US$380.00 · In stock · Download in 9 secondsGB/T 13286-2021: Criteria for independence of class 1E equipment and circuits in nuclear power plants Delivery: 9 seconds. True-PDF full-copy in English & invoice will be downloaded + auto-delivered via email. See step-by-step procedureStatus: Valid GB/T 13286: Evolution and historical versions
Standard ID | Contents [version] | USD | STEP2 | [PDF] delivery | Name of Chinese Standard | Status |
GB/T 13286-2021 | English | 380 |
Add to Cart
|
0-9 seconds. Auto-delivery
|
Criteria for independence of class 1E equipment and circuits in nuclear power plants
| Valid |
GB/T 13286-2008 | English | 879 |
Add to Cart
|
4 days
|
Criteria for independence of class 1E equipment and circuits in nuclear power plants
| Obsolete |
GB/T 13286-2001 | English | 759 |
Add to Cart
|
5 days
|
Criteria for independence of class 1E equipment and circuits in nuclear power plants
| Obsolete |
GB/T 13286-1991 | English | 679 |
Add to Cart
|
5 days
|
Criteria for independence of class 1E equipment and circuits in nuclear power plants
| Obsolete |
Excerpted PDFs (Download full copy in 9 seconds upon purchase)PDF Preview: GB/T 13286-2021
GB/T 13286-2021: Criteria for independence of class 1E equipment and circuits in nuclear power plants ---This is an excerpt. Full copy of true-PDF in English version (including equations, symbols, images, flow-chart, tables, and figures etc.), auto-downloaded/delivered in 9 seconds, can be purchased online: https://www.ChineseStandard.net/PDF.aspx/GBT13286-2021
GB
NATIONAL STANDARD OF THE
PEOPLE’S REPUBLIC OF CHINA
ICS 27.120.20
CCS F 83
Replacing GB/T 13286-2008
Criteria for independence of class 1E equipment and circuits
in nuclear power plants
ISSUED ON: DECEMBER 31, 2021
IMPLEMENTED ON: JULY 01, 2022
Issued by: State Administration for Market Regulation;
National Standardization Administration.
Table of Contents
Foreword ... 3
1 Scope ... 4
2 Normative references ... 4
3 Terms and definitions ... 4
4 General principles of independence ... 8
5 Physical separation criteria ... 14
6 Electrical isolation criteria ... 29
Appendix A (Informative) Isolation of fiber optic circuits ... 34
References ... 36
Criteria for independence of class 1E equipment and circuits
in nuclear power plants
1 Scope
This document specifies the independence criteria for physical separation and electrical
isolation of safety-class electrical equipment and circuits.
This document applies to the safety class of nuclear power plants and their related
electrical equipment and circuits.
This document does not apply to the determination of redundant equipment and circuits.
2 Normative references
The contents of the following documents constitute essential clauses of this document
through normative references in the text. Among them, for dated references, only the
version corresponding to that date applies to this document; for undated references, the
latest version (including all amendments) applies to this document.
GB/T 5204 Periodic surveillance testing of the safety system of nuclear power plant
GB 8624 Classification for burning behavior of building materials and products
GB/T 12790 Method for identification of documents related to safety class 1E
equipment and systems for nuclear power plants
GB 50016 Code for fire protection design of buildings
NB/T 20070 Criteria for design, installation, and qualification of raceway systems
for class 1E circuits in nuclear power plants
NB/T 20213 Qualification procedure of safety-related electric cables and field
splices for nuclear power plants
3 Terms and definitions
The following terms and definitions apply to this document.
3.1
The independence of safety-class electrical equipment and circuits shall not be
compromised by the functional failure of auxiliary supporting features. For example,
auxiliary supporting features (such as ventilation devices in safety-class switchgear
rooms) shall be specified as belonging to the same division as the safety-class electrical
system they support, to prevent the failure of a mechanical function in one division
from causing the failure of an electrical function in another division.
4.5 Associated circuits
4.5.1 General
In addition to the exceptions mentioned in 4.6c), d), e), non-safety-class power supplies,
control, instrumentation circuits may become associated circuits due to one or more of
the following situations:
a) Electrically connected to the safety-class power supply without using an isolation
device (see Figure 1);
b) Electrically connected to the related power supply without using an isolation
device (see Figure 1);
c) Close to safety-class equipment and circuits without a physical separation or
barrier that meets the requirements (see Figure 2);
d) Close to related equipment and circuits without a physical separation or barrier
that meets the requirements (see Figure 2);
e) Sharing a safety-class or related signal source without using an isolation device
(see Figures 3 and 8).
4.5.2 Guidelines
Associated circuits shall meet one of the following requirements.
a) They shall be marked according to the requirements of the associated circuit or
safety class and can be traced back to the safety class division related to them,
that is, they shall be physically separated in the same way as the safety class
circuits related to them. Unless it is proved by analysis or test that it will not cause
the performance of the safety class circuit to be reduced to an unacceptable level,
they shall meet the requirements of the safety class circuit.
b) All associated circuits, including safety class equipment and isolation devices,
shall comply with the requirements of 4.5.2a). If the circuit behind the isolation
device is no longer related to the safety class system, it is not necessary to comply
with the requirements of this document.
c) It shall be proved by analysis or test that these associated circuits will not cause
2) Through analysis, it is proved that the non-safety circuit will not cause the
performance of the safety circuit to be degraded to an unacceptable level. The
analysis shall evaluate the category of the non-safety circuit and its possible
energy.
e) Non-safety fiber optic loops do not need to be physically isolated from safety
circuits or associated circuits. Electrical isolation is an inherent characteristic of
fiber optic loops. Because fiber optic loops do not cause the safety circuit to
degrade, they can be treated as non-safety circuits rather than associated circuits.
4.7 Mechanical system
Safety-class circuits shall be laid or protected in a manner that prevents failure of a
division of mechanical equipment from causing failure of safety-class circuits or
equipment necessary for redundant systems or equipment to perform their safety
functions. When safety-class equipment or circuits are used to mitigate the
consequences of a mechanical system failure or misoperation, the impact of these
failures or mis-operations on the division itself shall be evaluated. At the same time, the
impact of pipe swing, jet impact, water spray, flooding, radiation, pressurization,
temperature rise or moisture on redundant electrical systems, as caused by mechanical
system failure, misoperation or operation, shall be evaluated. In addition, the potential
hazards of flying objects caused by rotating equipment or high-energy system failures
shall also be evaluated.
4.8 Structures and equipment
Safety-class electrical systems shall maintain their independence and redundancy
during and after the failure of structures and equipment that have not been identified
for design basis events.
4.9 Fire protection system
When redundant division equipment and circuits are arranged within the range of the
same fixed fire protection system, the design of these equipment and circuits shall be
coordinated with the fire protection system, so that the independence of the safety-class
electrical system is not impaired; the impact of false operation of the fire protection
system on equipment rooms and cable channels shall be evaluated.
4.10 Fire
4.10.1 An electrical fire occurring within a safety class division shall not cause the loss
of function of its redundant division.
4.10.2 Redundant safety class equipment and circuits shall maintain independence; a
fire in a fire hazardous area shall not prevent its redundant equipment and circuits from
performing safety functions.
4.11 Electromagnetic interference/Radio frequency interference
The possibility of electromagnetic interference/radio frequency interference affecting
the independence of redundant safety class equipment and circuits shall be evaluated.
Corrective measures to mitigate electromagnetic interference/radio frequency
interference interactions may include the following: grounding, use of low-voltage
components, physical separation, isolation devices, shielding of susceptible equipment
or circuits, shielding of electromagnetic interference sources, etc., see Appendix B of
GB/T 13284.1-2008.
The following interactions of EMI/RFI shall be evaluated:
a) EMI/RFI generated by a safety class division shall not reduce the ability of
redundant safety class equipment or circuits to perform safety functions;
b) EMI/RFI generated outside the safety class circuit (such as non-safety class
circuits and equipment, broadcasting, telephone) shall not reduce the ability of
safety class equipment and circuits to perform safety functions.
5 Physical separation criteria
5.1 Cable and wiring channels
5.1.1 General
5.1.1.1 Grading of areas
The cable laying and equipment areas of the safety class and its associated circuits shall
be reviewed, to find out whether there are potential hazards such as high-energy
pipelines, flying objects, flammable materials, ignition sources and flooding. These
areas shall be divided as follows:
a) Non-hazardous areas (see 5.1.3);
b) Low-hazard areas (see 5.1.4);
c) Hazardous areas (see 5.1.5).
In the early stages of design, a separation equivalent to the degree of potential hazardous
damage shall be provided through separate rooms, barriers and other facilities. If there
is sufficient heat dissipation capacity, the sides of the room or area can also be used as
a partition.
5.1.1.2 Minimum separation distance
5.1.1.2.1 Subject to the following criteria, the minimum separation distances specified
in 5.1.3 ~ 5.1.5 and 5.1.9 can be used to obtain a physical separation that meets the
the consequences (such as spraying devices) shall be evaluated.
5.1.2 Marking
Exposed safety-class and associated circuit cable wiring channels shall be permanently
marked at the entrances and exits of the enclosed area and at intervals of no more than
5 m on the channel. The marking shall be set before the cable is installed. Cables laid
in the wiring channel shall be permanently marked at intervals of no more than 3 m, so
that it can be verified from the beginning whether their laying meets the separation
criteria. The marking shall be set before or during the cable laying.
Cables of safety class and associated circuits shall be permanently marked at each end
in accordance with the requirements of the design drawings or cable lists.
To meet the above requirements, the marking method adopted shall be able to easily
distinguish between redundant safety class divisions, safety class and non-safety class
divisions, associated cables of different redundant safety class divisions. If no
separation is required between optical fiber loops, a single method can be used for
identification.
5.1.3 Non-hazardous area
5.1.3.1 Area requirements
The basis for determining the minimum separation distance applicable to this area is
limited to internal faults of electrical equipment and cables.
The area that meets the following requirements is defined as a non-hazardous area:
a) There are no high-energy equipment (such as switchgear, transformers, rotating
equipment) in this area, nor are there any potential hazards such as missiles,
pipeline damage or fire;
b) The circuits in this area shall be limited to instrumentation and control functions,
as well as power equipment and cables that only serve the equipment in this area;
c) The power cables in this area shall be installed in closed wiring channels;
d) The introduction of potential hazards shall be limited and controlled through
administrative measures for operation and maintenance activities.
5.1.3.2 Boundary of non-hazardous areas
The boundary of non-hazardous areas meets the following requirements:
a) The area shall be separated from other adjacent areas by a fire barrier, which shall
have a fire resistance equivalent to the possible fire hazard, or shall have a fire
resistance rating of 3 h;
In the hazardous area, comprehensive measures such as restrictions on cable laying or
special physical separation shall be adopted according to the requirements of 5.1.6 ~
5.1.8, to keep the independence of the redundant division of the safety class system
within an acceptable level.
The minimum distance between the non-safety class and the safety class or associated
circuits shall meet the requirements of 5.1.4.
5.1.6 Pipeline damage hazardous area
5.1.6.1 Area requirements
If there are pipelines operating normally at high or medium energy in a certain area, the
area shall be defined as a pipeline damage dangerous area.
For medium energy pipelines, it is not necessary to consider pipeline swing and jet
impact, but the impact on the surrounding area and the environment shall be evaluated.
5.1.6.2 Area boundary
Barriers, constraints, separation distances or appropriate combinations thereof shall be
used to protect non-hazardous areas and low-hazardous areas from the hazards of
pipeline damage hazardous areas.
5.1.6.3 Laying requirements
In the pipeline damage hazardous area, it shall be possible to prove that the pipeline
damage does not affect the ability of the safety-class equipment and circuits to perform
their safety functions. Otherwise, the laying of cables or wiring channels for safety-
class or associated circuits shall meet the following requirements.
a) If the relevant pipeline does not belong to a single division and has been qualified
by the design basis event, meanwhile no protective action is required for the
impact caused by its damage, the cables or wiring channels for the safety-class or
associated circuits laid in the area shall be limited to a single division.
b) If protective action is required for the impact caused by the damage to the pipeline,
except for the cables that shall be terminated to the devices or loads in the area
[special measures (such as increasing redundancy or diversity) may be required
for these cables to meet the single failure criterion], cables or wiring channels for
other safety-class or associated circuits shall not be laid in the area.
c) If the relevant pipeline belongs to a single division and has been qualified by the
design basis event, meanwhile no protective action is required for the impact
caused by its damage, the cables or wiring channels for the safety-class or
associated circuits laid in the area shall be limited to the same division as the
pipeline.
d) If the relevant pipeline has not been identified for design basis events, cables or
wiring channels of other safety-class or associated circuits shall not be laid in the
area, except for cables that shall be terminated to devices or loads in the area.
When the area where safety-class or associated circuits or wiring channels are
laid is designated as a hazardous area due to the presence of pipelines that have
not been identified for design basis events, these cables or wiring channels shall
be protected in accordance with the methods specified in 5.1.6.2, to avoid the
impact of the area; otherwise, the relevant pipeline shall be qualified after design
basis event identification.
5.1.7 Missile hazardous area
5.1.7.1 Area requirements
If there is a missile source with sufficient kinetic energy in a certain area under design
basis event conditions, which will damage the safety-class redundant circuits separated
according to the requirements of 5.1.4 and laid in the area, then the area shall be
designated as a missile hazardous area.
5.1.7.2 Area boundary
Barriers, orientation, separation distance or appropriate combination thereof shall be
adopted to protect non-hazardous areas and low-hazard areas from the hazards of
missile hazard areas.
5.1.7.3 Laying requirements
The cables or wiring channels for safety-class or associated circuits laid in this area
shall meet the following requirements.
a) If the relevant missile source does not belong to a single division and has been
qualified by the design basis event, meanwhile no protective action is required
for the impact caused by its damage, the cables or wiring channels for safety-class
or associated circuits laid in this area shall be limited to a single division.
b) If protective action is required for the impact caused by the missile source, except
for the cables that shall be terminated to the devices or loads in this area [special
measures (such as increasing redundancy or diversity) may be required for these
cables to meet the single failure criterion], cables or wiring channels for other
safety-class or associated circuits shall not be laid in this area.
c) If the relevant missile source belongs to a single division and has been qualified
by the design basis event, meanwhile the impact of its damage does not require
protective action, the cables or wiring channels of the safety class or associated
circuits laid in the area shall be limited to the same division as the missile source.
d) If the relevant missile source has not been qualified by the design basis event,
In the fire hazardous area, the cables or wiring channels for laying safety-class or
associated circuits shall meet the following requirements.
a) If the relevant fire hazard source does not belong to a single division and is
qualified by the design basis event, meanwhile the impact of its damage does not
require protective action, the cables or wiring channels for the safety-class or
associated circuits laid in the area shall be limited to a single division.
b) If protective action is required for the impact caused by the fire hazard source,
except for the cables that shall be terminated to the devices or loads in the area
[special measures (such as increasing redundancy or diversity) may be required
for these cables to meet the single fault criterion], cables or wiring channels for
other safety-class or associated circuits shall not be laid in the area.
c) If the relevant fire hazard source belongs to a single division and has been
qualified by the design basis event, meanwhile the impact of its damage does not
require protective action, the cables or wiring channels of the safety class or
associated circuits laid in the area shall be limited to the same division as the fire
hazard source.
d) If the relevant fire hazard source has not been qualified by the design basis event,
except for the cables that shall be terminated to the devices or loads in the area,
other cables or wiring channels of the safety class or associated circuits shall not
be laid in the area. When the area where the cables or wiring channels of the safety
class and associated circuits are laid is designated as a hazardous area due to the
presence of fire hazards not related to nuclear safety, these cables or wiring
channels shall be protected in accordance with the methods specified in 5.1.8.2,
to avoid the impact of the area.
5.1.9 Optical fiber loop
5.1.9.1 General
Optical fiber loops will not cause degradation of other optical fiber loops or live circuits.
Therefore, if the optical fiber loop is used as a fault source cable, there is no isolation
requirement. If the optical fiber loop is used as an affected cable, it shall meet the
isolation criteria requirements of 5.1.9.2. For more discussion on optical fiber loops,
see Appendix A.
5.1.9.2 Separation distance
In non-hazardous areas, there is no isolation distance requirement between the optical
fiber circuit of the safety-class division and the optical fiber circuit of its redundant
division. There is no isolation distance requirement between the safety-class optical
fiber circuit and the non-safety-class optical fiber circuit.
If the optical fiber circuit is used as the affected cable and the live circuit is used as the
The auxiliary equipment and local control devices of the redundant standby generator
set shall be arranged in a structure with the same safety class as the unit; otherwise, they
shall be physically separated in accordance with the requirements of Chapter 4.
5.3 DC system
5.3.1 Batteries
Redundant safety-class batteries shall be arranged in separated safety-class structures.
5.3.2 Battery chargers
The chargers of safety-class redundant batteries shall be physically separated in
accordance with the requirements of Chapter 4.
5.4 Power distribution system
5.4.1 Switchgear
The division of redundant safety-class distribution switchgear shall be physically
separated in accordance with the requirements of Chapter 4.
5.4.2 Motor control center
Redundant safety-class motor control center shall be physically separated in accordance
with the requirements of Chapter 4.
5.4.3 Switchboard
Redundant safety-class switchboards shall be physically separated in accordance with
the requirements of Chapter 4.
5.5 Containment electrical penetrations
Redundant safety-class containment electrical penetrations shall be physically
separated in accordance with the requirements of Chapter 4; redundant penetrations are
generally required to be widely distributed around the circumference of the containment.
The minimum physical separation distance of redundant penetrations shall meet the
requirements of 5.1.4 and 5.1.5 for cables and wiring channels.
Non-safety-class circuits passing through safety-class circuit penetrations shall be
handled in accordance with the requirements of 4.5 for associated circuits.
5.6 Control cabinets
5.6.1 Location and layout
The main control cabinet shall be arranged in a non-hazardous area within the safety-
class structure. The local control cabinet shall be arranged in accordance with the
requirements of 5.1.
Redundant safety-class equipment and circuits may be arranged in a control cabinet
physically separated in accordance with the requirements of 5.1 to be separated. From
the operational perspective, when redundant safety-class equipment or safety-class
equipment is placed in the same control cabinet or box with non-safety-class equipment,
the requirements of 5.6.2 ~ 5.6.6 shall be met.
5.6.2 Internal separation
5.6.2.1 In the control cabinet, the minimum separation distance required by Chapter 4
can be determined based on the analysis of the proposed installation method. This
analysis shall be based on tests, the purpose of which is to determine the flame retardant
properties of the wiring method, wire materials, equipment and other materials inside
the control switch cabinet. Considering the overall safety function of the circuit,
sufficient separation distance can be determined when the impact of the source cable
on the target cable is acceptable.
If the above analysis is not performed and the material of the control switch cabinet is
flaming retardant, when only live circuits are involved, the minimum horizontal
separation distance is 2.5 cm and the minimum vertical separation distance is 15.0 cm.
The minimum vertical separation distance can be reduced to 2.5 cm, if the wiring can
withstand the following worst transient conditions:
a) Heating of non-safety-class wires will not cause the wires to sag and touch safety-
class wires or components;
b) Heating of safety-class wires will not cause the wires to sag and touch safety-class
wires or components of redundant divisions.
Acceptable wire fixing methods include using stainless steel ties or other metal brackets
to fix the wires every 15.0 cm along the wires.
5.6.2.2 When fiber optic circuits are involved, the following isolation guidelines must
be followed:
a) There is no isolation distance requirement between the fiber optic circuit of the
safety-class division and the fiber optic circuit of its redundant division;
b) There is no isolation distance requirement between the safety-class fiber optic
circuit and the non-safety-class fiber optic circuit;
c) The isolation distance between the fiber optic circuit and the live circuit shall meet
the isolation distance requirements of Table 3.
If the above isolation distance cannot be maintained, partitions shall be installed
...... Source: Above contents are excerpted from the full-copy PDF -- translated/reviewed by: www.ChineseStandard.net / Wayne Zheng et al.
Tips & Frequently Asked QuestionsQuestion 1: How long will the true-PDF of English version of GB/T 13286-2021 be delivered?Answer: The full copy PDF of English version of GB/T 13286-2021 can be downloaded in 9 seconds, and it will also be emailed to you in 9 seconds (double mechanisms to ensure the delivery reliably), with PDF-invoice. Question 2: Can I share the purchased PDF of GB/T 13286-2021_English with my colleagues?Answer: Yes. The purchased PDF of GB/T 13286-2021_English will be deemed to be sold to your employer/organization who actually paid for it, including your colleagues and your employer's intranet. Question 3: Does the price include tax/VAT?Answer: Yes. Our tax invoice, downloaded/delivered in 9 seconds, includes all tax/VAT and complies with 100+ countries' tax regulations (tax exempted in 100+ countries) -- See Avoidance of Double Taxation Agreements (DTAs): List of DTAs signed between Singapore and 100+ countriesQuestion 4: Do you accept my currency other than USD?Answer: Yes. www.ChineseStandard.us -- GB/T 13286-2021 -- Click this link and select your country/currency to pay, the exact amount in your currency will be printed on the invoice. Full PDF will also be downloaded/emailed in 9 seconds. Question 5: Should I purchase the latest version GB/T 13286-2021?Answer: Yes. Unless special scenarios such as technical constraints or academic study, you should always prioritize to purchase the latest version GB/T 13286-2021 even if the enforcement date is in future. Complying with the latest version means that, by default, it also complies with all the earlier versions, technically.
How to buy and download a true PDF of English version of GB/T 13286-2021?A step-by-step guide to download PDF of GB/T 13286-2021_EnglishStep 1: Visit website https://www.ChineseStandard.net (Pay in USD), or https://www.ChineseStandard.us (Pay in any currencies such as Euro, KRW, JPY, AUD). Step 2: Search keyword "GB/T 13286-2021". Step 3: Click "Add to Cart". If multiple PDFs are required, repeat steps 2 and 3 to add up to 12 PDFs to cart. Step 4: Select payment option (Via payment agents Stripe or PayPal). Step 5: Customize Tax Invoice -- Fill up your email etc. Step 6: Click "Checkout". Step 7: Make payment by credit card, PayPal, Google Pay etc. After the payment is completed and in 9 seconds, you will receive 2 emails attached with the purchased PDFs and PDF-invoice, respectively. Step 8: Optional -- Go to download PDF. Step 9: Optional -- Click Open/Download PDF to download PDFs and invoice. See screenshots for above steps: Steps 1~3 Steps 4~6 Step 7 Step 8 Step 9
|