Safety technical specifications for using flammable refrigerants in household and similar room air conditioner industry
| Valid |
Standards related to (historical): QB/T 4975-2016
Preview PDF (Powered by Google. Reload if blank, scroll for next page)
QB/T 4975-2016: PDF in English (QBT 4975-2016) QB/T 4975-2016
QB
LIGHT INDUSTRY STANDARD
OF THE PEOPLE’S REPUBLIC OF CHINA
ICS 97.030
Classification number. Y61
Registration number. 56431-2016
Safety technical specifications for
using flammable refrigerants in household
and similar room air conditioner industry
ISSUED ON. OCTOBER 22, 2016
IMPLEMENTED ON. APRIL 01, 2017
Issued by. Ministry of Industry and Information Technology of PRC
3. No action is required - Full-copy of this standard will be automatically &
immediately delivered to your EMAIL address in 0~60 minutes.
Table of Contents
Foreword ... 3
1 Scope ... 4
2 Normative references ... 4
3 Terms and definitions ... 5
4 Dangerous area classification ... 6
5 General requirements of ventilation system ... 7
6 General requirements of gas detection and alarming system... 9
7 General requirements of grounding system ... 11
8 Refrigerant storage ... 11
9 Filling ... 15
10 Sealing ... 17
11 Detection of refrigerant leakage ... 18
12 Product operation test room ... 19
13 Repair ... 20
14 Finished product storage ... 20
15 Plant ... 21
16 Safety management ... 21
Appendix A (Normative) Ventilation volume calculation of the ventilation
system ... 25
Appendix B (Informative) Maximum allowable temperature of key refrigerant26
Appendix C (Informative) Emergency measures ... 27
Foreword
This standard was drafted in accordance with the rules of GB/T 1.1-2009.
This standard was proposed by the Federation of Light Industry.
This standard shall be under the jurisdiction of the National Household
Electrical Appliances Standardization Technical Committee (SAC/TC 46).
The drafting organizations of this standard. China Household Electrical
Appliances Association, Zhuhai Gree Electric Co., Ltd., Guangdong Media
Refrigeration Equipment Co., Ltd., Qingdao Haier Air Conditioner Limited
Company, TCL Air Conditioner (Zhongshan) Co., Ltd., Hisense Kelon Electric
Co., Ltd., China Light Industry Changsha Engineering Co., Ltd., Shanghai
Schenck Machinery Co., Ltd., Ulvac Eastern Vacuum (Chengdu) Co., Ltd.,
Ministry of Public Security Tianjin Fire Research Institute, Huazhong University
of Science and Technology, Ningbo Oaks Air Conditioning Co., Ltd.
The main drafters of this standard. Wang Lei, Dou Yanwei, Xu Chen, Zheng
Chongkai, Liu Weiwu, Zhuang Huawu, Ma Honglu, Wang Rui, Zhang Guo,
Zhang Wang, Li Tingxun, Han Peng, Liu Chang, Tan Chengbin, He Guogeng,
Bai Wei.
This standard is the first release.
Safety technical specifications for
using flammable refrigerants in household
and similar room air conditioner industry
1 Scope
This standard specifies the safety technical requirements, operation
procedures, and safety management for using flammable refrigerants in
household and similar room air conditioner industry.
This standard applies to the production line design, production, transform, daily
production and management of room air-conditioner products as defined in
GB/T 7725, the mobile air-conditioners as defined in GB/T 22257 AND the
dehumidifier as defined in GB/T 19411.
2 Normative references
The following documents are essential to the application of this document. For
the dated documents, only the versions with the dates indicated are applicable
to this document; for the undated documents, only the latest version (including
all the amendments) are applicable to this Standard.
GB 150 Pressure vessels (all parts)
GB 3836.1 Explosive atmospheres - Part 1. Equipment - General
requirements
GB 4208 Degrees of protection provided by enclosure (IP code)
GB 4706.32 Safety of household and similar electrical appliances -
Particular requirements for heat pumps, air-conditioner and dehumidifier
GB/T 7725 Room air conditioners
GB/T 7778 Number designation and safety classification of refrigerants
GB/T 8163-2008 Seamless steel tubes for liquid service
GB/T 19411 Dehumidifiers
GB/T 22257 General specification for mobile air conditioner
GB 50016 Code for design on building fire protection and prevention
GB 50058 Code for design of electrical installations in explosive
atmospheres
GB 50140 Code for design of extinguisher distribution in buildings
GB 50184 Code for acceptance of construction quality of industrial metallic
piping engineering
GB 50235 Code for construction of industrial metallic piping engineering
GB 50243-2002 Code of acceptance of construction quality of ventilation
and air conditioning
GB 50257 Code for construction and acceptance of electric equipment on
fire and explosion hazard electric equipment installation engineering
JT 617-2004 The regulation of automobile transportation of dangerous
goods
TSG R 7001-2013 Pressure vessels periodical inspection regulation
3 Terms and definitions
The terms and definitions as defined in GB/T 7725 and GB 4706.32 AND the
following terms and definitions apply to this document.
3.1
Flammable refrigerant
The refrigerant classified into type A2 and A3 in accordance with GB/T
7778.
3.2
Lower explosive limit, LEL
Under the temperature of 23 °C and the atmospheric pressure of 101325
Pa, the minimum concentration of the flammable gas when its mixture with
air can produce explosion in encountering fire source.
3.3
Mechanical ventilation
5.2.1 The ventilation equipment shall comply with the relevant requirements of
GB 3836.1 AND shall have the explosion-proof certificate.
5.2.2 The fan shall be of single set double speed exhaust fan or double set
single speed exhaust fan, AND the single speed exhaust fan must be one in
use and one for standby.
5.2.3 The ventilation pipeline shall be of metallic pipeline, AND after installation,
the test air leakage rate for 10% testing of all air pipeline shall reach to the
requirements of GB 50243-2002.
5.2.4 The ventilation system shall follow the principles of “fresh air incoming
from top and exhaust air from bottom”, the vent hole shall be as close to the
floor and the possible leakage point as possible, AND the height from the lower
edge of the vent hole to the floor shall not exceed 100 mm. The envelope room
and the relatively enclosed room shall be equipped with the fresh air inlet at the
upper part; AND if the inlet is within the workshop of dangerous area, the inlet
shall be higher above the dangerous area for more than 1.5 m.
5.2.5 The air duct shall be beyond the roof for 1 m ~ 2 m, AND it shall install
the lightning protection device as specified AND connect it to the lightning
protection network of the building.
5.2.6 The ventilation system shall be equipped with air pressure or air flow
switches; it shall not be able to start the relevant equipment when the
ventilation system does not run; AND when the ventilation system fails during
production, it shall issue alarm and cut off the relevant power supplies AND
stop the running of relevant equipment after time delay.
5.2.7 The branch pipe of air duct and each vent hole shall be installed with the
air volume regulator valve, AND clearly indicated of the valve switch.
5.2.8 All the flange connections of all air ducts shall be connected to a
grounding line of cross sectional area not less than 6 mm2, by the copper
screw or stainless-steel material, the grounding branch line shall be kept
continuous, AND the grounding line junction shall use copper busbar, with the
grounding resistance of not more than 10 Ω.
5.2.9 The refrigerant room, supply pump room, filling area, sealing area,
leakage testing area, repair area, inspection room, and laboratory shall be
equipped with reliable ventilation system, each ventilation system shall be
independent from each other, AND the ventilation system shall be at working
state for 24 h.
room, filler, sealing area, repair area, inspection room, and laboratory, etc., it
shall install the flammable gas detector.
6.1.3 The height from the bottom of the flammable gas detector to the floor
shall not be more than 200 mm. AND the detector installed in dangerous area
shall have corresponding explosionproof level.
6.1.4 The flammable gas detector shall, before being put into use, be
subjected to configuration inspection, test and calibration. AND it shall be
calibrated at least once a year after being put into use, AND it shall be checked
based on actual c...