V.
3.2 Allowable long-term working temperature of all types of cables and wires shall not
exceed 70°C.
3.3 Laying temperature of cables and wires shall not below 0°C. The allowable bending
radius of cables and wires, with external diameter (D) of less than 25mm, shall be not less
than 4D. And allowable bending radius of cables and wires, with external diameter (D) of
25mm or above, shall not be less than 6D.
4 Models
Cables and wires’ models are shown in Table 1.
Table 1 Models and names
Models Names Primary usage
BV Copper core polyvinyl chloride insulated wire Fixed wiring
BLV Aluminum core polyvinyl chloride insulated cable Fixed wiring
BVR Copper core polyvinyl chloride insulated flexible cable
Flexible site is required during fixing
the wires
BVV Copper core polyvinyl chloride insulated polyvinyl chloride sheathed round cable Fixed wiring
BLVV Aluminum core polyvinyl chloride insulated polyvinyl chloride sheathed round cable Fixed wiring
BVVB Copper core polyvinyl chloride insulated polyvinyl chloride sheathed flat cable Fixed wiring
BLVVB Aluminum core polyvinyl chloride insulated polyvinyl chloride sheathed flat cable Fixed wiring
5 Specifications
Specifications of cables and wires are shown in Table 2.
Table 2 Specifications
Models Rated voltage V
Core
number
Nominal sectional area of
conductor with the unit of mm2
Structural parameters
table number
BV 300/500 1 0.75-1.0 Table 3
BLV 450/750 1 2.5-400 Table 4
BVR 450/750 1 0.75-185 Table 5
BVV 300/500 1 0.75-185 Table 6
BLVV 300/500 1 2.5-185 Table 6
BVVB 300/500 2-3 0.75-10 Table 7
BLVVB 300/500 2-3 2.5-10 Table 7
6 Technical requirements
6.1 General principle
In addition to comply with the technical requirements specified in this part, the cables and
wires shall also comply with the provisions of JB/T 8734.1-2012.
6.2 Conductor
Core number and structure of conductor shall comply with the provisions in Table 3 - Table
7.
6.3 Insulation
The insulation wrapped on the conductor shall be polyvinyl chloride compound with code
of PVC/C.
Insulation thickness shall comply with the provisions of Table 3 - Table 7.
Insulation resistance shall not be less than the values specified in Table 3 - Table 7.
6.4 Insulated core cabling
Insulated core of flat cable shall be placed in parallel.
6.5 Sheath
The sheath wrapped on the insulation or finished cable core shall be polyvinyl chloride
compound with code of PVC/ST4.
cables - low
temperature shock test
7 Thermal shock test
7.1 Insulation T T T T T GB/T 2951.31-2008 9.1
7.2 Sheath - - - T T GB/T 2951.31-2008 9.2
8 Flame non-propagation test T T T T T
GB/T
18380.12-2008
9 Mark - rubbing resistance inspection T, S T, S T, S T, S T, S GB/T 5023.2-2008 1.8
......
Standard ID | JB/T 8734.2-2016 (JB/T8734.2-2016) | Description (Translated English) | Polyvinyl chloride insulated cables and wires and cords of rated voltages up to and including 450/750V - Part 2: Insulated cables and wires for fixed wiring | Sector / Industry | Mechanical & Machinery Industry Standard (Recommended) | Classification of Chinese Standard | K13 | Classification of International Standard | 29.060.20 | Word Count Estimation | 9,940 | Date of Issue | 2016-04-05 | Date of Implementation | 2016-09-01 | Older Standard (superseded by this standard) | JB/T 8734.2-2012 | Regulation (derived from) | The Ministry of Industry and Notice No. 2016 in 2016; industry standard filing notice 2016 No. 8 (total No. 200) | Summary | This standard specifies the type, specification, technical requirements and inspection of wire and cable for fixed wiring. |
|