HOME   Cart(0)   Quotation   About-Us Policy PDFs Standard-List
www.ChineseStandard.net Database: 189759 (26 Oct 2025)

DL/T 1985-2019 English PDF

US$189.00 · In stock
Delivery: <= 3 days. True-PDF full-copy in English will be manually translated and delivered via email.
DL/T 1985-2019: Determination of mining ratio of SF6 gas mixture
Status: Valid
Standard IDContents [version]USDSTEP2[PDF] delivered inStandard Title (Description)StatusPDF
DL/T 1985-2019English189 Add to Cart 3 days [Need to translate] Determination of mining ratio of SF6 gas mixture Valid DL/T 1985-2019

PDF similar to DL/T 1985-2019


Standard similar to DL/T 1985-2019

DL/T 506   GB/T 12326   GB/T 14549   DL/T 1981.10   DL/T 1978   DL/T 1977   

Basic data

Standard ID DL/T 1985-2019 (DL/T1985-2019)
Description (Translated English) Determination of mining ratio of SF6 gas mixture
Sector / Industry Electricity & Power Industry Standard (Recommended)
Classification of Chinese Standard F20
Classification of International Standard 27.100
Word Count Estimation 8,870
Date of Issue 2019-06-04
Date of Implementation 2019-10-01
Quoted Standard DL/T 1032
Issuing agency(ies) National Energy Administration
Summary This standard specifies the sensor method and gas chromatography method for determining the gas mixture ratio of sulfur hexafluoride (SF6) mixed insulating gas. This standard is applicable to the detection of the gas mixture ratio in SF6/CF4, SF6/N2 mixed gas insulation equipment, and the detection of other SF6 mixed insulation gas mixture ratios can be carried out by reference.

DL/T 1985-2019: Determination of mining ratio of SF6 gas mixture

---This is a DRAFT version for illustration, not a final translation. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.) will be manually/carefully translated upon your order.
Determination of mining ratio of SF6 gas mixture DL/T 996-2019 ICS 27.100 F 20 People's Republic of China Electric Power Industry Standard Detection method for mixing ratio of sulfur hexafluoride mixed insulating gas 2019-06-04 released 2019-10-01 implementation Issued by National Energy Administration DL/T 996-2019

Table of contents

1 Scope...1 2 Normative references...1 3 Terms and definitions...1 4 Sampling...1 5 Testing...1 DL/T 996-2019

Foreword

This standard was drafted in accordance with the rules given in GB/T 1.1-2009. Please note that certain contents of this document may involve patents. The issuing agency of this document is not responsible for identifying these patents. This standard was proposed by the China Electricity Council. This standard is under the jurisdiction of the National Electrochemical Standards Technical Committee. Drafting organizations of this standard. State Grid Anhui Electric Power Co., Ltd. Electric Power Research Institute, China Electric Power Research Institute Co., Ltd., State Grid Hubei Electric Power Co., Ltd. Maintenance Company, State Grid Shandong Electric Power Company Electric Power Research Institute, State Grid Fujian Electric Power Co., Ltd. Company Electric Power Research Institute, Guangxi Power Grid Corporation Electric Power Research Institute, State Grid Jiangsu Electric Power Research Institute, Henan Hitachi Xin Co., Ltd., Langxi Instrument (Shanghai) Co., Ltd. The main drafters of this standard. Qi Jiong, Ma Fengxiang, Zhu Feng, Ji Yansong, Fu Hanjiang, Yu Naihai, Lian Hongsong, Zhu Liping, Zhu Hong Bin, Li Jianguo, Li Jianhao, Yan Xianglian, Yuan Xiaofang, Liu Wei, Song Yumei, Zheng Dongsheng. This standard is formulated for the first time. The opinions or suggestions during the implementation of this standard will be fed back to the Standardization Center of the China Electricity Council (Baiguang Road 2nd, Beijing) Article No. 1, 100761). Detection method for mixing ratio of sulfur hexafluoride mixed insulating gas

1 Scope

This standard specifies the sensor method and chromatographic method for determining the mixing ratio of sulfur hexafluoride (SF6) mixed insulating gas. This standard applies to the detection of gas mixture ratio in SF6/CF4, SF6/N2 mixed gas insulation equipment, and other SF6 mixtures Insulating gas mixture ratio detection can be implemented by reference.

2 Normative references

The following documents are indispensable for the application of this document. For dated reference documents, only the dated version Applies to this document. For undated references, the latest version (including all amendments) applies to this document. DL/T 1032 Sulfur hexafluoride (SF6) gas sampling method for electrical equipment

3 Terms and definitions

The following terms and definitions apply to this document. 3.1 SF6 gas mixture SF6 gas is an insulating gas mixed with another gas in a certain proportion. 3.2 SF6 gas mixture insulated equipment Electrical equipment that uses SF6 mixed gas as an insulating medium. 3.3 Gas mixture rate The volume fraction of SF6 in the SF6 mixed gas.

4 sampling

4.1 On-site analysis and sampling Connect the pipeline according to the requirements of the testing instrument, adopt the lead-in sampling, flush the pipeline for 3 to 5 minutes, and then sample for testing. 4.2 Laboratory analysis and sampling Follow the relevant regulations in DL/T 1032.

5 detection

5.1 Sensor method 5.1.1 Method summary Use thermal conductivity or infrared sensor to detect the difference in thermal conductivity or infrared absorption characteristics between SF6 and another gas The mixing ratio of the mixed gas; at the same time, an electrochemical sensor is used to detect the O2 content in the gas. The detection process is shown in Figure 1. 5.1.2 Instrument requirements 5.1.3 Environmental conditions a) Temperature. -10℃ ~ 40℃; b) Humidity. ≤85%RH. 5.1.4 Test steps Operate as follows. a) Turn on the power of the instrument and perform the corresponding settings according to the instructions after the instrument has been warmed up; b) Confirm that the air inlet valve of the instrument is in the closed state, connect the air inlet of the air source and the sampling port of the instrument, and connect the exhaust gas collection device Connect to the exhaust port of the instrument; c) During measurement, keep the oxygen sensor protection valve in a closed state, slowly open the gas flow regulating valve, and open the side Valve, flush the pipeline for 3 min~5 min, then adjust the gas flow to the setting range and open the protection valve to start After the test data is stable, record the SF6 and O2 test results; d) After the measurement is completed, the instrument should be purged with dry nitrogen for 3 min~5 min, first close the oxygen sensor protection valve, and then Turn off the instrument; e) Recycle the gas in the exhaust gas collection device. 5.1.5 Test results Take the arithmetic mean of two parallel determination results as the test result, and the test result is expressed in volume fraction. 5.1.6 Precision The absolute deviation of the two test results is SF6≤1%, O2≤0.1%. 5.2 Gas chromatography 5.2.1 Method summary The chromatographic column is used to separate SF6, CF4, N2, O2 and other components, and the gas of each component is entered through a thermal conductivity detector (TCD). Line testing. The test result is expressed in volume fraction. 5.2.2 Apparatus and materials a) Gas chromatograph. It should be equipped with a TCD detector, which can detect SF6, CF4, N2, O2 and other components, and can be used Data analysis is carried out by external standard method and calibration standardization method. See Table 1 for typical gas path flow. 5.2.3 Environmental conditions a) Temperature. -10℃ ~ 40℃; b) Humidity. ≤85%RH. 5.2.4 Detection steps Operate as follows. a) Set the working parameters of the chromatograph according to the requirements of the instrument, and wait until the instrument is stable for use; b) Use external standard method to quantitatively calibrate the chromatograph. The calibration working conditions of the instrument should be the same as the detection conditions. The specified repeatability should not be greater than ±3%; c) Connect the gas inlet of the gas source to be tested and the sampling port of the chromatograph, and control the flow of the gas to be tested according to the conditions of use of the chromatograph Flush the sampling pipeline and the loop for no less than 3 minutes, close the sampling port of the chromatograph, switch the loop valve, and quickly Sample injection d) Record the peak area (or peak height) of each component and analyze the data; e) After the test is completed, turn off the chromatograph according to the instrument operation procedure, and turn off the power and all gas sources. 5.2.5 Sample chromatogram Typical chromatograms are shown in Figure 2 and Figure 3. 5.2.6.2 Calculating gas mixture ratio by external standard method According to the peak area (or peak height) of each component, calculate the SF6, CF4, N2, O2 in the mixed gas according to formula (3) Etc. content 5.2.7 Precision The absolute deviation of the two test results is SF6, N2, CF4≤0.5%, O2≤0.05%.


Refund Policy     Privacy Policy     Terms of Service     Shipping Policy     Contact Information