GB/T 34130.1-2017 PDF in English
GB/T 34130.1-2017 (GB/T34130.1-2017, GBT 34130.1-2017, GBT34130.1-2017)
Standard ID | Contents [version] | USD | STEP2 | [PDF] delivered in | Name of Chinese Standard | Status |
GB/T 34130.1-2017 | English | 430 |
Add to Cart
|
0-9 seconds. Auto-delivery.
|
Power-track systems -- Part 1: General requirements
| Valid |
Standards related to (historical): GB/T 34130.1-2017
PDF Preview
GB/T 34130.1-2017: PDF in English (GBT 34130.1-2017) GB/T 34130.1-2017
GB
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
ICS 29.120.10
K 30
Powertrack systems - Part 1. General requirements
(IEC 61534-1.2014, MOD)
ISSUED ON. JULY 31, 2017
IMPLEMENTED ON. FEBRUARY 01, 2018
Issued by. General Administration of Quality Supervision, Inspection and
Quarantine of the PRC;
Standardization Administration of the PRC.
Table of Contents
Foreword ... 5
Introduction ... 8
1 Scope ... 9
2 Normative references ... 9
3 Terms and definitions ... 11
4 General requirements ... 19
5 General notes on tests ... 19
6 Ratings ... 20
7 Classification ... 20
8 Marking and documentation ... 22
9 Construction ... 25
10 Clearances, creepage distances and solid insulation ... 29
11 Protection against electric shock ... 34
12 Terminals and terminations ... 36
13 Screws, current carrying parts and connections ... 39
14 Mechanical strength ... 42
15 Insulation resistance and dielectric strength ... 44
16 Normal operation ... 47
17 Temperature rise ... 48
18 Short-circuit protection and short-circuit withstand strength ... 51
19 Resistance to heat ... 57
20 Fire hazard ... 58
21 External influences ... 60
22 Electromagnetic compatibility ... 62
Annex A (Normative) Measurement of clearances and creepage distances .. 67
Annex B (Normative) Proof tracking test ... 73
Annex C (Normative) Relationship between rated impulse withstand voltage,
rated voltage and overvoltage category III ... 74
Annex D (Normative) Pollution degree ... 75
Annex E (Informative) Diagram for the dimensioning of clearances and
creepage distances ... 76
Annex F (Normative) Impulse voltage test ... 78
Annex G (Normative) Routine test ... 79
Bibliography ... 80
Figure 1 -- Pull apparatus for testing the cord anchorage ... 62
Figure 2 -- Torque apparatus for testing the cord anchorage ... 63
Figure 3 -- Arrangement for flame test ... 64
Figure 4 -- Enclosure for flame test ... 65
Figure 5 -- Static load test for a length of the PT system ... 65
Figure 6 -- Static load test for a joint ... 65
Figure 7 -- Short-circuit test arrangement ... 66
Figure E.1 -- Diagram for the dimensioning of clearances ... 76
Figure E.2 -- Diagram for the dimensioning of creepage distances ... 77
Table 1 -- Order of tests ... 20
Table 2 -- Pull and torque values for tests on cord anchorages ... 28
Table 3 -- Minimum clearances for basic insulation ... 31
Table 4 -- Minimum creepage distances for basic insulation ... 33
Table 5 -- Minimum connecting capacity of terminals ... 37
Table 6 -- Torque values for screws ... 40
Table 7 -- Minimum insulation resistance ... 46
Table 8 -- Dielectric strength ... 47
Table 9 -- Temperature rise values ... 49
Table 10 -- Cross-sectional areas of rigid test conductors (solid or stranded) 50
Table 11 -- Cross-sectional areas of flexible test conductors ... 50
Table 12 -- Standard values for the factor n ... 52
Table 13 -- Test temperatures for the glow wire test ... 59
Table A.1 -- Minimum values of width X ... 67
Table C.1 -- Rated impulse withstand voltage for PT systems energized directly
from the low voltage mains ... 74
Table F.1 -- Test voltages for verifying clearances at sea level ... 78
Foreword
GB/T 34130 “Powertrack systems” is divided into the following parts.
- Part 1. General requirements
- Part 21. Particular requirements for powertrack systems intended for wall
and ceiling mounting
- Part 22. Particular requirements for powertrack systems intended for on
floor or under floor installation
This Part is Part 1 of GB/T 34130.
This Part is drafted in accordance with the rules given in GB/T 1.1-2009.
This Part uses redraft law to modify and adopt IEC 61534-1.2014 “Powertrack
systems - Part 1. General requirements”.
The technical differences between this Part and IEC 61534-1.2014 and their
reasons are as follows.
- About normative references, this Part has made adjustments with technical
differences, to adapt to the technical conditions of China. The adjustments
are reflected in Clause 2 “Normative references”, as follows.
USE GB/T 156 Standard voltage (GB/T 156-2007, IEC 60038.2002,
MOD) to replace IEC 60038.2009;
USE GB/T 2099.1 Plugs and socket-outlets for household and similar
purposes - Part 1. General requirements (GB/T 2099.1-2008, IEC
60884-1.2006, MOD) to replace IEC 60884-1.2002+A1.2006;
USE GB/T 2423.18-2012 Environmental testing - Part 2. Test methods
- Test Kb. Salt mist, cyclic (sodium chloride solution) (IEC 60068-2-
52.1996, IDT) to replace IEC 60068-2-52;
USE GB/T 2423.55 Environmental testing for electric and electronic
products - Part 2. Test methods - Test Eh. hammer tests (GB/T
2423.55-2006, IEC 60068-2-75.1997, IDT) to replace IEC 60068-2-75;
USE GB/T 4207-2012 Method for the determination of the proof and
the comparative tracking indices of solid insulating materials (IEC
60112.2009, IDT) to replace IEC 60112.2003;
USE GB/T 4208-2008 Degrees of protection provided by enclosure
(IP code) (IEC 60529.2001, IDT) to replace IEC 60529.1989;
USE GB/T 5169.14 Fire hazard testing for electric and electronic
products - Part 14. Test flames - 1 kW nominal pre-mixed flame -
Apparatus confirmatory test arrangement and guidance (GB/T
5169.14-2007, IEC 60695-11-2.2003, IDT) to replace IEC 60695-11-
2.2003;
USE GB/T 5465 (all parts) Graphical symbols for use on electrical
equipment [IEC 60417 (all parts)] to replace IEC 60417;
USE GB/T 9364.1 Miniature fuses - Part 1. Definitions for miniature
fuses and general requirement for miniature fuse-links (GB/T 9364.1-
2015, IEC 60127-1.2006, MOD) to replace IEC 60127-1.2006;
USE GB/T 9797 Metallic coatings - Electroplated coatings of nickel
plus chromium and of copper plus nickel plus chromium (GB/T 9797-
2005, ISO 1456.2003, IDT) to replace ISO 1456.2009;
USE GB/T 12599 Metallic coatings - Electroplated coatings of tin -
Specification and test methods (GB/T 12599-2002, ISO 2093.1986,
MOD) to replace ISO 2093.1986;
USE GB/T 16927.1 High-voltage test techniques - Part 1. General
definitions and test requirements (GB/T 16927.1-2011, IEC 60060-
1.2006, MOD) to replace IEC 60060-1.2010;
USE GB/T 17196-1997 Connecting devices - Flat quick-connect
terminations for electrical copper conductors - Safety requirements
(IEC 61210.1993, IDT) to replace IEC 61210.2010.
This Part makes the following editorial change.
- DELETE some notes in IEC 61534-1.2014 which apply to other countries
and regions, such as notes of 9.5 and 12.2.
This Part was proposed by China Electrical Equipment Industry Association.
This Part shall be under the jurisdiction of National Technical Committee 67 on
Electrical Accessories of Standardization Administration of China (SAC/TC 67).
Drafting organizations of this Part. China National Electric Apparatus Research
Institute Co., Ltd., Feidiao Electrical Appliances Group Co., Ltd., Guangdong
Inspection and Quarantine Technology Center of Guangdong Entry-Exit
Inspection and Quarantine Bureau, Vkan Certification & Testing Co., Ltd.,
Powertrack systems - Part 1. General requirements
1 Scope
1.1 This Part of GB/T 34130 specifies general requirements and tests for
powertrack (PT) systems.
This Part applies to powertrack (PT) systems with a rated voltage not exceeding
277 V a.c. single phase, or 480 V a.c. two or three phase 50 Hz or 60 Hz with
a rated current not exceeding 63 A. These systems are used for distributing
electricity in household, commercial, or industrial premises.
1.2 Powertrack systems, according to this Part, are intended for use under the
following conditions.
- an ambient temperature in the range -5 °C~+40 °C, the average value over
a 24 h period not exceeding 35 °C;
- a situation not subject to a source of heat likely to raise temperatures above
the limits specified above;
- an altitude not exceeding 2000 m above sea level;
- an atmosphere not subject to excessive pollution by smoke, chemical
fumes, prolonged periods of high humidity or other abnormal conditions.
In locations where special conditions prevail, as in ships, vehicles and the like
and in hazardous locations, for instance, where explosions are liable to occur,
special constructions may be necessary.
This Part does not apply to.
- cable trunking systems and cable ducting systems covered by GB/T 19215;
- busbar trunking systems covered by GB 7251.2;
- electrical supply track systems for luminaires covered by GB/T 13961.
2 Normative references
The following documents are indispensable for the application of this document.
For the dated references, only the editions with the dates indicated are
applicable to this document. For the undated references, the latest edition
(including all the amendments) are applicable to this document.
GB/T 156 Standard voltage (GB/T 156-2007, IEC 60038.2002, MOD)
GB/T 2099.1 Plugs and socket-outlets for household and similar purposes -
Part 1. General requirements (GB/T 2099.1-2008, IEC 60884-1.2006, MOD)
GB/T 2423.18-2012 Environmental testing - Part 2. Test methods - Test Kb.
Salt mist, cyclic (sodium chloride solution) (IEC 60068-2-52.1996, IDT)
GB/T 2423.55 Environmental testing for electric and electronic products -
Part 2. Test methods - Test Eh. hammer tests (GB/T 2423.55-2006, IEC
60068-2-75.1997, IDT)
GB/T 4207-2012 Method for the determination of the proof and the
comparative tracking indices of solid insulating materials (IEC 60112.2009,
IDT)
GB/T 4208-2008 Degrees of protection provided by enclosure (IP code) (IEC
60529.2001, IDT)
GB/T 5169.11-2006 Fire hazard testing for electric and electronic products -
Part 11. Glowing/hot-wire based test methods - Glow-wire flammability test
method for end-products (IEC 60695-2-11.2000, IDT)
GB/T 5169.14 Fire hazard testing for electric and electronic products - Part
14. Test flames - 1 kW nominal pre-mixed flame - Apparatus confirmatory
test arrangement and guidance (GB/T 5169.14-2007, IEC 60695-11-2.2003,
IDT)
GB/T 5169.21 Fire hazard testing for electric and electronic products - Part
21. Abnormal heat - Ball pressure test (GB/T 5169.21-2006, IEC 60695-10-
2.2003, IDT)
GB/T 5465 (all parts) Graphical symbols for use on electrical equipment [IEC
60417 (all parts)]
GB/T 9364.1 Miniature fuses - Part 1. Definitions for miniature fuses and
general requirement for miniature fuse-links (GB/T 9364.1-2015, IEC 60127-
1.2006, MOD)
GB/T 9797 Metallic coatings - Electroplated coatings of nickel plus chromium
and of copper plus nickel plus chromium (GB/T 9797-2005, ISO 1456.2003,
IDT)
GB/T 9799 Metallic and other inorganic coatings - Electroplated coatings of
zinc with supplementary treatments on iron or steel (GB/T 9799-2011, ISO
2081.2008, IDT)
GB/T 12599 Metallic coatings - Electroplated coatings of tin - Specification
and test methods (GB/T 12599-2002, ISO 2093.1986, MOD)
GB/T 13140.1-2008 Connecting devices for low-voltage circuits for
household and similar purposes - Part l. General requirements (IEC 60998-
1.2002, IDT)
GB/T 13140.4-2008 Connecting devices for low voltage circuits for
household and similar purposes - Part 2. Particular requirements for
connecting devices as separate entities with insulation piercing clamping
units (IEC 60998-2-3.2002, IDT)
GB/T 13539.1 Low-voltage fuses - Part 1. General requirements (GB/T
13539.1-2008, IEC 60269-1.2006, IDT)
GB/T 16842 Protection of persons and equipment by enclosures - Probe for
verification (GB/T 16842-2008 IEC 61032.1997, IDT)
GB/T 16927.1 High-voltage test techniques - Part 1. General definitions and
test requirements (GB/T 16927.1-2011, IEC 60060-1.2006, MOD)
GB/T 17196-1997 Connecting devices - Flat quick-connect terminations for
electrical copper conductors - Safety requirements (IEC 61210.1993, IDT)
GB/T 17464-2012 Connecting devices - Electrical copper conductors -
Safety requirements for screw-type and screwless-type clamping units - Part
1. General requirements and particular requirements for clamping units for
conductors from 0.2 mm2 up to 35 mm2 (included) (IEC 60999-1.1999, IDT)
GB/T 20636 Connecting device - Electrical cooper conductors - Safety
requirements for screw-type and screwless-type clamping units - Particular
requirements for conductors above 35 mm2 up to 300 mm2 (GB/T 20636-
2006, IEC 60999-2.2003, IDT)
3 Terms and definitions
The following terms and definitions apply to this document.
3.1 Powertrack system; PT system