HOME   Cart(0)   Quotation   About-Us Tax PDFs Standard-List Powered by Google www.ChineseStandard.net Database: 189760 (5 Oct 2024)

GB/T 2625-1981 PDF in English


GB/T 2625-1981 (GB/T2625-1981, GBT 2625-1981, GBT2625-1981)
Standard IDContents [version]USDSTEP2[PDF] delivered inName of Chinese StandardStatus
GB/T 2625-1981English150 Add to Cart 0-9 seconds. Auto-delivery. Process detection and controlflow chart. Symbols and letter codes  
Standards related to (historical): GB/T 2625-1981
PDF Preview

GB/T 2625-1981: PDF in English (GBT 2625-1981)

GB 2625-1981 (GB/T 2625-1981) NATIONAL STANDARD OF THE PEOPLE’S REPUBLIC OF CHINA GB 2625-81 Process Detection and Control Flow Chart Symbols and Letter Codes ISSUED ON: APRIL 1, 1981 IMPLEMENTED ON: MARCH 1, 1982 Issued by: National Bureau of Standards Table of Contents 1. Introduction ... 4 2. Definitions ... 4 3. Symbols ... 6 4 Letter Codes ... 16 Appendix 1 ... 25 Appendix 2 ... 55 Process Detection and Control Flow Chart Symbols and Letter Codes 1. Introduction 1.1 This standard is applicable to chemical industry, petroleum industry, metallurgical industry, electricity industry, light industry, textile industry, building materials industry and other industries. It aims at specifying unified representation method for the instrument devices used in process detection and control flow chart. The symbols and letter codes specified in this standard may also be used in other design and technical documents. 1.2 The mark of instrument device is composed of symbols and letter codes. 1.3 All departments may put forward supplementary provisions under the condition that requirements of this standard are not violated. 2. Definitions For the purposes of this standard, the following definitions apply. 2.1 Process It refers to any operation or a series of operations that can change energy status, composition, dimension or other characteristics defined by the data available. 2.2 Function It refers to the purpose and actions achieved by instruments. 2.3 Loop It refers to the combination of one or more relevant instruments used for measuring and (or) controlling process variables. 2.4 Ballon It refers to the circular symbol used to indicate instrument or instrument mark. 2.5 Point of measurement It refers to the point at which process variable may be measured. 2.6 Test point It refers to the test joint to which instruments are not permanently connected and it is used for connecting instruments temporarily, intermittently or in future. 2.7 Detecting element, sensor, primary element It refers to the element responding to the value of measured variable directly and converting measured variable to the form suitable for measurement. 2.8 Transmitter It refers to the instrument which receives measured variable with the help of ○3 The significance expressed by the subsequent letters may be noun, verb or adjective. For example, "1" may be indicator, indication or indicated and "T" may be transmitter, transmission or transmitting. ○4 One of the modifier letters of the first letter "d" (difference),"f" (ratio) , "q" (integral, accumulation) constitutes another significance of measured variable by combining with the letter of measured variable (or initial variable), thus it shall be considered as one letter. For example: TdI and TI respectively are temperature difference indication and temperature indication. Modification letter shall be lowercase. It may also be capital when there is no confusion. ○5 The first letter "A" (analysis) includes the analysis items not specified in Table 13. When it is necessary to indicate the specific analysis items, "A" is still written in ballon and the analysis items are written in the upward side outside the circle. For example, "H2" shall be written in the upward side outside the circle and "A" in circle is unable to be superseded by "H2" ○6 The first letter "U" (multivariable) is used to supersede multiple letters expressing measured variable (or initial variable), namely "U" is used to express multivariable. ○7 Subsequent letter "U" (multifunction) is used to supersede multiple letters expressing function, namely "U" is used to express multifunction. ○8 "I" (indication) is only applicable to the reading of actual measurement. It is not applicable to the ruler without the measured quantity input and only for the manual regulating variable. ○9 See definition (2.18 and 2.1) for the difference between L (light) and A (alarm). If the light is a part of the circuit, then L shall be used by combining with the first letter. For example, the pilot light of instruction time cycle shall be KL. If the light is not a part of the circuit, "L" may be marked individually, and it may also be combined with the first letter of one selected measured variable in accordance with above-mentioned method. For example, the running light of electromotor may be assumed that the voltage is its measured variable and marked as EL; or it is assumed as triggered by the auxiliary electrical contacts of motor starter and marked as XL. ○10 The subsequent letters C (control), S (switch), V (valve) and Y (relay) shall be correctly differed and selected. Switch, relay, step-type controller and control valve are able to connect, disconnect or convert one or more lines. Control valve is used to control process fluid. Switch, relay, and step-type controller shall not be used to connect, disconnect or convert the fluid line. Switch (S) is manually operated. Automatic and the first device in the circuit is switch (S) or step-type controller and switch (S) is generally used for alarm pilot light, selection, interlocking or safety; but step-type controller (C) is generally used for normal operation control. Automatic but not the first such device in the circuit (for example, operated by switch or step-type controller) is relay (Y). Relay includes computing instrument, signal converter, selector and amplifier etc. (see definition 2.9). ○11 The subsequent letter shall be written in accordance with the following sequence: I R C T Q S A ○12 When the instrument is equipped with indication and recording functions at the same time, R (record) is the only one letter code to be written and I (indication) needs not to be written out. S refers to switch or interlocking. SA specially refers to interlocking plus alarm in one ballon; if alarm is triggered by switch, then S may be omitted and only A is written. 4.2.2 See Appendix B for various common combination of letter codes. 4.2.3 The first letter expressing measured variable (or initial variable) must be the starting of letter code (the only exception is the "L" described in the Note (9) in Table 13 of 4.2.1) and one or more subsequent letters expressing function are followed. 4.2.4 The first letter is determined in accordance with measured variable (or initial variable) but not the instrument structure. For example, differential pressure recorder used for measuring discharge shall be written as FR but not PdR. 4.2.5 Subsequent letter expressing function is selected in accordance with read or output function but not the handled variable. For example, the control valve accepting the signal from liquid level regulator to change flow shall be marked as LV but not FV. 4.3 Writing rule of instrument location number 4.3.1 In ballon, the writing method of instrument location number is: letter code shall be written in the upside of circle and serial number and suffix shall be written in the downside of circle, as shown in Figure 9. Local instrument Board-mounted instrument Figure 9 4.3.2 Area number and loop number in serial number generally start form 1 and are compiled in sequence but vacant number is allowed in the middle. 4.3.3 If two or multiple circuits share an instrument, then this instrument shall be provided with the respective location number belonging to each circuit. 4.3.4 Instrument shall compile the serial number in accordance with measured variable (or initial variable), namely for the instrument of the same measured variable (or initial variable) in the same area, its loop number shall be compiled from 1 in sequence and vacant number is allowed in the middle. For the instrument of different measured variable (or initial variable), the loop number is not continuously specified with putting together. Note: If necessary, for the instrument of different measured variables (or initial variables), the loop number may be unified and continuously compiled. 4.3.5 Measured variable (or initial variable) with the modifiers "d", "f", "q" shall be put together with the measured variable (or initial variable) without modifier to compile serial number and they do not serve as separate measured variable (or initial variable) to compile serial number separately. For example, temperature difference indicator TdI-105 shall be compiled the serial number with temperature indicator TI-106 in accordance with unified sequence. 4.3.6 Only when necessary, modifiers "d", "f" and "q" are added for measuring instruments. For example, there is no need to add the modifier letter "d" expressing temperature difference to detecting elements TE-105A and TE-105B which are connected with TdI. 4.3.7 If there are instruments with more than one same letter codes (i.e., the measured variable or initial variable have same functions), suffix of capital English letters shall be added after the loop number to show the difference. For example, FT-201A and FT-201B can be used to express two flow transmitters in one loop; FV-311A and FV-311B can be used to express two flow control valves in one loop. 4.3.8 When multiple detecting elements in different zones share one instrument (not multi-pen or multi-needle instruments), area No. may be omitted for detecting elements, short dash shall be added after loop number for separation and Arabic numbers may be added as serial numbering to serve as suffix, e.g., TE-25-1, TE-25-2 and TF-25-3. 4.3.9 Instrument location number for instruments with two or more functions shall be given according to their complete functions. For example, for flow recorder FR-2 accompanied with pressure recorder PR-4, FR-2/PR-4 shall be written in the detailed list, UR-7 is also adoptable; double-pen pressure recorder shall be written as PR-7/8. 4.3.10 There is no need to mark instrument accessories in the flow diagram, e.g., rotor flowmeter for flushing, air filtration decompressor etc. When one instrument location number is required, the location No. of its instrument may be adopted, but its name shall be noted. For example, flange components equipped with orifice plate FE-7 may be marked as "FE-flange"; rotor flowmeter for flushing - self-operated control valve group equipped for pressure gauge PI-8 may be marked as "PI -8 flushing". 4.3.11 For simple local indication instruments which are adopted in a large quantity, e.g., pressure gauge, thermometer etc., if necessary, instrument location number may not be prepared as prescribed above, letter code of the measured variable is provided instead, and loop numbers which are arranged in order shall be added after area No. Area No. may also be omitted, e.g., P-301, P-302…for pressure gauge; T-01, T-02…for thermometer, etc. 4.3.12 When it is necessary to express high/medium/low (e.g., high alarm, high-high level interlocking etc.), H (high), L (low), M (medium) or HH (high-high) and LL (low-low) may be written in top right, bottom right and right side middle part outside the ballon. HH or LL indicates that H (high) and HH (high-high) or L (low) and LL (low-low) exist. However, H or L is omitted and only HH or LL is marked in one ballon. H, L, M are corresponding to value of measured variable rather than signal value. For example, for high liquid level alarm provided by reaction liquid level transmitter, H shall be written at top left outside the ballon mark LA, even though the alarm is triggered when the signal drops to a certain low value. H (high) and L (low) may also be used to express the position of valve or other switching devices: H refers to that the valve is located in or inclines to full opening position; L refers to the valve is located in or inclines to full close position. 4.4 Additional symbols and codes of relay. When functions of relay are required to be further expressed, symbols and codes listed in Table 14 may be filled up in top right outside the ballon. ......
 
Source: Above contents are excerpted from the PDF -- translated/reviewed by: www.chinesestandard.net / Wayne Zheng et al.