DL/T 1000.1-2018: PDF in English (DLT 1000.1-2018) DL/T 1000.1-2018
DL
ELECTRICAL INDUSTRY STANDARD
OF THE PEOPLE’S REPUBLIC OF CHINA
ICS 29.240
K 48
Filing No.: 69024-2019
Replacing DL/T 1000.1-2006
Application guide of insulators for overhead lines with a
nominal voltage over 1000V - Part 1: Ceramic or glass
insulators for A.C. system
ISSUED ON: DECEMBER 25, 2018
IMPLEMENTED ON: MAY 01, 2019
Issued by: National Energy Administration
Table of Contents
Foreword ... 3
1 Scope ... 5
2 Normative references ... 5
3 Terms and definitions ... 6
4 General technical requirements ... 6
5 Selection principles ... 9
6 Inspection ... 10
7 Acceptance ... 13
8 On-site storage and transportation ... 14
9 Installation ... 14
10 Operation and maintenance ... 15
Appendix A (Normative) Impact load test ... 16
Application guide of insulators for overhead lines with a
nominal voltage over 1000V - Part 1: Ceramic or glass
insulators for A.C. system
1 Scope
This standard specifies the general technical requirements, selection principles,
inspection, acceptance, on-site storage and transportation, installation and operation
and maintenance of AC overhead line insulators which have a nominal voltage higher
than 1000 V.
This standard applies to disc-shaped suspended porcelain and glass insulators
(hereinafter referred to as insulators) for AC overhead power lines, power plants,
substations, which have a nominal voltage higher than 1000 V and a frequency of 50
Hz. The installation site is below 1000 m above sea level; the ambient temperature is
between -40 °C ~ +40 °C.
2 Normative references
The following documents are essential to the application of this document. For the dated
documents, only the versions with the dates indicated are applicable to this document;
for the undated documents, only the latest version (including all the amendments) is
applicable to this standard.
GB/T 311.1 Insulation coordination - Part 1: Definitions, principles and rules
GB/T 772 High-voltage insulator porcelain parts - Technical conditions
GB/T 1001.1 Insulators for overhead lines with a nominal voltage above 1000V -
Part 1: Ceramic or glass insulator units for a.c. systems - Definitions, test methods
and acceptance criteria
GB/T 2900.5 Electrotechnical terminology - Electrical insulating solids, liquids and
gases
GB/T 2900.8 Electrotechnical terminology - Insulators
GB/T 7253 Insulators for overhead lines with a nominal voltage above 1000 V -
Ceramic or glass insulator units for a.c. systems - Characteristics of insulator units
of the cap and pin type
GB/T 16927.1 High-voltage test techniques - Part 1: General definitions and test
requirements
GB/T 20642 Impulse puncture test in air on insulators for overhead lines
GB/T 24623 Radio interference test on high-voltage insulators
GB/T 25318 Locking devices for ball and socket couplings of string insulator units
- Dimensions and tests
GB/T 26218.1 Selection and dimensioning of high-voltage insulators intended for
use in polluted conditions - Part 1: Definitions, information and general principles
DL/T 626 Testing procedures of degradation of suspension insulator
JB/T 4307 Cement mortar for insulators
JB/T 8177 The hot dip galvanized coating of metallic parts for insulators general
technical specification
JB/T 8178 Technical specification of cap for cap and pin insulators
JB/T 9677 Steel pins of cap and pin insulators
JB/T 9678 Appearance quality of toughened glass insulator bodies for cap and pin
insulators
3 Terms and definitions
The terms and definitions defined in GB/T 2900.5, GB/T 2900.8, GB/T 1001.1 apply
to this document.
4 General technical requirements
4.1 Component characteristics
The characteristics of insulator components shall comply with the provisions of GB/T
7253.
4.2 Insulator
4.2.1 Porcelain components
Porcelain components shall meet the following requirements:
a) The appearance quality of porcelain components shall comply with the provisions
of GB/T 772 and GB/T 1001.1. They shall not have warping, cracks, sand holes,
shrinkage crimping or any other process with more than one piece of material.
g) The iron cap of the insulator shall not touch the upper surface of the insulating
part; the iron cap, insulator, steel foot are on the same axis.
h) The iron cap and steel foot of the insulator, which has a strength level of 160 kN
and above, shall be tested by flaw detection one by one.
4.4 Locking pin
The locking pin shall meet the following requirements:
a) The locking pin shall comply with the provisions of GB/T 25318 and GB/T 1001.1.
b) The locking pin shall be made of stainless steel; the material shall not have an
anti-corrosion surface layer. To prevent leakage, the size of the bent part at the
end of the pin leg shall meet the provisions of GB/T 25318.
c) Insulators with strength levels of 160 kN and above shall use R-type pins. The R-
type pin shall have two separate ends, to prevent it from completely falling out of
the ball socket when it is locked and connected.
d) Special tools shall be used to assemble the locking pin, to avoid damaging the
galvanized layer of the metal accessories.
4.5 Cement adhesive
Cement adhesive shall meet the following requirements:
a) Insulators shall be glued with silicate cement of strength grade 42.5 (R) or above,
or adhesive prepared with specially made high-strength low-expansion aluminate
cement.
b) After the cement adhesive is cured, the iron cap and steel foot of the insulator shall
not be loose.
c) The cement adhesive shall completely fill the gap between the insulating part and
the metal part and eliminate bubbles.
d) The autoclave expansion rate of the cement adhesive shall not exceed 0.10%.
e) The cement adhesive shall not chemically react with metal accessories.
f) The flatness of the exposed surface of the cement adhesive shall not exceed 2 mm,
meanwhile there shall be no cracks or damage.
g) The prepared cement adhesive shall comply with the provisions of JB/T 4307.
The manufacturer shall provide a type test report and a sampling test report, that
the cement adhesive complies with the relevant standards.
Note: The steel foot can be considered as loose, when the horizontal rotation angle is not greater
than 3°.
4.6 Deterioration rate (self-explosion rate) of insulators
If the average annual degradation rate (self-explosion rate) of the insulator from
installation to commissioning exceeds 0.04%, it is necessary to analyze the cause and
take corresponding measures.
The average annual degradation rate (self-explosion rate) of the insulator shall not be
greater than 0.04%, within 2 years after commissioning; the average annual degradation
rate (self-explosion rate) shall not be greater than 0.02% during the inspection cycle
after 2 years, OR the annual degradation rate (self-explosion rate) shall not be greater
than 0.1%.
Note: Experience shows that nickel sulfide homogenization treatment of glass parts is an
effective measure to reduce the self-explosion rate.
5 Selection principles
5.1 General principles
The selected insulators shall have mature technology, advanced process, reliable quality,
operating experience; follow the following principles:
a) Comprehensively consider the purpose of safe, stable, economical, high-quality
power supply of the power grid.
b) The insulator has a type test report provided by a qualified inspection organization.
c) The new product has a successful supply record of not less than 1 year of trial
operation and not less than 2000 trial operation units.
d) The mechanical strength of the insulator shall be compatible with the design and
operation requirements of transmission lines of different voltage levels and shall
be selected in accordance with GB/T 7253.
e) The pollution characteristics of different types of insulators shall be compared
according to the voltage level, operating conditions, use environment; it shall give
priority to the insulators, which have high pollution withstand voltage, excellent
pollution accumulation characteristics, self-cleaning characteristics under unit
structural height.
f) When the insulator is used at an altitude of more than 1000 m, its external
insulation shall be corrected for altitude according to the provisions of GB/T
8 On-site storage and transportation
8.1 On-site storage
On-site storage shall meet the following requirements:
a) The storage site shall be flat and solid; have necessary drainage measures.
b) Different insulators shall be stacked separately; the stacking height of the same
type of insulators shall be appropriate.
c) The packaging status shall be checked regularly; the damaged packaging shall be
repaired or stacked separately.
d) Other engineering materials or construction tools shall not be placed on the
insulators.
8.2 On-site transportation
On-site transportation shall meet the following requirements:
a) Choose a reasonable transportation method based on the site conditions.
b) Avoid opening the packaging as much as possible during transportation; take
necessary measures to alleviate the pressure and impact during transportation.
c) Handle with care during transportation; do not throw or drag.
9 Installation
9.1 Appearance inspection
Before installation, the appearance of the insulators shall be inspected one by one
according to GB/T 1001.1 and this Part. Insulators that do not meet the relevant
requirements are prohibited from use.
9.2 Insulation resistance measurement
Before installing the porcelain insulators, measure the insulation resistance one by one
using an insulation resistance meter of not less than 5000 V. Under dry conditions, the
insulation resistance shall not be less than 500 MΩ. Insulators that fail the inspection
shall not be installed and used. When the number of unqualified in the same batch is
greater than 0.02%, it shall analyze the reasons; carry out dry power frequency
withstanding voltage tests one by one.
9.3 Precautions
Installation precautions include:
a) Be careful to handle with care; do not throw or drag; avoid collision or friction
with hard objects.
b) Take appropriate measures to avoid collision between insulators or between
insulators and iron towers.
c) Use appropriate tools and correct methods to pull the locking pin out to the
connection position or put it back to the locking position; confirm the state of the
locking pin after completing the connection.
d) When replacing insulators, working tools or fixtures shall not act on the gap
between the iron cap opening and the insulating part.
e) Insulators shall not be used as hanging points.
10 Operation and maintenance
10.1 File creation
The operating organization shall establish an insulator file in accordance with the
provisions of DL/T 626.
10.2 Inspection
When inspecting and checking the insulator, if the locking pin is missing or the
insulating part is damaged, it shall be supplemented or replaced in time.
If one of the following situations occurs, the insulator can be determined to be invalid:
a) The iron cap, insulating part, steel foot are not on the same axis.
b) The iron cap, insulating part, steel foot are severely burned or burned by the arc.
c) The iron cap, insulating part, steel foot are cracked, split, or damaged.
d) The steel foot is bent.
e) The cement adhesive at the steel foot is obviously detached.
10.3 Degradation detection
Degradation detection shall be carried out in accordance with the relevant provisions of
DL/T 626.